Plan Review Notes
Plan Review Notes For Permit 08070134
Permit Number 08070134
Review Stop M
Sequence Number 1
Notes
Date Text
2008-07-21 16:27:58REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 ADMINISTRATIVE COMMENTS:
  
 1. PG CVR: IN THE CODE REVIEW SECTION, PLEASE NOTE THE
 FOLLOWING DISCREPANCIES:
 ITEM #4 SHOULD BE: 2005 NATIONAL ELECTRICAL CODE
 ITEM #5 SHOULD BE: 2003 FLORIDA FIRE PREVENTION CODE?
 ITEM #7 SHOULD BE: 2004 FLORIDA BUILDING CODE, BUILDING
 CHAPTER 13.
 ITEM #9 SHOULD BE: WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT / 561-805-6700
 ITEM #11 SHOULD BE: WEST PALM BEACH FIRE DEPARTMENT /
 561-804-4724
  
 2. PAGES CVR, IND AND ALL A PAGES: THESE PAGES (ON ONE
 OF THE TWO SETS SUBMITTED) DO NOT CONTAIN ORIGINAL
 SIGNATURE AND RAISED SEAL OF THE ARCHITECT. RATHER THEY
 CONTAIN WHAT APPEARS TO BE A PRINTED SEAL AND
 PHOTOCOPIED SIGNATURE. PLANS AND SPECIFICATIONS SHALL
 BE SIGNED AND SEALED BY THE DESIGNER OF RECORD IN
 ACCORDANCE WIT FBCB 106.1, FS 481 AND FAC RULE
 61G1-16.
  
 3. PAGE CVR: THIS IS AN EXISTING BUILDING. THE DESIGN
 PROFESSIONAL MUST ELECT ONE OR A COMBINATION OF LEVELS
 OF ALTERATION IN ACCORDANCE WITH FBCEB 301.5.
  
 4. PAGES MP, E AND FP: A TITLE BLOCK SHALL BE USED ON
 EACH SHEET CONTAINING THE PRINTED NAME, ADDRESS, AND
 LICENSE NUMBER OF THE ENGINEER, AND IF PRACTICING
 THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS IN ACCORDANCE WITH FAC RULE
 61G15-23.002(2).
  
 CODE COMMENTS:
  
 5. PG MP-1: THE AIR DISTRIBUTION DEVICE SCHEDULE
 REMARKS FOR SD1 AND SD2 REFER TO A DETAIL ON PAGE
 MP-1.3. PAGE MP-1.3 IS NOT INCLUDED IN THE SUBMITTED
 PLANS. PLEASE SHOW WHERE THIS INFORMATION CAN BE FOUND.
 FBCM 603.1, FBCM 106.1.1.
  
 6. PG MP-1: PROVIDE OUTSIDE AIR CALCULATIONS SHOWING
 OCCUPANCY CLASSIFICATIONS, OCCUPANT LOADS, REQUIRED
 VENTILATION RATES AND AMOUNTS PROVIDED IN ACCORDANCE
 WITH FBCM 403.3 OR 403.4.
  
 7. PG MP-1: EF SCHEDULE NOTE #1 CALLS FOR EF-1 TO BE
 INTELOCKED WITH LIGHT SWITCH IN BATHROOMS. THIS FAN
 NEEDS TO RUN WHENEVER RTU-2 IS RUNNING (WHETHER OR NOT
 LIGHT SWITCH IS ON) AS RECIRCULATION OF AIR FROM THESE
 SPACES IS PROHIBITED AND ALL AIR SUPPLIED TO THE
 BATHROOMS SHALL BE EXHAUSTED IN ACCORDANCE WITH FBCM
 403.2.1(3).
  
 8. PG MP-1.1: FLOOR PLAN SHOWS A 20X14 SUPPLY DUCT AND
 AN 18X12 RETURN DUCT, BOTH FROM RTU-5, PENETRATING A
 2-HOUR FIRE RESISTANCE RATED WALL. THESE PENETRATIONS
 ARE REQUIRED TO BE PROTECTED WITH FIRE DAMPERS IN
 ACCORDANCE WITH FBCM 607.5. SHOW HOW THESE DUCT
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 THIS SECTION. THE RATED DUCT PENETRATION DETAIL #6 ON
 PAGE MP-1.2 IS NOT APPLICABLE AS IT IS RATED FOR 1-HOUR
 (THE WALL IS 2-HOUR) AND THE SIZES OF THE PENETRATING
 DUCTS EXCEED THE MAXIMUM ALLOWED IN THE INSTRUCTIONS
 WHICH ACCOMPANY THE THROUGH-PENETRATION DETAIL.
  
 9. PG MP-1.1: SEVERAL DUCT BRANCHES DO NOT HAVE SIZES
 SHOWN ON FLOOR PLAN. SOME OF THESE BRANCH SISZES CAN BE
 DETERMINED BASED ON THE NECK SIZE SHOWN ON THE AIR
 DISTRIBUTION SCHEDULE BUT SOME CAN NOT. EXAMPLE: PLEASE
 SHOW ON PLANS THE SIZES OF THE TRANSFER DUCTS AT
 RESTROOM VESTIBULE 114. PLEASE CHECK PLANS FOR ALL
 DUCTS WHICH ARE MISSING SIZES ON PLANS AND PROVIDE THE
 MISSING INFORMATION. AIR DISTRIBUTION SYSTEMS SHALL BE
 DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
  
  
 10. PG MP-1.2: CURB AND HURRICANE STRAP DETAILS CONTAIN
 CONFLICTING INFORMATION. PLEASE COORDINATE DETAILS AND
 CLARIFY THE WIND RESISTANCE METHOD TO BE USED FOR CURB,
 RTU AND EXHAUST FANS. PROVIDE WIND LOAD CALCULATIONS
 FOR OVERTURN AND UPLIFT FOR ALL ROOFTOP APPLIANCES FOR
 BUILDING REVIEW IN ACCORDANCE WITH FBCM 301.13.
  
 11. PG MP-1.2: IN ADDITION TO THE COMMENTS ABOVE,
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING PER FBCM 301.13. PROVIDE SUPPORTING
 DOCUMENTATION FROM THE APPLIANCE MANUFACTURER SHOWING
 THESE RTU?S AND EXHAUST FANS ARE DESIGNED TO RESIST
 WIND PRESSURES IN ACCORDANCE WITH THIS SECTION. PLEASE
 NOTE THAT THIS REQUIREMENT APPLIES TO THE CONSTRUCTION
 OF THE APPLIANCES THEMSELVES AND NOT JUST THE
 ATTACHMENT TO THE BUILDING STRUCTURE.
  
 12. PG MP-2.1 CONDENSATE DRAIN DETAIL: AUXILIARY OR
 SECONDARY DRAIN PROTECTION IS REQUIRED IN ACCORDANCE
 WITH FBCM 307.2.3. A FLOAT SWITCH MAY BE INSTALLED
 INSIDE THE RTU ON THE PRIMARY DRAIN PAN TO COMPLY WITH
 THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]