Plan Review Notes
Plan Review Notes For Permit 08070127
Permit Number 08070127
Review Stop P
Sequence Number 6
Notes
Date Text
2009-01-06 17:12:05REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P0.1 SHOWS MANY CHANGES TO THE EQUIPMENT
 SCHEDULE THAT ARE NOT INDICATED WITH A REVISION NUMBER
 , NOR CLOUDED AS REQUIRED. ALL REVISIONS SHALL BE
 INDICATED WITH A CLOUD AND A REVISION NUMBER. SECTION
 106.1.3. -- THE REVISION INDEX SHOWS A REVISION 4 THAT
 IS NOT INDICATED ON THE FLOOR PLAN. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  