| 2008-09-12 15:25:10 | |
| | |
| | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE LIGHTING CONTROLS DO NOT MEET |
| | SECTIONS OF THE CODES GIVEN ON PREVIOUS REVIEW. SOME |
| | SPECIFIC EXAMPLES WILL BE GIVEN BELOW. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3. |
| | |
| | FOR EXAMPLE: PLANS INDICATE LIGHTING CONTROL CIRCUIT |
| | E-38 WHICH BY NOTES TAKE THIS BACK TO THE LIGHTING |
| | CONTROL PANEL *RPA*. BASED ON THE ONLY TWO SWITCH BANKS |
| | NOTED, THIS IS NOT PART OF EITHER SWITCH BANK. |
| | |
| | FOR EXAMPLE: PLEASE SEE CIRCUITS E-30 AND E20 WHICH ARE |
| | SHOWN TO EXIT/EGRESS HALLWAYS. WHERE ARE THE SEPARATE |
| | CONTROLS REQUIRED? |
| | ** PLEASE BE SURE TO SEE COMMENTS BELOW WITH RESPECT TO |
| | LIFE SAFETY NFPA-101. |
| | |
| | FOR EXAMPLE: PLEASE SHOW WHERE AND HOW AREAS AS NOTED |
| | ABOVE FOR SEPARATE CONTROLS MEET SECTIONS. THE OCCUPANT |
| | IS REQUIRED TO SEE *ALL* LIGHTING WHICH IS BEING |
| | CONTROLLED OR MEET THE EXCEPTIONS IN THE CODE. THE |
| | PLANS DO NOT SHOW THIS. |
| | |
| | |
| | ** THIS IS ONLY A COUPLE OF EXAMPLES. THIS IS GIVEN AS |
| | A BENEFIT ONLY AND IS NOT ALL ITEMS WHICH NEED TO BE |
| | ADDRESSED WITH RESPECT LIGHTING CONTROLS. |
| | |
| | 2) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.2.1, |
| | 13-415.2.ABC .2.2 FOR LIGHTING PERFORMANCE |
| | CALCULATIONS. PLEASE BE SURE TO SEE THE CODE SECTIONS |
| | AS GIVEN AND PLEASE COORDINATE ALL LIGHTING ON THE |
| | FIXTURE LEGEND AND THE CALCULATIONS. |
| | |
| | ONE EXAMPLE: PLEASE SEE FIXTURE *J* WHICH INDICATES |
| | THIS ON THE LIGHTING PERFORMANCE CALCULATIONS AS A |
| | 35WATT FIXTURE HOWEVER SEE SHEET E0.1 WHICH INDICATES |
| | THIS SAME FIXTURE AS 150WATT. |
| | |
| | ** THIS WAS ONLY ONE EXAMPLE: PLEASE COORDINATE *ALL* |
| | FIXTURES, THE NUMBER OF FIXTURES, THE TYPES OF |
| | FIXTURES, THE COUNT ETC. |
| | |
| | 3) NOTE: PLEASE SEE FBC 1006.1.2 AND NFPA-101 |
| | 7.8.1.2.2. BASED ON PLANS AND NOTES ABOVE THE LIGHTING |
| | IN EGRESS/EXIT HALLWAYS ARE BEING SHOWN ON THE LIGHTING |
| | CONTROL PANEL *RPA* WHICH IS OK, HOWEVER IF THIS |
| | LIGHTING CONTROL PANEL OR THE OVER RIDES SHOWN TURN OFF |
| | THE LIGHTING AT ANY POINT, THESE AREAS ARE LEFT IN |
| | TOTAL DARKNESS WITH NO OVER RIDE DEVICES SUCH AS FAIL |
| | SAFE OCCUPANCY SENSORS ETC. |
| | THIS IS A MAJOR LIFE SAFETY ISSUE AND BASED ON THE |
| | CODE(S) THE METHOD OF CONTROLS IN THESE AREAS AND ANY |
| | EGRESS AREA NEEDS TO BE RE-=CONSIDERED IN DESIGN. |
| | PLEASE BE SURE TO SEE THE NEXT COMMENT. |
| | |
| | 4) NOTE: PLEASE SEE TYPE *M* FOR EXAMPLE: THE FIXTURE |
| | LEGEND INDICATES THIS FIXTURE IS TO BE SELECTED HOWEVER |
| | BASED ON THIS FIXTURE BEING LOCATED IN MANY EGRESS |
| | PATHS OR CORRIDORS. |
| | AS THIS FIXTURE SIMPLY NOTES TO SEE ARCHITECTURAL FOR |
| | HEIGHTS AND THE SPECIFIC FIXTURE IS NOT CALLED OUT |
| | PLEASE KNOW A SPECIFIC FIXTURE IS REQUIRED TO BE SHOWN |
| | MEETING CODE COMPLIANCE ALONG WITH HEIGHTS/LOCATIONS |
| | ETC TO MEET FBC 11.4.4.1 |
| | |
| | 11-4.4.1 GENERAL. |
| | OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES) |
| | WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80 |
| | INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR |
| | SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO |
| | WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE |
| | FIGURE 8(A)]. OBJECTS MOUNTED WITH THEIR LEADING EDGES |
| | AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED FLOOR |
| | MAY PROTRUDE ANY AMOUNT [SEE FIGURE 8(A) AND FIGURE |
| | 8(B)]. FREE-STANDING OBJECTS MOUNTED ON POSTS OR PYLONS |
| | MAY OVERHANG 12 IN (305 MM) MAXIMUM FROM 27 INCHES TO |
| | 80 INCHES (685 MM TO 2030 MM) ABOVE THE GROUND OR |
| | FINISHED FLOOR [SEE FIGURE 8(C) AND FIGURE 8(D)]. |
| | PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR WIDTH OF |
| | AN ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE FIGURE |
| | 8(E)]. |
| | 11-4.4.2 HEADROOM. WALKS, HALLS, CORRIDORS, |
| | PASSAGEWAYS, AISLES, OR OTHER CIRCULATION SPACES SHALL |
| | HAVE 80 INCHES (2030 MM) MINIMUM CLEAR HEAD ROOM [SEE |
| | FIGURE 8(A)]. IF VERTICAL CLEARANCE OF AN AREA |
| | ADJOINING AN ACCESSIBLE ROUTE IS REDUCED TO LESS THAN |
| | 80 INCHES (2032 MM) (NOMINAL DIMENSION), A BARRIER TO |
| | WARN BLIND OR VISUALLY-IMPAIRED PERSONS SHALL BE |
| | PROVIDED [SEE FIGURE 8(C-1)]. |
| | |
| | ** BE SURE TO SEE OTHER FIXTURES IN OTHER LOCATIONS. |
| | THERE ARE THREE HALLWAYS (AS NOTED ON PLANS) WHICH TYPE |
| | *M* FIXTURES ARE OF CONCERN. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | EGRESS STAIRS PER LS 101 7.8.1.3. THE NEW PHOTO-METRICS |
| | SUBMITTED DO NOT INDICATE THE 10FT CANDLE UNDER NORMAL |
| | LEVELS. |
| | *** ALL STAIRS INCLUDING AREAS WHERE PERFORMANCES ARE |
| | LOCATED. ** DURING TIMES OF PERFORMANCES LIGHTING |
| | LEVELS ARE PERMITTED TO MEET EXCEPTIONS HOWEVER ALL |
| | OTHER NORMAL TIMES OF OCCUPANCY MUST MEET THE *MINIMUM* |
| | FOR THE LIFE SAFETY CODE. |
| | DUE TO THE AMOUNT OF THE SCOPE OF WORK SOME BATHROOM |
| | AREAS WILL BE REQUIRED TO ADD BATTERY BACK UP LIGHT |
| | FIXTURES OF SOME KIND. FOR EXAMPLE: PLEASE SEE RESTROOM |
| | AND CORRIDOR IN NE CORNER TENANT SPACE. |
| | |
| | 6) NOTE: PLEASE COORDINATE PANELS AND RISER: |
| | |
| | FOR EXAMPLE: PANEL *H1* SHOWS A SUB-FEED TO A |
| | TRANSFORMER *T1* YET THERE IS NO TRANSFORMER *T1* ON |
| | RISER OR PLANS. |
| | 240.21,310.16,240.4, 450.3 ETC |
| | FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 7) NOTE: PLEASE EXPLAIN HOW THE THREE POLE BREAKERS ON |
| | PANELS K1 AND H1 TAKE SPACE FOR 6-POLES EACH. |
| | WHAT TYPE OF BREAKER DOES THIS? PLEASE SUPPLY CUT SHEET |
| | FOR THIS TYPE OF BREAKER OR IS THIS A MISPRINT OF SOME |
| | SORT? NE C110.3,90.7 |
| | |
| | 8) NOTE: PLEASE SHOW COMPLETE LOAD CALCULATIONS ON |
| | EXISTING SERVICE IN WHICH NEW LOADS ARE BEING ADDED. |
| | PLEASE EXPLAIN HOW THE LOAD FOR WHAT IS BEING ASSUMED |
| | AS TRANSFORMER TEA IS NOT THE SAME ON PANEL *H1*. |
| | 220.87 |
| | FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE AT THIS TIME. ONE SET OF ELECTRICAL PLANS ARE |
| | BEING RETAINED AND WILL BE PLACED WITH PREVIOUS PLANS |
| | RETAINED. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |