| 2008-07-09 11:57:45 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. SHT A120.1 CODE ANALYSIS INDICATES GROSS AREA @ |
| | 15,832SF & NET AREA @ 15,304SF, BUT THE ADDITION OF THE |
| | SHOWROOM, STAGE, BUSINESS, KITCHEN, BAR & WAITING AREAS |
| | ONLY ADD UP TO 11, 864SF. PLEASE CLARIFY. SECTIONS 1004 |
| | & 403 & TABLES 1004.1.2 & 403.1. ALSO THE COVERED PATIO |
| | AREA IS NOT INCLUDED IN THE ANALYSIS. PLEASE INDICATE |
| | THE OCCUPANT LOAD AND IF THERE IS SEATING IN THIS AREA. |
| | SECTIONS 1004.8 & 403.1.3. |
| | |
| | 2. SHT A120.1 PER TABLES 1004.1.2 & 403.1 & SECTION |
| | 403.1.1.2, 10 WATER CLOSETS ARE REQUIRED FOR THE MEN. |
| | THIS MAY CHANGE WITH THE OCCUPANCY OF THE COVERED PATIO |
| | ESTABLISHED AND ADDED TO TOTAL. |
| | |
| | 3. BECAUSE OF THE TOTAL AMOUNT OF SEATING THE UTILITY |
| | DEPT., INDUSTRIAL PRETREATMENT, ENVIRONMENTAL |
| | COMPLIANCE SHALL BE CONTACTED TO DETERMINE THE |
| | REQUIREMENTS FOR THE GREASE INTERCEPTOR. PLEASE CONTACT |
| | RODNEY (561) 644-1821, FAX (561) 822-2287 OR E-MAIL HIM |
| | AT [email protected]. ARTICLE III SECTION 90-124(7). |
| | |
| | 4. SHT P0.1 PLUMBING SCHEDULE: ITEMS P21, P36.2, P68, |
| | PB4.1 & PB4.2C SHOWN ON THE SCHEDULE WERE NOT FOUND ON |
| | THE FLOOR PLAN. -- ITEM P45 INDICATES QTY 1 ON THE |
| | SCHEDULE, BUT 2 WERE FOUND ON THE FLOOR PLAN. -- ITEM |
| | PB1 INDICATES QTY 2 ON THE SCHEDULE, BUT 3 WERE FOUND |
| | ON THE FLOOR PLAN. -- ITEM PB4C INDICATES QTY 2 ON THE |
| | SCHEDULE, BUT ONLY 1 WAS FOUND ON THE FLOOR PLAN. -- |
| | ITEM PB28 INDICATES QTY 5 ON THE SCHEDULE, BUT ONLY 4 |
| | WERE FOUND ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 5. SHT P2.1 ITEM P48 SHALL DRAIN INTO THE SANITARY |
| | SYSTEM AND NOT THE GREASE SYSTEM. ARTICLE III SECTION |
| | 90-124(7)(B). PLEASE SHOW PROPER CONNECTION. |
| | |
| | 6. SHT P2.1 ITEM P61 INDICATED ON THE FLOOR PLAN IS NOT |
| | SHOWN ON THE SCHEDULE SHT P0.1. PLEASE CORRELATE. |
| | SECTION 106.1.1. |
| | |
| | 7. SHT P5.1 FLOOR SINK TO ITEM 48 SHALL DRAIN INTO THE |
| | SANITARY SYSTEM AND NOT THE GREASE SYSTEM. ARTICLE III |
| | SECTION 90-124(7)(B). PLEASE SHOW PROPER CONNECTION. |
| | |
| | 8. THE WATER FILTER INDICATED ON ITEM PB4.2C SHT P0.1 |
| | SHALL MEET THE REQUIREMENTS OF NSF-42. PLEASE SUBMIT |
| | MANUF. SPECIFICATION SHEETS SHOWING COMPLIANCE. |
| | SECTIONS 106.1.2 & 611.1. |
| | |
| | 9. SHT P6.1 A SEPARATE GAS PERMIT IS REQUIRED. THE |
| | REQUIREMENTS FOR PERMIT FOLLOW: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN |
| | COMMENT 9(A) IS ADDRESSED. |
| | |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | G. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | K. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. -- (NO UNIONS |
| | INDICATED) |
| | |
| | L. INDICATE THE PIPE SIZE FOR EACH APPLIANCE STUB-OUT |
| | FROM THE BRANCH LINE. SHUT OFF VALVE SHALL BE THE SAME |
| | SIZE AS THE STUB-OUT FOR THE APPLIANCE. SECTION 402. |
| | |
| | M. SHUT OFF VALVES ARE REQUIRED FOR LINES 1 & 2 AS THEY |
| | ENTER THE TENANT SPACE. SECTION 409.3.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |