Plan Review Notes
Plan Review Notes For Permit 08070127
Permit Number 08070127
Review Stop E
Sequence Number 2
Notes
Date Text
2008-09-12 15:25:10 
  
  
  
 ** DENIED 2ND REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE THE LIGHTING CONTROLS DO NOT MEET
 SECTIONS OF THE CODES GIVEN ON PREVIOUS REVIEW. SOME
 SPECIFIC EXAMPLES WILL BE GIVEN BELOW.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3.
  
 FOR EXAMPLE: PLANS INDICATE LIGHTING CONTROL CIRCUIT
 E-38 WHICH BY NOTES TAKE THIS BACK TO THE LIGHTING
 CONTROL PANEL *RPA*. BASED ON THE ONLY TWO SWITCH BANKS
 NOTED, THIS IS NOT PART OF EITHER SWITCH BANK.
  
 FOR EXAMPLE: PLEASE SEE CIRCUITS E-30 AND E20 WHICH ARE
 SHOWN TO EXIT/EGRESS HALLWAYS. WHERE ARE THE SEPARATE
 CONTROLS REQUIRED?
 ** PLEASE BE SURE TO SEE COMMENTS BELOW WITH RESPECT TO
 LIFE SAFETY NFPA-101.
  
 FOR EXAMPLE: PLEASE SHOW WHERE AND HOW AREAS AS NOTED
 ABOVE FOR SEPARATE CONTROLS MEET SECTIONS. THE OCCUPANT
 IS REQUIRED TO SEE *ALL* LIGHTING WHICH IS BEING
 CONTROLLED OR MEET THE EXCEPTIONS IN THE CODE. THE
 PLANS DO NOT SHOW THIS.
  
  
 ** THIS IS ONLY A COUPLE OF EXAMPLES. THIS IS GIVEN AS
 A BENEFIT ONLY AND IS NOT ALL ITEMS WHICH NEED TO BE
 ADDRESSED WITH RESPECT LIGHTING CONTROLS.
  
 2) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.2.1,
 13-415.2.ABC .2.2 FOR LIGHTING PERFORMANCE
 CALCULATIONS. PLEASE BE SURE TO SEE THE CODE SECTIONS
 AS GIVEN AND PLEASE COORDINATE ALL LIGHTING ON THE
 FIXTURE LEGEND AND THE CALCULATIONS.
  
 ONE EXAMPLE: PLEASE SEE FIXTURE *J* WHICH INDICATES
 THIS ON THE LIGHTING PERFORMANCE CALCULATIONS AS A
 35WATT FIXTURE HOWEVER SEE SHEET E0.1 WHICH INDICATES
 THIS SAME FIXTURE AS 150WATT.
  
 ** THIS WAS ONLY ONE EXAMPLE: PLEASE COORDINATE *ALL*
 FIXTURES, THE NUMBER OF FIXTURES, THE TYPES OF
 FIXTURES, THE COUNT ETC.
  
 3) NOTE: PLEASE SEE FBC 1006.1.2 AND NFPA-101
 7.8.1.2.2. BASED ON PLANS AND NOTES ABOVE THE LIGHTING
 IN EGRESS/EXIT HALLWAYS ARE BEING SHOWN ON THE LIGHTING
 CONTROL PANEL *RPA* WHICH IS OK, HOWEVER IF THIS
 LIGHTING CONTROL PANEL OR THE OVER RIDES SHOWN TURN OFF
 THE LIGHTING AT ANY POINT, THESE AREAS ARE LEFT IN
 TOTAL DARKNESS WITH NO OVER RIDE DEVICES SUCH AS FAIL
 SAFE OCCUPANCY SENSORS ETC.
 THIS IS A MAJOR LIFE SAFETY ISSUE AND BASED ON THE
 CODE(S) THE METHOD OF CONTROLS IN THESE AREAS AND ANY
 EGRESS AREA NEEDS TO BE RE-=CONSIDERED IN DESIGN.
 PLEASE BE SURE TO SEE THE NEXT COMMENT.
  
 4) NOTE: PLEASE SEE TYPE *M* FOR EXAMPLE: THE FIXTURE
 LEGEND INDICATES THIS FIXTURE IS TO BE SELECTED HOWEVER
 BASED ON THIS FIXTURE BEING LOCATED IN MANY EGRESS
 PATHS OR CORRIDORS.
 AS THIS FIXTURE SIMPLY NOTES TO SEE ARCHITECTURAL FOR
 HEIGHTS AND THE SPECIFIC FIXTURE IS NOT CALLED OUT
 PLEASE KNOW A SPECIFIC FIXTURE IS REQUIRED TO BE SHOWN
 MEETING CODE COMPLIANCE ALONG WITH HEIGHTS/LOCATIONS
 ETC TO MEET FBC 11.4.4.1
  
 11-4.4.1 GENERAL.
 OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES)
 WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80
 INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR
 SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE
 FIGURE 8(A)]. OBJECTS MOUNTED WITH THEIR LEADING EDGES
 AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED FLOOR
 MAY PROTRUDE ANY AMOUNT [SEE FIGURE 8(A) AND FIGURE
 8(B)]. FREE-STANDING OBJECTS MOUNTED ON POSTS OR PYLONS
 MAY OVERHANG 12 IN (305 MM) MAXIMUM FROM 27 INCHES TO
 80 INCHES (685 MM TO 2030 MM) ABOVE THE GROUND OR
 FINISHED FLOOR [SEE FIGURE 8(C) AND FIGURE 8(D)].
 PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR WIDTH OF
 AN ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE FIGURE
 8(E)].
 11-4.4.2 HEADROOM. WALKS, HALLS, CORRIDORS,
 PASSAGEWAYS, AISLES, OR OTHER CIRCULATION SPACES SHALL
 HAVE 80 INCHES (2030 MM) MINIMUM CLEAR HEAD ROOM [SEE
 FIGURE 8(A)]. IF VERTICAL CLEARANCE OF AN AREA
 ADJOINING AN ACCESSIBLE ROUTE IS REDUCED TO LESS THAN
 80 INCHES (2032 MM) (NOMINAL DIMENSION), A BARRIER TO
 WARN BLIND OR VISUALLY-IMPAIRED PERSONS SHALL BE
 PROVIDED [SEE FIGURE 8(C-1)].
  
 ** BE SURE TO SEE OTHER FIXTURES IN OTHER LOCATIONS.
 THERE ARE THREE HALLWAYS (AS NOTED ON PLANS) WHICH TYPE
 *M* FIXTURES ARE OF CONCERN.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 EGRESS STAIRS PER LS 101 7.8.1.3. THE NEW PHOTO-METRICS
 SUBMITTED DO NOT INDICATE THE 10FT CANDLE UNDER NORMAL
 LEVELS.
 *** ALL STAIRS INCLUDING AREAS WHERE PERFORMANCES ARE
 LOCATED. ** DURING TIMES OF PERFORMANCES LIGHTING
 LEVELS ARE PERMITTED TO MEET EXCEPTIONS HOWEVER ALL
 OTHER NORMAL TIMES OF OCCUPANCY MUST MEET THE *MINIMUM*
 FOR THE LIFE SAFETY CODE.
 DUE TO THE AMOUNT OF THE SCOPE OF WORK SOME BATHROOM
 AREAS WILL BE REQUIRED TO ADD BATTERY BACK UP LIGHT
 FIXTURES OF SOME KIND. FOR EXAMPLE: PLEASE SEE RESTROOM
 AND CORRIDOR IN NE CORNER TENANT SPACE.
  
 6) NOTE: PLEASE COORDINATE PANELS AND RISER:
  
 FOR EXAMPLE: PANEL *H1* SHOWS A SUB-FEED TO A
 TRANSFORMER *T1* YET THERE IS NO TRANSFORMER *T1* ON
 RISER OR PLANS.
 240.21,310.16,240.4, 450.3 ETC
 FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION.
  
 7) NOTE: PLEASE EXPLAIN HOW THE THREE POLE BREAKERS ON
 PANELS K1 AND H1 TAKE SPACE FOR 6-POLES EACH.
 WHAT TYPE OF BREAKER DOES THIS? PLEASE SUPPLY CUT SHEET
 FOR THIS TYPE OF BREAKER OR IS THIS A MISPRINT OF SOME
 SORT? NE C110.3,90.7
  
 8) NOTE: PLEASE SHOW COMPLETE LOAD CALCULATIONS ON
 EXISTING SERVICE IN WHICH NEW LOADS ARE BEING ADDED.
 PLEASE EXPLAIN HOW THE LOAD FOR WHAT IS BEING ASSUMED
 AS TRANSFORMER TEA IS NOT THE SAME ON PANEL *H1*.
 220.87
 FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE AT THIS TIME. ONE SET OF ELECTRICAL PLANS ARE
 BEING RETAINED AND WILL BE PLACED WITH PREVIOUS PLANS
 RETAINED.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  