Plan Review Notes
Plan Review Notes For Permit 08070134
Permit Number 08070134
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-07-31 14:14:16***DENIED***
  
 1) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHEET FA-1
 NOTE C-1
  
 2) FIRE ALARM SYSTEM TO BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE. PROVIDE NOTE WITH SPECIFIC LANGUAGE ON
 FA SHEET.
  
 3) FIRE ALARM SHALL BE CLASS A OR FULLY ADDRESSABLE.
  
 4) DUCT SMOKE DETECTORS REQUIRED IN SUPPLY DUCT WHERE
 UNIT IS GREATER THAN 2000 CFM UNLESS REQUIRED IN SUPPLY
 AND RETURN FOR LARGER UNITS. FA-1 NOTE 22.
  
 5) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003. CONSTRUCTION,
 ALTERATION AND DEMOLITION TO COMPLY WITH NFPA 241.
 PLEASE ADD TO CODE REVIEW ON SHEET CVR.
  
 6) PHYSICAL ADDRESS REQUIRED ON EACH SHEET.
  
 7) PHONE NUMBER FOR WEST PALM BEACH FIRE RESCUE IS
 INCORRECT. THE CORRECT NUMBER IS (561) 804-4700. SHEET
 CVR
  
 8) PROVIDE LIFE SAFETY PLAN ILLUSTRATING REQUIRED MEANS
 OF EGRESS AND TRAVEL DISTANCES.
  
 9) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING THAT COMPLIES WITH NFPA 101,
 CHAPTER-10.
  
 10) INDICATE ANY DOORS THAT ARE FIRE RATED AND PROVIDE
 RATING IN MINUTES IN DOOR SCHEDULE. IN ADDITION, RATED
 DOORS SHALL BE PROVIDED WITH UL LISTED DOOR CLOSERS.
  
 11) ADDRESS REQUIRED ON BUILDING THAT SHALL BE MINIMUM
 OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH
 BACKGROUND FOR COMMERCIAL BUILDINGS.
  
 12) KNOX BOX IS REQUIRED ON BUILDING FOR AFTER NORMAL
 BUSINESS HOURS EMERGENCY ACCESS. CONTACT WPBFR BUREAU
 OF FIRE PREVENTION AT (561) 804-4724 FOR ASSISTANCE.
  
 13) PLEASE EXPLAIN NOTES ON SHEET FP-1 REFERENCING FLOW
 TEST RESULTS TAKEN BY TVA FIRE AND LIFE SAFETY?
  
 14) IF FIRE DEPARTMENT CONNECTION FOR PROJECT IS NEW,
 KNOX LOCKING CAPS ARE REQUIRED.
  
  
 A RESPONSE LETTER INDICATING HOW AND WHERE ON PLANS
 COMMENTS HAVE BEEN ADDRESSED WOULD HELP EXPEDITE THE
 PLAN REVIEW PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  
  
  