| Notes |
| Date |
Text |
| 2008-09-23 09:38:14 | | | | | | | | | | PASSED/PROVISO | | | | | | 1. SUBMIT MANUF. SPECIFICATIONS FOR ALL GAS APPLIANCES | | | AT THE TIME OF PERMIT APPLICATION SHOWING LISTING & BTU | | | LOAD. BTU LOAD SHALL REFLECT THE BTU LOAD SHOWN ON THE | | | GAS RISER ON PLANS. | | | | | | 2. PIPE SIZES FOR APPLIANCES RED LINED APPLIANCES P19G, | | | P23G & P57G SHALL BE 1-1/2" NOT 1-1/4" AS INDICATED. | | | PIPE SIZE FOR THE GAS MAIN LINE SHALL BE MINIMUM 2-1/2" | | | UPSTREAM OF APPLIANCE P24G. TABLE 402.4(2) FBC-FUEL GAS | | | -- REVISION REQUIRED. | | | | | | 3. WATER FILTER SHALL MEET NSF-42 REQUIREMENTS. MANUF. | | | SPECIFICATIONS REQUIRED AT THE TIME OF FINAL PLUMBING | | | INSPECTION. | | | | | | | | | | | | | | | | | | | | | | | | | | | . |
|