Plan Review Notes
Plan Review Notes For Permit 08070127
Permit Number 08070127
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-07-24 14:11:15***DENIED***
  
 1) PLEASE ADD THE FOLLOWING CODE TO APPLICABLE CODE
 SECTION:
 A) FIRE SPRINKLER WORK SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 13, 2003.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL. ADDITIONALLY, PROVIDE A FIRE
 SPRINKLER LAYOUT WITH MASTER PERMIT SUBMITTAL.
  
 3) EXISTING BUILDING FIRE PROTECTION SYSTEMS SHALL
 REMAIN IN SERVICE. CONTACT WPB BUREAU OF FIRE
 PREVENTION AT (561) 804-4724 SHOULD ANY INTERUPTION OF
 REQUIRED SYSTEMS OCCUR.
  
 4) JOB SITE TO BE CLEANED OF EXCESS DEBRIS DAILY OR
 MORE FREQUENTLY TO MAINTAIN SAFE OPERATION.
  
 5) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING THAT IS SPECIFIC TO THIS PROJECT.
  
 6) PROVIDE PRESCRIPTIVE STENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDS.
  
 7) KNOX BOX IS REQUIRED FOR AFTER NORMAL BUSINESS HOURS
 EMERGENCY SERVICE ACCESS. CONTACT WPB BUREAU OF FIRE
 PREVENTION AT (561) 804-4724 FOR ASSISTANCE.
  
 8) EGRESS DOORS SERVING AN AREA OR ROOM THAT SERVES
 GREATER THAN (100) OCCUPANTS SHALL BE PROVIDED WITH
 PANIC OR FIRE EXIT HARDWARE.CLEARLY IDENTIFY APPLICABLE
 DOORS. RATED DOORS SHALL BE PROVIDED WITH UL LISTED
 CLOSERS FOR POSITIVE LATCH EFFECT. PLEASE ADD TO DOOR
 SCHEDULE.
  
 9) OCCUPANT LOAD SIGNS TO BE POSTED PRIOR TO FINAL
 INSPECTION.
  
 10) RAMPS TO COMPLY WITH NFPA 101, SEC. 7.2.5.
  
 11) DOOR SWINGS IN AREAS OR ROOMS SERVING (50) OR MORE
 OCCUPANTS SHALL SWING IN THE DIRECTION OF TRAVEL.
  
 12) HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM. NEW HOOD SUPPRESSION
 SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF UL 300
 FOR WET CHEMICAL AGENT. SEPARATE SHOP DRAWINGS AND
 PERMIT REQUIRED FOR NEW OR ALTERED HOOD/SUPPRESSION
 SYSTEMS.
  
 13) SOFFITS SHALL NOT INTERFERE WITH OR OBSTRUCT FIRE
 SPRINKLER COVERAGE.
  
 14) SOME SHEETS ILLUSTRATE AN EXIT SIGN LEADING
 OCCUPANTS FROM THE MAIN EAST EXIT HALLWAY INTO A
 SEATING AREA WITH OBSTRUCTION OF TABLES AND CHAIRS.
 PLEASE CORRECT AND CORRELATE ALL SHEETS.
  
 15) ELECTRICAL POWER PLAN (SHEET E-3.1) DOES NOT
 INDICATE ANY LAY OUT OF FIRE ALARM EQUIPMENT. IN
 ADDITION, SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED
 FOR FIRE ALARM REMODEL OR INSTALLATION.
  
 16) HOW WILL THIS PROJECT IMPACT EXISTING MEANS OF
 EGRESS, MORE SPECIFICALLY EXIT DISCHARGE?
  
 17) THE DOOR SWING FROM THE VESTIBULE IS CONFLICTING ON
 DIFFERENT SHEETS. PLEASE CORRELATE INFORMATION.
  
 18) CONTACT BUREAU OF FIRE PREVENTION PRIOR TO CUTTING
 OR WELDING OPERATIONS. WORK SHALL COMPLY WITH NFPA
 51B.
  
 19) DUCT SMOKE DETECTORS IN ADDITION TO FAN SHUT DOWN,
 SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 20) PLEASE EXPLAIN HOW SMOKE WOULD BE REMOVED OR
 RELOCATED SHOULD A FIRE EMERGENCY OCCUR.
  
 21) FIRE ALARM SYSTEM TO BE UL CERTIFICATED FOR CENTRAL
 STATION SERVICE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  