| 2009-03-29 09:57:22 | ** DENIED REVIEW ** |
| | |
| | *** DENIED REVISIONS*** |
| | |
| | 1) NOTE: AS GIVEN ON ORIGINAL PROVISO AND IN PREVIOUS |
| | NOTES, PLEASE REVISE PLANS TO CONFORM TO THE MINIMUM |
| | CODES FOR LIGHTING CONTROLS IN FBC 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3. EXAMPLES WERE GIVEN ON PREVIOUS REVIEWS |
| | HOWEVER PLANS STILL DO NOT SHOW ITEMS NEEDED. |
| | |
| | A) IN THE PREVIOUS REVIEW COMMENTS WERE GIVEN WITH |
| | RESPECT TO THE BATHROOMS. THESE NOW SHOW *SINGLE POLE* |
| | SWITCHES AS THE SEPARATE SPACE CONTROL AND OVER RIDES |
| | TO THE LIGHTING CONTROL PANEL WHICH THESE LIGHTS ARE |
| | CIRCUITED. |
| | THE FIRST ITEM IS THAT ALL THE LIGHTING SHALL BE TURNED |
| | OFF ON THIS BUILDING AUTOMATICALLY. ALL SEPARATE SPACES |
| | SHALL HAVE CONTROLS EITHER OF THE FOLLOWING: A DEVICE |
| | WHICH OVER RIDES THE SCHEDULED SYSTEM OR AUTOMATED |
| | SINGLE CONTROLS FOR SUCH SPACE. ( AN EXAMPLE WOULD BE |
| | OCCUPANCY SENSORS). IN EITHER CASE THESE DEVICES MUST |
| | BE AUTOMATED. |
| | SEE SECTIONS ABOVE. |
| | |
| | B) ANOTHER AREA IS WHEN ENTERING THROUGH THE FRONT DOOR |
| | TO SEPARATE BAR SEATING AREA THERE IS NO OVER RIDE |
| | CONTROLS OR A OCCUPANCY SENSOR WHICH RIDES THE TIME OF |
| | DAY SCHEDULING. |
| | SEE SECTIONS ABOVE. |
| | |
| | C) LIGHTING CIRCUITS/RELAY NUMBERS ON RPA OR ANY OTHER |
| | PANEL HAVE NOT ALL BEEN UPDATED. WHERE IS E-3, 5 ETC |
| | THE NOTES MENTIONS TO DIMMING CONTROL POWER BOOSTER |
| | PANEL HOWEVER THE NOTES FOR CONNECTION OF POWER BOOSTER |
| | PANEL TO THE PANEL RPA ARE NOT COMPLETE. |
| | THERE IS NO INDICATION FOR CIRCUITING IN RPA OF MANY OF |
| | THESE CIRCUITS UNDER THE CONTROL OF THE LIGHTING |
| | CONTROL PANEL. |
| | |
| | ** ONCE AGAIN AS REQUESTED ON PROVISO ON 9/24/08, |
| | PROVIDE COMPLETE FUNCTIONALITY OF SYSTEM. |
| | PLEASE BE SURE TO ALSO SEE FBC 1006.1.2, NFPA-101 |
| | 7.8.1.2.2 FOR CONTROLS FOR *MINIMUM* LIFE SAFETY. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | UPDATING ALL LIGHTING PERFORMANCE CALCULATIONS PER |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | THE SAME EXAMPLE GIVEN IS RESTROOM LIGHTING. THESE |
| | NEEDS TO BE INCLUDED IN CALCULATIONS BASED ON THE FACT |
| | NEW FIXTURES ARE SHOWN. IN OTHER BATHROOMS NO |
| | INFORMATION ON FIXTURES ARE SHOWN YET THESE ARE FIGURED |
| | INTO CALCULATIONS. |
| | PLEASE SEE SHEET E2.2 FOR EXAMPLE: THE LARGE RESTROOMS |
| | DO NOT INCLUDE ANY FIXTURE INFORMATION. THIS IS THE |
| | SAME FOR THE SMALLER LOCATIONS ALSO. |
| | |
| | 3) NOTE: AS GIVEN ON PREVIOUS REVIEW. PLEASE UPDATE ALL |
| | CIRCUITING ON ALL PANELS WITH PLANS. PLEASE SEE E PANEL |
| | CIRCUIT #12, NOTED AS BILLIARD ROOM. THIS ROOM NO |
| | LONGER EXISTS. |
| | 408.4 |
| | ** THIS IS ONLY ONE EXAMPLE; THERE ARE OTHERS. ALL |
| | CIRCUITS NEED TO BE SPECIFIC TO THE ROOMS AND AREAS IN |
| | WHICH THEY FEED. |
| | |
| | 4) NOTE: AS NOTED ON PREVIOUS REVIEW: PLEASE UPDATE ALL |
| | LOAD CALCULATIONS. ONE EXAMPLE WAS GIVEN THAT NOT ALL |
| | LOADS ON PANELS WERE UPDATE AND CARRIED THROUGH. |
| | AN EXAMPLE: PANEL *B* PHASE A AND OTHER PHASES ALSO. |
| | PLEASE GO OVER ALL LOADS ON ALL PANELS AND UPDATE ALL. |
| | THIS IS ONE EXAMPLE GIVEN AS A BENEFIT. |
| | 220, 220.12,220.14,220.42,220.44 ETC |
| | 215.3, 230.42 |
| | |
| | 5) NOTE: ONE SET OF PLANS IS BEING RETAINED BY THIS |
| | OFFICE. ONLY TWO SETS WILL BE GIVEN BACK. |
| | |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |