Plan Review Notes
Plan Review Notes For Permit 08070127
Permit Number 08070127
Review Stop E
Sequence Number 6
Notes
Date Text
2009-01-02 18:55:06** DENIED REVIEW OF REVISIONS **
  
 1) NOTE: PLEASE LABEL ALL REVISIONS ON PLANS WITH
 CLOUDS WITH REVISION NUMBER IDENTIFICATION AS NOTED IN
 TITLE BLOCKS. THERE HAVE BEEN TWO SETS OF REVISIONS
 MADE HOWEVER UNTIL NOW NO REVISIONS WERE SUBMITTED FOR
 REVIEW. THE NUMERICAL DESIGNATION IS ON PLANS HOWEVER
 THE REVISED ITEMS HAVE NOT BE IDENTIFIED.
 FBC 106.5, 106.1.1, NEC 2005, FBC 2005 FOR CLARITY,
 COORDINATION AND ADDITIONAL INFORMATION NEEDED.
  
 2) NOTE: PLEASE SEE PROVISO ISSUED IN SEPTEMBER OF
 2008. NO REVISED ELECTRICAL PLANS HAVE COME INTO THIS
 OFFICE GIVING THE FUNCTIONALITY OF THE TENANT SPACE
 LIGHTING CONTROL SYSTEM IN ORDER TO VERIFY NOT ONLY
 LIGHTING CONTROL COMPLIANCE PER FBC CHAPTER 13 BUT ALSO
 THE LIGHTING FOR EGRESS UNDER NORMAL, EMERGENCY AND
 SHOW CONDITIONS.
 THIS WAS A REQUEST OF DESIGNER SO THE SYSTEM COULD BE
 WORKED OUT.
 THE PROJECT IS NOW REQUESTING A TCO AND ONLY SOME ITEMS
 HAVE BEEN REVISED ON PLANS. SOME ITEMS ON PLANS ARE NOT
 COMPLETE AND THE COMMENTS FROM PREVIOUS PROVISO IS
 STILL IN NEED OF ADDRESSING.
 FBC 13-415.1.ABC.1.1, .1.2, .1.3. LS 101 7.8, 7.9, FBC
 1006.1
  
 A) PLEASE SEE THERE ARE LIGHTING FIXTURES ON PLANS
 WHICH HAVE BEEN REVISED WHICH NOW DO NOT INDICATE ANY
 CIRCUITING OR CONTROLS. SEE RECESSED FIXTURES AND
 SCONCES AT ENTRANCE INTO CLUB AREA AS ONE EXAMPLE.
  
 B) PLEASE SEE CIRCUITING ON THE LIGHTING CONTROL PANEL
 SHALL BE UPDATED FOR ALL ALONG WITH PANEL SCHEDULES.
 ONE EXAMPLE OF COORDINATION IS THE BILLIARD ROOM WHICH
 IS STILL SHOWN AS CIRCUIT #12 ON THE RPA PANEL YET
 THERE IS NO LONGER A BILLIARD ROOM.
 THIS IS ONLY ONE.
  
 C) NOTE: PLEASE SEE AREAS SUCH AS THE LARGE MULTI-GANG
 BATHS WHICH DO NOT COMPLY WITH SEPARATE SPACE CONTROL
 EVEN THOUGH THEY ARE WIRED TO THE LIGHTING CONTROL
 PANEL. PLEASE SEE 13-415.1.ABC.1.2. THIS MUST HAVE
 SEPARATE CONTROL.
 PLEASE SEE OTHER SMALLER BATHS WHICH INDICATE MOTION
 SENSORS HOWEVER VERIFY THESE AS DUAL TECHNOLOGY IN
 ORDER TO MEET THE LIFE SAFETY CODE FOR OCCUPANTS IN ANY
 STALL AREAS.
  
 D) PLEASE REVISE ALL PHOTO-METRICS FOR NORMAL, AND SHOW
 TIMES. AT THE REQUEST OF THE DESIGNER THIS WAS GOING TO
 BE MEASURE AND SHOWN ONCE INSTALLED. IT WAS KNOWN TO
 BOTH THE ARCHITECT AND KAMM CONSULTING THAT IF THE
 STAIR LEVEL LIGHTING AND OTHER AREAS DID NOT MEET THE
 MINIMUM IN THE LIFE SAFETY CODE THAT FIXTURES MAY NEED
 TO BE ADDED. THIS NEEDS TO BE CONFIRMED AND SHOWN.
 RECORD PLANS NEED TO SHOW THIS. A FIELD INSPECTION MAY
 ALSO BE NEEDED.
  
 ** THE PROVISO WAS GRANTED IN ORDER TO PERMIT THE
 PROJECT AND TO GET EVERYTHING STARTED. THE PROVISO IS
 GIVEN TO GIVE THE CONTRACTOR AND THE DESIGN TEAM THE
 OPPORTUNITY TO OBTAIN INFORMATION ETC AND REVISE PLANS.
 IN THE MEETING HELD BEFORE PERMIT ISSUANCE THIS
 REVIEWER SPECIFICALLY MENTION REVISED PLANS NEEDED TO
 BE SUBMITTED IN PLENTY OF TIME WITH ALL INFORMATION
 BEFORE FINAL INSPECTIONS WERE BEING SCHEDULED.
 SUBMITTING THE PLANS THE WEEK BEFORE NEEDED FINALS IS
 NOT ENOUGH TIME TO DO REVIEWS, ADDRESS ANY POSSIBLE
 COMMENTS AND FOR PLANS TO BE ON THE SITE FOR
 INSPECTIONS.
  
  
 3) NOTE: PREVIOUS PLANS CLEARLY INDICATE THE EXISTING
 TRANSFORMER TEA AS GROUND MOUNTED, NOW THE POWER PLANS
 INDICATES THIS AS ABOVE. TRANSFORMERS OVER 50KVA ARE
 NOT PERMITTED ABOVE THE CEILING. PLEASE EXPLAIN WHAT IS
 MEANT BY *ABOVE* AS STATED ON PLANS.
 PLEASE SEE 450.13 AS THE LOCATION NEEDS TO BE VERIFIED
 MEETING CODE COMPLIANCE.
  
 4) NOTE: LOADS ON PANELS AND EQUIPMENT ALONG WITH
 CIRCUITING HAS BEEN REVISED HOWEVER NOT ALL LOADS ETC
 HAVE BEEN CARRIED THROUGH. ONE EXAMPLE IS PANEL K1
 WHICH HAS A SUBSTANTIALLY INCREASED LOAD WHICH AFFECTS
 H1A YET THE LOAD ON THE MAIN SERVICE LOAD CALCULATIONS
 HAS NOT BEEN REVISED. THE PLANS IN FACT SHOW THE SAME
 LOADS AS NOTED ON ORIGINAL PERMITTED PLANS.
  
 5) NOTE: THE LIGHTING PERFORMANCE CALCULATIONS NEED TO
 BE UPDATED WITH ALL LIGHTING IF ALLOWANCES FOR ALL
 LIGHTING IS GOING TO BE USED. AN EXAMPLE OF THIS IS THE
 ALLOWANCE BEING FIGURED FOR RESTROOMS YET NO FIXTURES
 WITH ANY INFORMATION IS ON PLANS. MAY NOT USE THE SQ FT
 WITHOUT INCLUDING ALL LIGHTS. AS THESE SUPPOSEDLY ARE
 EXISTING TO REMAIN PLEASE REMOVE. IF THESE ARE NEW,
 THEN REVISED ALL INFORMATION FOR FIXTURES ETC
 13-415.2.ABC.1.1,.1.2.
 ALL SPECIFIC FIXTURES NEED TO BE LISTED WITH
 MANUFACTURE AND MODEL NUMBER ETC. THE VERIFICATION OF
 LIGHTING COMPLIANCE CAN NOT BE CONFIRMED.
 PLEASE KEEP IN MIND ALL WATTAGE USED FOR CALCULATIONS
 SHALL BE BASED ON THE RATING OF FIXTURE NOT THE FIXTURE
 BULB RATING.
 ALL FIXTURES SHALL CONTAIN A LISTING FROM A NRTL.110.3
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II