Plan Review Notes
Plan Review Notes For Permit 08070134
Permit Number 08070134
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-24 15:18:38BUILDING PLAN REVIEW
 PERMIT: 08070134
 ADD: 2021 OKEECHOBEE BLVD # A2
 CONT: GERARDI CONSTRUCTION
 TEL: (813)433-3868
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) COVER SHEET CVR, CODE REVIEW
 2A) PLEASE UPDATE TO THE 2007 SUPPLEMENTS, BUILDING
 2B) COMMENT# 7 ENERGY CODE COMMONWEALTH OF
 MASSACHUSETTS, PLEASE CORRECT
 2C) COMMENT# 9 THIS IS NOT THE PALM BEACH COUNTY
 PLANNING, ZONING AND BUILDING DEPARTMENTPLEASE CORRECT
 TO THE CORRECT JURISDICTION
 2D) UNDER THE CODE REVIEW PLANS FAIL TO INDICATE THE
 2004 EXISTING BUILDING CODE AND TO WHAT LEVEL OR
 COMBINATION OF LEVELS THE DESIGN PROFESSIONAL OR OWNER
 HAS DESIGNED TO. FBC EXISTING BUILDING
 CODE301.5.
  
 3) SHEET A5 INDICATES A DETAIL 12/ A9.1 WHICH IS A
 SOFFIT DETAIL INDICATING A SINGLE # 12 PAN HEAD SCREW
 2'-0" O.C. IN TENSION TO HOLD THE 5/8" DRYWALL AND WALL
 FRAMING FROM WHAT TYPE OF STRUCTURE ABOVE?
 PLEASE INDICATE WHAT STRUCTURAL MEMBER THIS SOFFIT
 WILL BE HUNG FROM AND PROVIDE CLALCULATIONS ON THE
 FASTENER IN TENTION LISTED ABOVE AND THE DEAD LOADING
 ON THIS SCREW AND SAFETY FACTORS INVOLVED.
 1604.2 STRENGTH.
  
 4) SHEET A7 DETAIL# 4 INDICATES A BREAK ROOM SINK,
 PLEASE PROVIDE THE FOLLOWING INFORMATION:
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 5) SHEET A11 INDICATES WOOD BACKING OR BLOCKING, PLEASE
 SEE 603.1 FOR AREAS WHERE FIRE RETARDANT TREATED WOOD
 CAN BE USED.
  
 6) I COULD NOT FIND IN THE PLANS A ACTUAL FINISH
 SCHEDULE, PLEASE COMPLY WITH 1210.2 WALLS WITHIN 2 FEET
 OF URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON ABSORBANT SURFACE, TO A HEIGHT OF 4'-0".
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  