| 2008-07-31 14:14:16 | ***DENIED*** |
| | |
| | 1) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHEET FA-1 |
| | NOTE C-1 |
| | |
| | 2) FIRE ALARM SYSTEM TO BE UL CERTIFICATED FOR CENTRAL |
| | STATION SERVICE. PROVIDE NOTE WITH SPECIFIC LANGUAGE ON |
| | FA SHEET. |
| | |
| | 3) FIRE ALARM SHALL BE CLASS A OR FULLY ADDRESSABLE. |
| | |
| | 4) DUCT SMOKE DETECTORS REQUIRED IN SUPPLY DUCT WHERE |
| | UNIT IS GREATER THAN 2000 CFM UNLESS REQUIRED IN SUPPLY |
| | AND RETURN FOR LARGER UNITS. FA-1 NOTE 22. |
| | |
| | 5) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE |
| | SAFETY TO COMPLY WITH NFPA 101, 2003. CONSTRUCTION, |
| | ALTERATION AND DEMOLITION TO COMPLY WITH NFPA 241. |
| | PLEASE ADD TO CODE REVIEW ON SHEET CVR. |
| | |
| | 6) PHYSICAL ADDRESS REQUIRED ON EACH SHEET. |
| | |
| | 7) PHONE NUMBER FOR WEST PALM BEACH FIRE RESCUE IS |
| | INCORRECT. THE CORRECT NUMBER IS (561) 804-4700. SHEET |
| | CVR |
| | |
| | 8) PROVIDE LIFE SAFETY PLAN ILLUSTRATING REQUIRED MEANS |
| | OF EGRESS AND TRAVEL DISTANCES. |
| | |
| | 9) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR |
| | WALLS AND CEILING THAT COMPLIES WITH NFPA 101, |
| | CHAPTER-10. |
| | |
| | 10) INDICATE ANY DOORS THAT ARE FIRE RATED AND PROVIDE |
| | RATING IN MINUTES IN DOOR SCHEDULE. IN ADDITION, RATED |
| | DOORS SHALL BE PROVIDED WITH UL LISTED DOOR CLOSERS. |
| | |
| | 11) ADDRESS REQUIRED ON BUILDING THAT SHALL BE MINIMUM |
| | OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH |
| | BACKGROUND FOR COMMERCIAL BUILDINGS. |
| | |
| | 12) KNOX BOX IS REQUIRED ON BUILDING FOR AFTER NORMAL |
| | BUSINESS HOURS EMERGENCY ACCESS. CONTACT WPBFR BUREAU |
| | OF FIRE PREVENTION AT (561) 804-4724 FOR ASSISTANCE. |
| | |
| | 13) PLEASE EXPLAIN NOTES ON SHEET FP-1 REFERENCING FLOW |
| | TEST RESULTS TAKEN BY TVA FIRE AND LIFE SAFETY? |
| | |
| | 14) IF FIRE DEPARTMENT CONNECTION FOR PROJECT IS NEW, |
| | KNOX LOCKING CAPS ARE REQUIRED. |
| | |
| | |
| | A RESPONSE LETTER INDICATING HOW AND WHERE ON PLANS |
| | COMMENTS HAVE BEEN ADDRESSED WOULD HELP EXPEDITE THE |
| | PLAN REVIEW PROCESS. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |