Plan Review Notes
Plan Review Notes For Permit 08070134
Permit Number 08070134
Review Stop E
Sequence Number 2
Notes
Date Text
2008-08-26 13:37:38 
  
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
  
  
 1) NOTE: PLEASE SEE THE COVER SHEET WHICH STATES
 CHAPTER 13 OF THE FLORIDA BUILDING CODE FOR
 ACCESSIBILITY. THIS NEEDS TO BE CHAPTER 11. IF THIS
 WERE THE ONLY COMMENT THE PLANS COULD BE REDLINED
 HOWEVER THERE ARE OTHER COMMENTS BELOW WHICH ARE IN
 NEED OF ADDRESSING.
  
 2) NOTE: PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER IS STILL MISSING FROM ALL
 NOTATIONS OF ENGINEERING FIRM(S). PLEASE SEE COVER
 SHEET WHICH STILL SHOWS HALLBERG ENGINEERING. THIS IS
 SHOWN FOR ELECTRICAL AND OTHER TRADES.
 PLEASE ALSO SEE THE FIRE PROTECTION SHEETS WHICH STILL
 CONTAIN ARCHITECTURAL FIRM INFORMATION WHICH WOULD
 REQUIRE THE CERTIFICATE OF AUTHORIZATION NUMBER.
  
 FAC 61G15-23.002, FS 471.023 FOR ENGINEERS
 FAC61G1-16.004, FS 481.219 FOR ARCHITECTS.
  
 ** THESE ARE REQUIRED FOR ALL TRADES AND FOR ALL
 LOCATIONS ON PLANS WHETHER OR NOT COMMENT IS MADE BY
 THOSE OTHER TRADE REVIEWER(S).
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES FOR LIGHTING
 CONTROLS REQUIRED PER FBC 13-415.1.ABC.1.1, .1.2 AND
 .1.3. PLEASE SEE PLANS AS THERE ARE LOCATIONS IN WHICH
 ARE CONSIDERED SEPARATE SPACES AND ONLY STANDARD SINGLE
 POLE DEVICES ARE SHOWN. THESE ARE NOT ACCEPTABLE AND
 REQUIRE SOME SORT OF AUTOMATED MEANS FOR CONTROLLING
 LIGHTING. IF A SYSTEM IS PROVIDED THEN SEPARATE
 CONTROLS OF OVER RIDING THAT SYSTEM IS REQUIRED.
 PLEASE SEE OTHER AREAS SUCH AS STAGING AREA WHICH ONLY
 SEEMS TO SHOW ONE OCCUPANCY SENSOR TYPE DEVICE. PLEASE
 PROVIDE SPECS ON THIS PROPOSED DEVICE WHICH WILL
 PROVIDE COMPLETE COVERAGE OF THE OVER RIDE FUNCTION.
  
 4) NOTE: PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON
 PLANS AND CLEARLY INDICATE EACH FIXTURE. FOR EXAMPLE
 SOME FIXTURES SUCH AS THE CORELIGHT BRAND DOES NOT
 INDICATE ANY CLEAR DELINEATION OF THE FIXTURE. THE
 FIXTURE LEGEND NOTES A CERTAIN LENGTH HOWEVER BASED ON
 PLANS AND SCALE SHOWN THE LINEAR FEET OF FIXTURES IS
 SUBSTANTIALLY MORE THAN WHAT IS LISTED ON LEGEND. THIS
 IS ALSO NOTED FOR OTHER FIXTURES SUCH AS THE TRACK
 FIXTURE.
 PLEASE SEE THE INPUT DATA REPORT SUBMITTED DOES NOT
 COORDINATE WITH PLANS. IN FACT THERE ARE FIXTURES SHOWN
 ON PLANS WHICH ARE NOT IN THE INPUT DATA REPORT AT ALL.
  
 ONE EXAMPLE OF THIS IS THE EXTERIOR LIGHTING SHOWN IN
 THE IDR. THE LAST REVIEW OF THESE DOCUMENTS DID NOT
 INDICATE ANY FIXTURES AND NOW THE FIXTURE WHICH ARE
 SHOWN IN THE IDR ARE NOT THE SAME AS FIXTURES ON PLANS.
 IN FACT THERE ARE 250WATT FIXTURES AND 300WATT
 FIXTURE(S) WHICH ARE NOT IN THE IDR AT ALL AND YET
 THESE ARE ON PLANS.
  
 ANOTHER EXAMPLE IS THE INTERIOR LIGHTS WHICH NEED TO
 COORDINATE ALL ZONES AND SPACES. ONE OF THESE IS THE
 DESIGNATIONS OF *OFFICES*. THE IDR SHOWS 23 FIXTURES IN
 OFFICES AND BASED ON THE SHEET A-2, THERE ARE ONLY TWO
 OFFICES AND BOTH OF THEM TOGETHER DO NOT CONTAIN 23
 FIXTURES.
 HOW ARE THESE THINGS POSSIBLE?
 PLEASE COORDINATE ALL LIGHTING FIXTURES ON PLANS WITH
 THE ALLOWANCES. PLEASE SEE TABLE *C* IN 13-415.2.C. IF
 *C* METHOD IS CHOSEN THEN THE LIGHTING WATTAGE PER SQ
 FT OF THE ENTIRE SPACE MAY NOT EXCEED THE LEVEL OF 1.5
 WATTS PER SQUARE FOOT.
 THIS IS NOT AN EXHAUSTED LIST AS THERE ARE OTHER
 INCONSISTENCIES. PLEASE BE SURE TO COORDINATE ALL AND
 CALL TO GO OVER HOW TO SHOW COMPLIANCE.
  
 *** PLEASE SEE 13-415.2.ABC.1.1,.1.2,.1.3, 13-415.2.B,
 13-415.2.C ETC.
  
 5) NOTE: PLEASE COORDINATE AND COMPLETE ALL ROOM AND
 AREA DESIGNATIONS AS SHOWN ON A-2 WITH THAT OF
 ELECTRICAL PLANS. ONE EXAMPLE OF THIS IS ROOM 114 WHICH
 ON THE A2 SHEET IS SHOWN AS AN ELECTRICAL ROOM AND
 NOTES EQUIPMENT ETC. HOWEVER BASED ON THE ELECTRICAL
 PLANS THIS SAME ROOM DOES NOT SHOW ANY ELECTRICAL
 EQUIPMENT.
  
 110.26, 240.24, 408.17 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 6) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW THE
 WORST CASE VOLTAGE DROP NEEDS TO BE SHOWN FOR BRANCH
 CIRCUIT(S). THE PLANS ONLY CHANGED TO QUOTE THE
 REQUIREMENT AND DID NOT PROVIDE THE INFORMATION.
 RESPONSE LETTER MENTIONS THIS WAS DONE AND COULD BE
 FOUND ON E-2 HOWEVER NO VOLTAGE DROP CALCULATION WAS
 PLACED ON PLANS.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]