| Plan Review Notes For Permit 08070128 |
| Permit Number |
08070128 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-23 09:57:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.PLEASE PROVIDE MORE INFORMATION REGARDING EXISTING | | | CONDITIONS.ARE EXISTING DOORS BEING REPLACED, (FOR | | | INSTANCE, SWING DOORS REPLACED BY THE FOLDING DOORS), | | | OR ARE THE NEW DOORS NEW OPENINGS?A FLOOR PLAN | | | SHOWING THE PROPOSED WAS SUBMITTED, BUT NO DEMO PLAN. | | | SEE FBC1001.4; IT IS NOT CLEAR IF YOU ARE PROPOSING TO | | | INCREASE EGRESS CAPACITY, IF IT WILL REMAIN THE SAME, | | | OR BE REDUCED.THE FOLDING DOORS DO NOT COMPLY WITH | | | FBC1008.1.2 AND FBC11-4.13.IT IS NOT CLEAR IF THE NEW | | | DOORS ARE REQUIRED FOR EXITING. | | | | | | IT IS POSSIBLE THAT THIS ISSUE MAY BE RESOLVED WITH A | | | TELEPHONE CONVERSATION WITH THE ARCHITECT.A CALL HAS | | | BEEN PLACED TO RJS ARCHITECTS, INC. | | | | | | |
|