Plan Review Notes For Permit 08070127
Permit Number 08070127
Review Stop P
Sequence Number 2
Notes
Date Text
2008-08-27 10:46:30DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A120.1 CODE ANALYSIS INDICATES GROSS AREA @
 15,832SF & NET AREA @ 15,304SF, BUT THE ADDITION OF THE
 SHOWROOM, STAGE, BUSINESS, KITCHEN, BAR & WAITING AREAS
 ONLY ADD UP TO 11, 864SF. PLEASE CLARIFY. SECTIONS 1004
 & 403 & TABLES 1004.1.2 & 403.1. ALSO THE COVERED PATIO
 AREA IS NOT INCLUDED IN THE ANALYSIS. PLEASE INDICATE
 THE OCCUPANT LOAD AND IF THERE IS SEATING IN THIS AREA.
 SECTIONS 1004.8 & 403.1.3.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 2. SHT A120.1 PER TABLES 1004.1.2 & 403.1 & SECTION
 403.1.1.2, 10 WATER CLOSETS ARE REQUIRED FOR THE MEN.
 THIS MAY CHANGE WITH THE OCCUPANCY OF THE COVERED PATIO
 ESTABLISHED AND ADDED TO TOTAL.
 ****RESPONSE NOTED, BUT DUE TO NEW INFORMATION
 REQUIRED, IT IS INDICATED THAT THERE ARE "ALOT OF SEATS
 IN THE SPACE, BUT A LOT OF PEOPLE WILL TAKE JUST A
 DRINK (THIS IS A COMEDY CLUB)" (SEE ATTACHED SHEETS)
  
 3. OK
  
 4. SHT P0.1 PLUMBING SCHEDULE: ITEMS P21, P36.2, P68,
 PB4.1 & PB4.2C SHOWN ON THE SCHEDULE WERE NOT FOUND ON
 THE FLOOR PLAN. -- ITEM P45 INDICATES QTY 1 ON THE
 SCHEDULE, BUT 2 WERE FOUND ON THE FLOOR PLAN. -- ITEM
 PB1 INDICATES QTY 2 ON THE SCHEDULE, BUT 3 WERE FOUND
 ON THE FLOOR PLAN. -- ITEM PB4C INDICATES QTY 2 ON THE
 SCHEDULE, BUT ONLY 1 WAS FOUND ON THE FLOOR PLAN. --
 ITEM PB28 INDICATES QTY 5 ON THE SCHEDULE, BUT ONLY 4
 WERE FOUND ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT ITEMS P21 & P68 ARE STILL NOT
 FOUND ON THE FLOOR PLAN.
  
 5. OK
 6. OK
 7. OK
  
 8. THE WATER FILTER INDICATED ON ITEM PB4.2C SHT P0.1
 SHALL MEET THE REQUIREMENTS OF NSF-42. PLEASE SUBMIT
 MANUF. SPECIFICATION SHEETS SHOWING COMPLIANCE.
 SECTIONS 106.1.2 & 611.1.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 9. SHT P6.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 REQUIREMENTS FOR PERMIT FOLLOW:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED FOR THE
 IWH'S.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 I. N/A
 J. N/A
 K. OK
  
 L. INDICATE THE PIPE SIZE FOR EACH APPLIANCE STUB-OUT
 FROM THE BRANCH LINE. SHUT OFF VALVE SHALL BE THE SAME
 SIZE AS THE STUB-OUT FOR THE APPLIANCE. SECTION 402.
 ****RESPONSE NOTED, BUT PIPE SIZE AND VALVE TO EACH
 APPLIANCE SHALL BE FULL SIZE. SEE TABLE 402.4(6).
  
 M. OK
  
 ***********NEW COMMENT***********
  
 1B. INDICATE IF THE GAS PIPING WILL BE WELDED OR SCREW
 PIPE ON THE PLANS. IF WELDED THEN THE WELDING PROCEDURE
 AND WELDING CERTIFICATIONS & PICTURE I.D. OF THE PERSON
 WELDING THE PIPE ARE REQUIRED AT THE TIME OF GAS PERMIT
 APPLICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]