| Date |
Text |
| 2008-07-29 09:52:49 | |
| | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE JURISDICTION IN WHICH THIS |
| | SCOPE OF WORK HAS BEEN APPLIED IN LOCATED IN THE CITY |
| | OF WEST PALM BEACH, FLORIDA. THERE ARE REFERENCES ON |
| | PLANS TO PALM BEACH COUNTY BUILDING DEPARTMENT. PLEASE |
| | ADJUST. |
| | |
| | 2) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED |
| | ON PLANS INCLUSIVE OF ARCHITECTURAL PLANS AS WELL AS |
| | ELECTRICAL SHEETS. |
| | SOME CODES LISTED SUCH AS THE 2004 ELECTRICAL CODE AND |
| | 2002 LIFE SAFETY CODE DO NOT EXIST. PLEASE SEE THE |
| | PLANS ALSO INDICATE THE *COMMONWEALTH OF MASSACHUSETTS* |
| | FOR THE ENERGY CODE. THE FLORIDA BUILDING CODE CHAPTER |
| | 13 IS THE STATE OF FLORIDA ENERGY CODE. |
| | PLEASE ADJUST. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | 2004 FBC W/2007 REVISIONS. |
| | |
| | 3) NOTE: PLEASE SEE THE MISSING INFORMATION ON THE |
| | TITLE BLOCKS ON FIRE ALARM PLANS. THE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 REQUIRES THE PRINTED |
| | NAME, PRINTED LICENSE NUMBER OF THE ENGINEER ALONG WITH |
| | THE REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER. |
| | PLEASE SEE FLORIDA STATUTES 471.023 FOR THE REQUIREMENT |
| | OF LICENSING FOR FIRM. |
| | |
| | 4) NOTE: PLEASE SEE COMMENT #3 ABOVE THE MEP PLANS ARE |
| | ALSO MISSING THE REQUIRED INFORMATION TO BE COMPLETED |
| | ON TITLE BLOCKS. |
| | THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER IS ALSO |
| | REQUIRED. |
| | FAC 61G15-23.002, FS 471.023. |
| | |
| | 5) NOTE: PLEASE SUBMIT THE COMPLETE PERFORMANCE |
| | CALCULATIONS AS REQUIRED PER 13-415.2.ABC.1.1, .1.2, |
| | .1.3, 13-415.2. |
| | PLEASE SEE THE SQUARE FOOTAGE SHOWN ON THE CALCULATIONS |
| | AS SUBMITTED ARE LESS THAN THE SQ FT SHOWN ON |
| | ARCHITECTURAL PLANS. |
| | PLEASE SEE THE SUBMITTED CALCULATIONS ALONG WITH THE |
| | INPUT DATA REPORT DO NOT COORDINATE WITH PLANS. ALL |
| | FIXTURE WATTAGES, FIXTURE COUNTS ETC NEED TO MATCH WITH |
| | PLANS. |
| | IN FACT PLEASE SEE THE INPUT DATA REPORT. SOME ITEMS IN |
| | THE IDR ARE BLANK. HOW IS THIS POSSIBLE WHEN THESE |
| | ITEMS ARE IN FACT ON PLANS. |
| | JUST ONE EXAMPLE OF THIS IS THE EXTERIOR LIGHTING ON |
| | THE IDR. THIS IS BLANK WITH NO INPUT. |
| | ** THIS IS ONE EXAMPLE ONLY. |
| | |
| | **PLEASE NOTE: THE PERSON AS SIGNED ON THE |
| | CERTIFICATION SHEET OF THE ENERGY CALCULATIONS AS THE |
| | *PREPARER* IS NOT LISTED AS ONE OF THE ENGINEERS OF |
| | RECORD. AS THE SCOPE OF WORK FALLS UNDER THE |
| | REQUIREMENTS OF AN ENGINEER THIS PERSON MUST BE |
| | LICENSED IN THE STATE OF FLORIDA AS SUCH. |
| | PLEASE PROVIDE LICENSE INFORMATION FOR SAID PREPARER |
| | MR. TREVOR GILBERTSON. |
| | 13-103.1, FS 471.003 |
| | |
| | 6) NOTE: PLEASE SUBMIT PLANS COMPLYING WITH THE FBC |
| | CHAPTER 13 FOR LIGHTING CONTROLS. THE EMS SYSTEM AS |
| | SUBMITTED DOES NOT COMPLETELY COMPLY WITH THE FOLLOWING |
| | SECTIONS. 13-415.1.ABC.1.1,.1.2, .1.3. |
| | PLEASE SEE NO OVER RIDES FOR OCCUPANTS COULD BE LOCATED |
| | ON PLANS. |
| | PLEASE SUBMIT ALL MAXIMUM TIMES ON OVER RIDES AND SPACE |
| | CONTROLS. |
| | PLEASE SEE NO SEPARATE SPACE CONTROLS ARE SHOWN ON |
| | PLANS. THE STANDARD DEVICES AS SHOWN DO NOT COMPLY WITH |
| | 13-415.1.ABC.1.2. |
| | PLEASE COMPLETE LIGHTING CONTROLS AND CIRCUITING FOR |
| | CONTACTOR SCHEDULES. PLEASE KNOW THIS MAY CHANGE BASED |
| | ON THE NOTES ABOVE WITH THE SYSTEM DESIGN AT PRESENT. |
| | ** AS A COMPLETE SYSTEM AND MANY DEVICES ARE NOT SHOWN |
| | THERE MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | 7) NOTE: PLEASE INCLUDE NOTES ON PLANS PER |
| | 13-413.1.ABC.2.1 |
| | DRAWINGS. |
| | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30 |
| | DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD |
| | DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED |
| | TO THE BUILDING OWNER, INCLUDING: |
| | 1. A SINGLE-LINE DIAGRAM OF THE BUILDING ELECTRICAL |
| | DISTRIBUTION SYSTEM AND |
| | 2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR |
| | ALL DISTRIBUTION. |
| | 13-413.1.ABC.2.2 MANUALS. |
| | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING |
| | MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE |
| | BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A |
| | MINIMUM, THE FOLLOWING: |
| | 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED |
| | OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING |
| | MAINTENANCE. |
| | 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH |
| | PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED |
| | ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY |
| | IDENTIFIED. |
| | 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED |
| | SERVICE AGENCY. |
| | |
| | 8) NOTE: PLEASE INCLUDE WORST CASE VOLTAGE DROP PER |
| | 13-413.1.ABC.1.1 AND .1.2. |
| | |
| | 9) NOTE: PLEASE INCLUDE REQUIRED MINIMUM FOR ADA |
| | COMPLIANCE FOR FIRE ALARM DEVICES INCLUSIVE OF ALL |
| | LEVELS LISTED IN 11-4.28.1, .2 AND .3 OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 10) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF THE |
| | EMERGENCY LIGHTS AND EXIT LIGHTS TO THE LOCAL LIGHTING |
| | BRANCH CIRCUITS. THE PLANS CALL FOR A LOCK OFF BREAKER |
| | TO MEET THE EXCEPTION IN THE NEC. PLEASE KNOW THE LOCK |
| | OFF BREAKER SHALL HAVE THE LOCK OFF MECHANISM PART OF |
| | THE BREAKER. THE *SNAP* ON OR *CLIP* ON TYPE LOCK OFF |
| | DEVICES ARE NOT ACCEPTABLE. PLEASE BE SURE TO CHECK THE |
| | LISTING OF THE UNIT IN DESIGN FOR *PERMANENT* |
| | INSTALLATION.110.3 |
| | NOT CIRCUITING TO LOCAL BRANCH CIRCUIT IS THE EXCEPTION |
| | TO THE CODE. |
| | |
| | 11) NOTE: PLEASE SEE THE RISER AS THIS NOTES *FEEDERS* |
| | BEFORE THE FIRST MEANS OF DISCONNECT. PLEASE SEE |
| | DEFINITIONS IN THE NEC AS THESE ARE THE SERVICE |
| | ENTRANCE CONDUCTORS. |
| | NEC 100. |
| | |
| | 12) NOTE: PLEASE SHOW THE LOCATION OF THE SERVICE MAIN |
| | ON PLANS. |
| | 110.26, 240.24, 230.70, 230.71 ETC |
| | |
| | 13) NOTE: PLEASE SEE RISER AS THIS SHOWS THE |
| | TRANSFORMER BEING FED FROM THE RENAMED PANEL *A* YET |
| | THE PANEL *A* SCHEDULE DOES NOT INDICATE ANY OVER |
| | CURRENT PROTECTION OR FEED TO THIS TRANSFORMER. NEED TO |
| | VERIFY LOADS, OVER CURRENT PROTECTION, FEEDERS, |
| | EQUIPMENT GROUNDING ETC. 250.110,240.4,450.3,310.16, |
| | 215.5 ETC |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | |
| | 14) NOTE: AS THE CIRCUITING FOR EXTERIOR LIGHTS THROUGH |
| | THE TIME CLOCKS FOR ANY OUTSIDE LIGHTING IS NOT SHOWN |
| | COMPLIANCE WITH FBC 13-415.1.ABC.1.4 CAN NOT BE |
| | VERIFIED AS CODE COMPLIANT. |
| | |
| | 15) NOTE: PLEASE BE SUR EOT INLCUDE THE ADDRESS |
| | LOCATION AS APPLIED ON TITLE BLOCKS. THE ADDRESS |
| | LOCATION AS APPLIED IS 2021 OKEECHOBEE BLVD. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | ** |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |