Plan Review Notes
Plan Review Notes For Permit 08070134
Permit Number 08070134
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-29 09:52:49 
 ** DENIEDREVIEW **
  
  
 1) NOTE:PLEASE SEE THE JURISDICTION IN WHICH THIS
 SCOPE OF WORK HAS BEEN APPLIED IN LOCATED IN THE CITY
 OF WEST PALM BEACH, FLORIDA. THERE ARE REFERENCES ON
 PLANS TO PALM BEACH COUNTY BUILDING DEPARTMENT. PLEASE
 ADJUST.
  
 2) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON PLANS INCLUSIVE OF ARCHITECTURAL PLANS AS WELL AS
 ELECTRICAL SHEETS.
 SOME CODES LISTED SUCH AS THE 2004 ELECTRICAL CODE AND
 2002 LIFE SAFETY CODE DO NOT EXIST. PLEASE SEE THE
 PLANS ALSO INDICATE THE *COMMONWEALTH OF MASSACHUSETTS*
 FOR THE ENERGY CODE. THE FLORIDA BUILDING CODE CHAPTER
 13 IS THE STATE OF FLORIDA ENERGY CODE.
 PLEASE ADJUST.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2004 FBC W/2007 REVISIONS.
  
 3) NOTE: PLEASE SEE THE MISSING INFORMATION ON THE
 TITLE BLOCKS ON FIRE ALARM PLANS. THE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 REQUIRES THE PRINTED
 NAME, PRINTED LICENSE NUMBER OF THE ENGINEER ALONG WITH
 THE REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE FLORIDA STATUTES 471.023 FOR THE REQUIREMENT
 OF LICENSING FOR FIRM.
  
 4) NOTE: PLEASE SEE COMMENT #3 ABOVE THE MEP PLANS ARE
 ALSO MISSING THE REQUIRED INFORMATION TO BE COMPLETED
 ON TITLE BLOCKS.
 THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER IS ALSO
 REQUIRED.
 FAC 61G15-23.002, FS 471.023.
  
 5) NOTE: PLEASE SUBMIT THE COMPLETE PERFORMANCE
 CALCULATIONS AS REQUIRED PER 13-415.2.ABC.1.1, .1.2,
 .1.3, 13-415.2.
 PLEASE SEE THE SQUARE FOOTAGE SHOWN ON THE CALCULATIONS
 AS SUBMITTED ARE LESS THAN THE SQ FT SHOWN ON
 ARCHITECTURAL PLANS.
 PLEASE SEE THE SUBMITTED CALCULATIONS ALONG WITH THE
 INPUT DATA REPORT DO NOT COORDINATE WITH PLANS. ALL
 FIXTURE WATTAGES, FIXTURE COUNTS ETC NEED TO MATCH WITH
 PLANS.
 IN FACT PLEASE SEE THE INPUT DATA REPORT. SOME ITEMS IN
 THE IDR ARE BLANK. HOW IS THIS POSSIBLE WHEN THESE
 ITEMS ARE IN FACT ON PLANS.
 JUST ONE EXAMPLE OF THIS IS THE EXTERIOR LIGHTING ON
 THE IDR. THIS IS BLANK WITH NO INPUT.
 ** THIS IS ONE EXAMPLE ONLY.
  
 **PLEASE NOTE: THE PERSON AS SIGNED ON THE
 CERTIFICATION SHEET OF THE ENERGY CALCULATIONS AS THE
 *PREPARER* IS NOT LISTED AS ONE OF THE ENGINEERS OF
 RECORD. AS THE SCOPE OF WORK FALLS UNDER THE
 REQUIREMENTS OF AN ENGINEER THIS PERSON MUST BE
 LICENSED IN THE STATE OF FLORIDA AS SUCH.
 PLEASE PROVIDE LICENSE INFORMATION FOR SAID PREPARER
 MR. TREVOR GILBERTSON.
 13-103.1, FS 471.003
  
 6) NOTE: PLEASE SUBMIT PLANS COMPLYING WITH THE FBC
 CHAPTER 13 FOR LIGHTING CONTROLS. THE EMS SYSTEM AS
 SUBMITTED DOES NOT COMPLETELY COMPLY WITH THE FOLLOWING
 SECTIONS. 13-415.1.ABC.1.1,.1.2, .1.3.
 PLEASE SEE NO OVER RIDES FOR OCCUPANTS COULD BE LOCATED
 ON PLANS.
 PLEASE SUBMIT ALL MAXIMUM TIMES ON OVER RIDES AND SPACE
 CONTROLS.
 PLEASE SEE NO SEPARATE SPACE CONTROLS ARE SHOWN ON
 PLANS. THE STANDARD DEVICES AS SHOWN DO NOT COMPLY WITH
 13-415.1.ABC.1.2.
 PLEASE COMPLETE LIGHTING CONTROLS AND CIRCUITING FOR
 CONTACTOR SCHEDULES. PLEASE KNOW THIS MAY CHANGE BASED
 ON THE NOTES ABOVE WITH THE SYSTEM DESIGN AT PRESENT.
 ** AS A COMPLETE SYSTEM AND MANY DEVICES ARE NOT SHOWN
 THERE MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 7) NOTE: PLEASE INCLUDE NOTES ON PLANS PER
 13-413.1.ABC.2.1
 DRAWINGS.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30
 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD
 DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED
 TO THE BUILDING OWNER, INCLUDING:
 1. A SINGLE-LINE DIAGRAM OF THE BUILDING ELECTRICAL
 DISTRIBUTION SYSTEM AND
 2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR
 ALL DISTRIBUTION.
 13-413.1.ABC.2.2 MANUALS.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING
 MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE
 BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A
 MINIMUM, THE FOLLOWING:
 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED
 OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING
 MAINTENANCE.
 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH
 PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED
 ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY
 IDENTIFIED.
 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED
 SERVICE AGENCY.
  
 8) NOTE: PLEASE INCLUDE WORST CASE VOLTAGE DROP PER
 13-413.1.ABC.1.1 AND .1.2.
  
 9) NOTE: PLEASE INCLUDE REQUIRED MINIMUM FOR ADA
 COMPLIANCE FOR FIRE ALARM DEVICES INCLUSIVE OF ALL
 LEVELS LISTED IN 11-4.28.1, .2 AND .3 OF THE FLORIDA
 BUILDING CODE.
  
 10) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF THE
 EMERGENCY LIGHTS AND EXIT LIGHTS TO THE LOCAL LIGHTING
 BRANCH CIRCUITS. THE PLANS CALL FOR A LOCK OFF BREAKER
 TO MEET THE EXCEPTION IN THE NEC. PLEASE KNOW THE LOCK
 OFF BREAKER SHALL HAVE THE LOCK OFF MECHANISM PART OF
 THE BREAKER. THE *SNAP* ON OR *CLIP* ON TYPE LOCK OFF
 DEVICES ARE NOT ACCEPTABLE. PLEASE BE SURE TO CHECK THE
 LISTING OF THE UNIT IN DESIGN FOR *PERMANENT*
 INSTALLATION.110.3
 NOT CIRCUITING TO LOCAL BRANCH CIRCUIT IS THE EXCEPTION
 TO THE CODE.
  
 11) NOTE: PLEASE SEE THE RISER AS THIS NOTES *FEEDERS*
 BEFORE THE FIRST MEANS OF DISCONNECT. PLEASE SEE
 DEFINITIONS IN THE NEC AS THESE ARE THE SERVICE
 ENTRANCE CONDUCTORS.
 NEC 100.
  
 12) NOTE: PLEASE SHOW THE LOCATION OF THE SERVICE MAIN
 ON PLANS.
 110.26, 240.24, 230.70, 230.71 ETC
  
 13) NOTE: PLEASE SEE RISER AS THIS SHOWS THE
 TRANSFORMER BEING FED FROM THE RENAMED PANEL *A* YET
 THE PANEL *A* SCHEDULE DOES NOT INDICATE ANY OVER
 CURRENT PROTECTION OR FEED TO THIS TRANSFORMER. NEED TO
 VERIFY LOADS, OVER CURRENT PROTECTION, FEEDERS,
 EQUIPMENT GROUNDING ETC. 250.110,240.4,450.3,310.16,
 215.5 ETC
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 14) NOTE: AS THE CIRCUITING FOR EXTERIOR LIGHTS THROUGH
 THE TIME CLOCKS FOR ANY OUTSIDE LIGHTING IS NOT SHOWN
 COMPLIANCE WITH FBC 13-415.1.ABC.1.4 CAN NOT BE
 VERIFIED AS CODE COMPLIANT.
  
 15) NOTE: PLEASE BE SUR EOT INLCUDE THE ADDRESS
 LOCATION AS APPLIED ON TITLE BLOCKS. THE ADDRESS
 LOCATION AS APPLIED IS 2021 OKEECHOBEE BLVD.
 FAC 61G1-16.004, 61G15-23.002
  
 **
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved