| 2008-12-01 13:32:52 | |
| | ** FAILED REVISION** |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT COORDINATING PLANS FOR REFLECTED |
| | CEILING WITH RESPECT TO LIGHTING AND AREAS. |
| | FOR EXAMPLE: SHEETS A180.1 AND OTHERS IN ARCHITECTURAL |
| | SET WHICH WERE JUST RECENTLY REVISED DO NOT CONTAIN |
| | MANY OF THE SAME LIGHTING FIXTURES WHICH ARE ON THE |
| | ELECTRICAL PLANS. |
| | PLEASE SEE AREAS SUCH AS THE * SEATING AREA* OUTSIDE |
| | THE RESTROOMS WHICH ON ELECTRICAL PLANS IS SHOWN AS A * |
| | PRIVATE BILLIARD ROOM*. |
| | |
| | 2) NOTE: PLEASE SUBMIT REVISED LIGHTING PERFORMANCE |
| | CALCULATIONS. PLEASE EXPLAIN HOW THE LIGHTING DESIGN |
| | WATTAGE HAS GONE DOWN FROM PERMITTED PLANS WHEN |
| | FIXTURES SUCH AS THE *E* FIXTURE HAS ACTUALLY INCREASED |
| | IN THE WATTAGE. IN FACT FIXTURE *E* HAS MORE THAN |
| | DOUBLED IN THE WATTAGE ON THE FIXTURE LEGEND. |
| | PLEASE BE SURE TO COORDINATE ALL. |
| | 13-415.2,13-415.2.ABC.1.1,1.2. |
| | |
| | 3) NOTE: PLEASE SEE * PROVISO* FROM PERMIT ISSUANCE. |
| | PLEASE SUBMIT INFORMATION AND DOCUMENTATION FOR |
| | FUNCTIONALITY OF LIGHTING CONTROL SYSTEM AND SEQUENCE |
| | OF OPERATION. |
| | 13-415.1.ABC.1.1,.1.2 AND.1.3. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |