| Date |
Text |
| 2008-07-22 13:57:11 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A0 DEMOLITION PLAN, KEYED NOTES #3 STATES |
| | "REMOVE EXISTING RESTROOM FIXTURES", HOWEVER SHEET A2 |
| | FLOOR PLAN IN WOMENS #111 AND MENS #112 BATHROOM |
| | HANDICAP STALLS THE LAVATORIES ARE NOT BEING |
| | REINSTALLED. PER FBC-2004 CHAPTER 11, FLORIDA |
| | ACCESSIBILITY CODE SECTION 11-4.17.3 EXCEPTIONS |
| | (1)(2). |
| | |
| | (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL |
| | CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF |
| | SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17 |
| | INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL |
| | MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO |
| | OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION |
| | 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO |
| | COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH |
| | LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED |
| | FIXTURE COUNT FOR THE BUILDING. |
| | (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN |
| | THE CORNER, DIAGONAL TO THE DOOR. |
| | |
| | 2. SHEET A7 DETAIL 1, ENLARGED RESTROOM: CLEARLY |
| | INDICATE THE CLEAR FLOOR SPACE AND WHEELCHAIR TURNING |
| | SPACE FOR THE FOLLOWING FIXTURES ON THE DETAIL |
| | COMPLIANT WITH FBC-2004 CHAPTER 11, FLORIDA |
| | ACCESSIBILITY CODE THE FOLLOWING SECTIONS. |
| | A} SECTION 11-4.15.5 CLEARANCES, DRINKING FOUNTAIN |
| | (30"X48"). |
| | B} SECTION 11-4.16.2 CLEAR FLOOR SPACE, WATER CLOSETS |
| | (SEE FIGURE 28). |
| | C} SECTION 11-4.18.3 CLEAR FLOOR SPACE, URINALS |
| | (30"X48"). |
| | D} SECTION 11-4.19.3 CLEAR FLOOR SPACE, LAVATORIES |
| | (30"X48" AND SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH |
| | THE LAVATORY). |
| | E} SECTION 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR |
| | TURNING SPACE SHALL BE 180-DEGREE WITH A MINIMUM 60" |
| | CLEAR FLOOR SPACE. (CLEARLY INDICATE TURNING SPACE IN |
| | BATHROOM, BATHROOM ACCESSIBLE STALLS, AND DRINKING |
| | FOUNTAIN ROOM) |
| | |
| | 3. SHEET A7 DETAIL 4, ENLARGED OFFICE/BREAKROON PLAN: |
| | CLEARLY INDICATE THE CLEAR FLOOR SPACE AND WHEELCHAIR |
| | TURNING SPACE FOR THE BREAKROOM SINK ON THE DETAIL |
| | COMPLIANT WITH FBC-2004 CHAPTER 11, FLORIDA |
| | ACCESSIBILITY CODE THE FOLLOWING SECTIONS. |
| | A} SECTION 11-4.24.5 CLEAR FLOOR SPACE, SINK (30"X48" |
| | AND CLEAR FLOOR SPACE SHALL EXTEND A MAXIMUM OF 19" |
| | UNDERNEATH THE SINK). |
| | B} SECTION 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR |
| | TURNING SPACE SHALL BE 180-DEGREE WITH A MAIMUM 60" |
| | CLEAR FLOOR SPACE. |
| | |
| | 4. SHEET MP-1 NOTES LOCATED BELOW PLUMBING FIXTURE |
| | SCHEDULE: PLEASE ADD THE FOLLOWING FOR THE HC |
| | ACCESSIBLE URINAL COMPLIANT WITH FBC-2004 CHAPTER 11, |
| | FLORIDA ACCESSIBILITY CODE SECTION 11-4.18.4 FLUSH |
| | CONTROL FOR THE URINAL MAXIMUM 44" A.F.F. |
| | |
| | 5. SHEET MP-2 DETAIL 3, WATER RISER DIAGRAM: THE 12" |
| | AIR CHAMBERS SPECIFIED IN THE DETAIL ARE NOT COMPLIANT |
| | WITH THE FBC-2004 PLUMBING, SECTION 604.9 WATER HAMMER. |
| | PER 604.9, A WATER-HAMMER ARRESTOR SHALL BE INSTALLED |
| | WHERE QUICK CLOSING VALVES ARE UTILIZED. PLEASE DELETE |
| | THE 12" AIR CHAMBERS ON THE RESUBMITTAL. |
| | |
| | 6. SHEET MP-2 DETAIL 5, WATER HEATER DETAIL: CLEARLY |
| | INDICATE THE FOLLOWING ON THE WATER HEATER DETAIL |
| | COMPLIANT WITH THE FBC-2004 PLUMBING SECTIONS. |
| | A} SECTION 504.4 RELEIF VALVE. |
| | B} SECTION 504.5 RELIEF VALVE APPROVAL. |
| | C} SECTION 504.6 RELIEF OUTLET WASTE. |
| | D} SECTION 504.6.1 DISCHARGE. |
| | E} SECTION 607.3 THERMAL EXPANSION CONTROL. |
| | |
| | 7. ALL MP SHEETS FROM MP-1 THRU MP2.1 REQUIRE A |
| | CERTIFICATE OF AUTHORIZATION NUMBER ON THESE SHEETS. |
| | PER FAC 61G15-23.002(2). |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |