Plan Review Notes
Plan Review Notes For Permit 08070127
Permit Number 08070127
Review Stop G
Sequence Number 4
Notes
Date Text
2009-01-06 17:33:01REVISION DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHT P6.1 THERE ARE CHANGES TO THE GAS RISER DIAGRAM
 THAT ARE NOT CLOUDED NOR INDICATED WITH A REVISION
 NUMBER. EACH REVISION SHALL BE INDICATED WITH A CLOUD
 AND A REVISION NUMBER. (SEE P19G 35,000 BTU DELETED AT
 THE END OF LINE 2, P23G 225,000 BTU STUB OUT PIPE SIZE
 CHANGED TO 1-1/2" LINE 2. -- SEE P17G 70,000 BTU ADDED
 TO LINE 1, P25G 140,000 BTU DELETED FROM LINE 1). ALSO
 CLARIFY THE P57G ON LINE 1 IS INDICATED AS 224,000 BTU,
 BUT THE P57G ON LINE 2 IS INDICATED AS 168,000 BTU. IS
 THIS A DIFFERENT GAS APPLIANCE? IF SO PLEASE SUBMIT THE
 MANUF. SPECIFICATION FOR THE NEW P57G SHOWING LISTING
 AND BTU LOAD.
  
 2. SHT P6.1 SHOWS A REVISION 4 IN THE REVISION INDEX
 THAT IS NOT SHOWN ON THE RISER DIAGRAMS. PLEASE CLARIFY
 AS THIS REVISION HAS NOT BEEN APPROVED OR REVIEWED.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  