Plan Review Notes
Plan Review Notes For Permit 08070127
Permit Number 08070127
Review Stop E
Sequence Number 7
Notes
Date Text
2009-03-29 09:57:22** DENIED REVIEW **
  
 *** DENIED REVISIONS***
  
 1) NOTE: AS GIVEN ON ORIGINAL PROVISO AND IN PREVIOUS
 NOTES, PLEASE REVISE PLANS TO CONFORM TO THE MINIMUM
 CODES FOR LIGHTING CONTROLS IN FBC 13-415.1.ABC.1.1,
 .1.2 AND .1.3. EXAMPLES WERE GIVEN ON PREVIOUS REVIEWS
 HOWEVER PLANS STILL DO NOT SHOW ITEMS NEEDED.
  
 A) IN THE PREVIOUS REVIEW COMMENTS WERE GIVEN WITH
 RESPECT TO THE BATHROOMS. THESE NOW SHOW *SINGLE POLE*
 SWITCHES AS THE SEPARATE SPACE CONTROL AND OVER RIDES
 TO THE LIGHTING CONTROL PANEL WHICH THESE LIGHTS ARE
 CIRCUITED.
 THE FIRST ITEM IS THAT ALL THE LIGHTING SHALL BE TURNED
 OFF ON THIS BUILDING AUTOMATICALLY. ALL SEPARATE SPACES
 SHALL HAVE CONTROLS EITHER OF THE FOLLOWING: A DEVICE
 WHICH OVER RIDES THE SCHEDULED SYSTEM OR AUTOMATED
 SINGLE CONTROLS FOR SUCH SPACE. ( AN EXAMPLE WOULD BE
 OCCUPANCY SENSORS). IN EITHER CASE THESE DEVICES MUST
 BE AUTOMATED.
 SEE SECTIONS ABOVE.
  
 B) ANOTHER AREA IS WHEN ENTERING THROUGH THE FRONT DOOR
 TO SEPARATE BAR SEATING AREA THERE IS NO OVER RIDE
 CONTROLS OR A OCCUPANCY SENSOR WHICH RIDES THE TIME OF
 DAY SCHEDULING.
 SEE SECTIONS ABOVE.
  
 C) LIGHTING CIRCUITS/RELAY NUMBERS ON RPA OR ANY OTHER
 PANEL HAVE NOT ALL BEEN UPDATED. WHERE IS E-3, 5 ETC
 THE NOTES MENTIONS TO DIMMING CONTROL POWER BOOSTER
 PANEL HOWEVER THE NOTES FOR CONNECTION OF POWER BOOSTER
 PANEL TO THE PANEL RPA ARE NOT COMPLETE.
 THERE IS NO INDICATION FOR CIRCUITING IN RPA OF MANY OF
 THESE CIRCUITS UNDER THE CONTROL OF THE LIGHTING
 CONTROL PANEL.
  
 ** ONCE AGAIN AS REQUESTED ON PROVISO ON 9/24/08,
 PROVIDE COMPLETE FUNCTIONALITY OF SYSTEM.
 PLEASE BE SURE TO ALSO SEE FBC 1006.1.2, NFPA-101
 7.8.1.2.2 FOR CONTROLS FOR *MINIMUM* LIFE SAFETY.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 UPDATING ALL LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.2.ABC.1.1, .1.2.
 THE SAME EXAMPLE GIVEN IS RESTROOM LIGHTING. THESE
 NEEDS TO BE INCLUDED IN CALCULATIONS BASED ON THE FACT
 NEW FIXTURES ARE SHOWN. IN OTHER BATHROOMS NO
 INFORMATION ON FIXTURES ARE SHOWN YET THESE ARE FIGURED
 INTO CALCULATIONS.
 PLEASE SEE SHEET E2.2 FOR EXAMPLE: THE LARGE RESTROOMS
 DO NOT INCLUDE ANY FIXTURE INFORMATION. THIS IS THE
 SAME FOR THE SMALLER LOCATIONS ALSO.
  
 3) NOTE: AS GIVEN ON PREVIOUS REVIEW. PLEASE UPDATE ALL
 CIRCUITING ON ALL PANELS WITH PLANS. PLEASE SEE E PANEL
 CIRCUIT #12, NOTED AS BILLIARD ROOM. THIS ROOM NO
 LONGER EXISTS.
 408.4
 ** THIS IS ONLY ONE EXAMPLE; THERE ARE OTHERS. ALL
 CIRCUITS NEED TO BE SPECIFIC TO THE ROOMS AND AREAS IN
 WHICH THEY FEED.
  
 4) NOTE: AS NOTED ON PREVIOUS REVIEW: PLEASE UPDATE ALL
 LOAD CALCULATIONS. ONE EXAMPLE WAS GIVEN THAT NOT ALL
 LOADS ON PANELS WERE UPDATE AND CARRIED THROUGH.
 AN EXAMPLE: PANEL *B* PHASE A AND OTHER PHASES ALSO.
 PLEASE GO OVER ALL LOADS ON ALL PANELS AND UPDATE ALL.
 THIS IS ONE EXAMPLE GIVEN AS A BENEFIT.
 220, 220.12,220.14,220.42,220.44 ETC
 215.3, 230.42
  
 5) NOTE: ONE SET OF PLANS IS BEING RETAINED BY THIS
 OFFICE. ONLY TWO SETS WILL BE GIVEN BACK.
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  