| 2009-01-06 17:33:01 | REVISION DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P6.1 THERE ARE CHANGES TO THE GAS RISER DIAGRAM |
| | THAT ARE NOT CLOUDED NOR INDICATED WITH A REVISION |
| | NUMBER. EACH REVISION SHALL BE INDICATED WITH A CLOUD |
| | AND A REVISION NUMBER. (SEE P19G 35,000 BTU DELETED AT |
| | THE END OF LINE 2, P23G 225,000 BTU STUB OUT PIPE SIZE |
| | CHANGED TO 1-1/2" LINE 2. -- SEE P17G 70,000 BTU ADDED |
| | TO LINE 1, P25G 140,000 BTU DELETED FROM LINE 1). ALSO |
| | CLARIFY THE P57G ON LINE 1 IS INDICATED AS 224,000 BTU, |
| | BUT THE P57G ON LINE 2 IS INDICATED AS 168,000 BTU. IS |
| | THIS A DIFFERENT GAS APPLIANCE? IF SO PLEASE SUBMIT THE |
| | MANUF. SPECIFICATION FOR THE NEW P57G SHOWING LISTING |
| | AND BTU LOAD. |
| | |
| | 2. SHT P6.1 SHOWS A REVISION 4 IN THE REVISION INDEX |
| | THAT IS NOT SHOWN ON THE RISER DIAGRAMS. PLEASE CLARIFY |
| | AS THIS REVISION HAS NOT BEEN APPROVED OR REVIEWED. |
| | SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |