| 2009-01-02 18:55:06 | ** DENIED REVIEW OF REVISIONS ** |
| | |
| | 1) NOTE: PLEASE LABEL ALL REVISIONS ON PLANS WITH |
| | CLOUDS WITH REVISION NUMBER IDENTIFICATION AS NOTED IN |
| | TITLE BLOCKS. THERE HAVE BEEN TWO SETS OF REVISIONS |
| | MADE HOWEVER UNTIL NOW NO REVISIONS WERE SUBMITTED FOR |
| | REVIEW. THE NUMERICAL DESIGNATION IS ON PLANS HOWEVER |
| | THE REVISED ITEMS HAVE NOT BE IDENTIFIED. |
| | FBC 106.5, 106.1.1, NEC 2005, FBC 2005 FOR CLARITY, |
| | COORDINATION AND ADDITIONAL INFORMATION NEEDED. |
| | |
| | 2) NOTE: PLEASE SEE PROVISO ISSUED IN SEPTEMBER OF |
| | 2008. NO REVISED ELECTRICAL PLANS HAVE COME INTO THIS |
| | OFFICE GIVING THE FUNCTIONALITY OF THE TENANT SPACE |
| | LIGHTING CONTROL SYSTEM IN ORDER TO VERIFY NOT ONLY |
| | LIGHTING CONTROL COMPLIANCE PER FBC CHAPTER 13 BUT ALSO |
| | THE LIGHTING FOR EGRESS UNDER NORMAL, EMERGENCY AND |
| | SHOW CONDITIONS. |
| | THIS WAS A REQUEST OF DESIGNER SO THE SYSTEM COULD BE |
| | WORKED OUT. |
| | THE PROJECT IS NOW REQUESTING A TCO AND ONLY SOME ITEMS |
| | HAVE BEEN REVISED ON PLANS. SOME ITEMS ON PLANS ARE NOT |
| | COMPLETE AND THE COMMENTS FROM PREVIOUS PROVISO IS |
| | STILL IN NEED OF ADDRESSING. |
| | FBC 13-415.1.ABC.1.1, .1.2, .1.3. LS 101 7.8, 7.9, FBC |
| | 1006.1 |
| | |
| | A) PLEASE SEE THERE ARE LIGHTING FIXTURES ON PLANS |
| | WHICH HAVE BEEN REVISED WHICH NOW DO NOT INDICATE ANY |
| | CIRCUITING OR CONTROLS. SEE RECESSED FIXTURES AND |
| | SCONCES AT ENTRANCE INTO CLUB AREA AS ONE EXAMPLE. |
| | |
| | B) PLEASE SEE CIRCUITING ON THE LIGHTING CONTROL PANEL |
| | SHALL BE UPDATED FOR ALL ALONG WITH PANEL SCHEDULES. |
| | ONE EXAMPLE OF COORDINATION IS THE BILLIARD ROOM WHICH |
| | IS STILL SHOWN AS CIRCUIT #12 ON THE RPA PANEL YET |
| | THERE IS NO LONGER A BILLIARD ROOM. |
| | THIS IS ONLY ONE. |
| | |
| | C) NOTE: PLEASE SEE AREAS SUCH AS THE LARGE MULTI-GANG |
| | BATHS WHICH DO NOT COMPLY WITH SEPARATE SPACE CONTROL |
| | EVEN THOUGH THEY ARE WIRED TO THE LIGHTING CONTROL |
| | PANEL. PLEASE SEE 13-415.1.ABC.1.2. THIS MUST HAVE |
| | SEPARATE CONTROL. |
| | PLEASE SEE OTHER SMALLER BATHS WHICH INDICATE MOTION |
| | SENSORS HOWEVER VERIFY THESE AS DUAL TECHNOLOGY IN |
| | ORDER TO MEET THE LIFE SAFETY CODE FOR OCCUPANTS IN ANY |
| | STALL AREAS. |
| | |
| | D) PLEASE REVISE ALL PHOTO-METRICS FOR NORMAL, AND SHOW |
| | TIMES. AT THE REQUEST OF THE DESIGNER THIS WAS GOING TO |
| | BE MEASURE AND SHOWN ONCE INSTALLED. IT WAS KNOWN TO |
| | BOTH THE ARCHITECT AND KAMM CONSULTING THAT IF THE |
| | STAIR LEVEL LIGHTING AND OTHER AREAS DID NOT MEET THE |
| | MINIMUM IN THE LIFE SAFETY CODE THAT FIXTURES MAY NEED |
| | TO BE ADDED. THIS NEEDS TO BE CONFIRMED AND SHOWN. |
| | RECORD PLANS NEED TO SHOW THIS. A FIELD INSPECTION MAY |
| | ALSO BE NEEDED. |
| | |
| | ** THE PROVISO WAS GRANTED IN ORDER TO PERMIT THE |
| | PROJECT AND TO GET EVERYTHING STARTED. THE PROVISO IS |
| | GIVEN TO GIVE THE CONTRACTOR AND THE DESIGN TEAM THE |
| | OPPORTUNITY TO OBTAIN INFORMATION ETC AND REVISE PLANS. |
| | IN THE MEETING HELD BEFORE PERMIT ISSUANCE THIS |
| | REVIEWER SPECIFICALLY MENTION REVISED PLANS NEEDED TO |
| | BE SUBMITTED IN PLENTY OF TIME WITH ALL INFORMATION |
| | BEFORE FINAL INSPECTIONS WERE BEING SCHEDULED. |
| | SUBMITTING THE PLANS THE WEEK BEFORE NEEDED FINALS IS |
| | NOT ENOUGH TIME TO DO REVIEWS, ADDRESS ANY POSSIBLE |
| | COMMENTS AND FOR PLANS TO BE ON THE SITE FOR |
| | INSPECTIONS. |
| | |
| | |
| | 3) NOTE: PREVIOUS PLANS CLEARLY INDICATE THE EXISTING |
| | TRANSFORMER TEA AS GROUND MOUNTED, NOW THE POWER PLANS |
| | INDICATES THIS AS ABOVE. TRANSFORMERS OVER 50KVA ARE |
| | NOT PERMITTED ABOVE THE CEILING. PLEASE EXPLAIN WHAT IS |
| | MEANT BY *ABOVE* AS STATED ON PLANS. |
| | PLEASE SEE 450.13 AS THE LOCATION NEEDS TO BE VERIFIED |
| | MEETING CODE COMPLIANCE. |
| | |
| | 4) NOTE: LOADS ON PANELS AND EQUIPMENT ALONG WITH |
| | CIRCUITING HAS BEEN REVISED HOWEVER NOT ALL LOADS ETC |
| | HAVE BEEN CARRIED THROUGH. ONE EXAMPLE IS PANEL K1 |
| | WHICH HAS A SUBSTANTIALLY INCREASED LOAD WHICH AFFECTS |
| | H1A YET THE LOAD ON THE MAIN SERVICE LOAD CALCULATIONS |
| | HAS NOT BEEN REVISED. THE PLANS IN FACT SHOW THE SAME |
| | LOADS AS NOTED ON ORIGINAL PERMITTED PLANS. |
| | |
| | 5) NOTE: THE LIGHTING PERFORMANCE CALCULATIONS NEED TO |
| | BE UPDATED WITH ALL LIGHTING IF ALLOWANCES FOR ALL |
| | LIGHTING IS GOING TO BE USED. AN EXAMPLE OF THIS IS THE |
| | ALLOWANCE BEING FIGURED FOR RESTROOMS YET NO FIXTURES |
| | WITH ANY INFORMATION IS ON PLANS. MAY NOT USE THE SQ FT |
| | WITHOUT INCLUDING ALL LIGHTS. AS THESE SUPPOSEDLY ARE |
| | EXISTING TO REMAIN PLEASE REMOVE. IF THESE ARE NEW, |
| | THEN REVISED ALL INFORMATION FOR FIXTURES ETC |
| | 13-415.2.ABC.1.1,.1.2. |
| | ALL SPECIFIC FIXTURES NEED TO BE LISTED WITH |
| | MANUFACTURE AND MODEL NUMBER ETC. THE VERIFICATION OF |
| | LIGHTING COMPLIANCE CAN NOT BE CONFIRMED. |
| | PLEASE KEEP IN MIND ALL WATTAGE USED FOR CALCULATIONS |
| | SHALL BE BASED ON THE RATING OF FIXTURE NOT THE FIXTURE |
| | BULB RATING. |
| | ALL FIXTURES SHALL CONTAIN A LISTING FROM A NRTL.110.3 |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |