| Date |
Text |
| 2008-07-18 17:14:45 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: **** PLEASE READ **** |
| | IT IS IMPORTANT TO UNDERSTAND THAT THE PLANS SUBMITTED |
| | ARE NOT COMPLETE. THERE ARE SEVERAL ITEMS MISSING FROM |
| | MINIMUM CODE COMPLIANCE DESIGN. AS MANY OF THESE ITEMS |
| | ARE NOT SHOWN A COMPLETE REVIEW FOR MINIMUM CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE BE SURE |
| | TO SEE ALL COMMENTS BELOW AND UNDERSTAND THERE MAY VERY |
| | WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | ** CALLED KAMM CONSULTING AND SPOKE TO ART KAMM WITH |
| | RESPECT TO PLANS. MR. KAMM MADE COMMENT THAT INCORRECT |
| | PLANS WERE SIGNED, SEALED AND SUBMITTED. |
| | ONE COPY OF ELECTRICAL PLANS WERE RETAINED. |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETE PLANS WITH ALL |
| | CIRCUITING FOR ALL LIGHTING. |
| | NEC 408, 240.4, 310.16 ETC |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY |
| | LIGHTS AND EXIT LIGHTS. |
| | |
| | 4) NOTE: PLEASE SUBMIT PLANS SHOWING COMPLIANCE WITH |
| | FBC 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. MOST |
| | REQUIRED LIGHTING CONTROLS ARE MISSING FROM PLANS. |
| | |
| | 5) NOTE: PLEASE COMPLETE PLANS FOR IDENTIFICATION OF |
| | ALL LIGHTING FIXTURES. PLEASE SUBMIT COMPLETE LIGHTING |
| | PERFORMANCE CALCULATIONS PER 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2. |
| | PLEASE SEE THE PARTIAL LIGHTING DENSITIES SHOWN ON |
| | E-2.1 ARE NOT CODE COMPLIANT IN ANY WAY. |
| | |
| | 6) NOTE: PLEASE SEE THE CONDUCTORS ON THE SECONDARY |
| | SIDE OF TRANSFORMER TEA TO PANEL K1 SHALL MEET OR |
| | EXCEED THE OVER CURRENT PROTECTION IN WHICH THE TAPPED |
| | CONDUCTORS TERMINATES. TYPICALLY IT IS PERMITTED TO GO |
| | TO THE NEXT SIZE UP HOWEVER NOT ON THE SECONDARY SIDE |
| | OF A TRANSFORMER. |
| | 240.4,310.16,240.21,240.6 ETC |
| | ** THIS IS A LIFE SAFETY AND FIRE HAZARD AND SHALL BE |
| | CORRECTED EVEN IF EXISTING. |
| | |
| | 7) NOTE: PLEASE SEE RISER SHOWS PANELS E AND F YET THE |
| | PANEL SCHEDULES WERE NOT SUBMITTED ON SHOWN ON PLANS. |
| | 408.4, 215.5, 240.21, 408.36 |
| | FBC 106.3.5.1.2, 106.1.1 |
| | |
| | 8) NOTE: PLEASE SUBMIT PHOTO-METRICS AND LIGHTING |
| | LEVELS FOR ALL EGRESS PATHS. PLEASE SEE NFPA-101 2006 |
| | 7.8.1.3, 7.9.2.1 |
| | AS FIXTURES ARE NOT COMPLETEAND UNCLEAR IT IS NOT |
| | KNOWN ALL FIXTURES WHICH MAY PROVIDE THE BACK UP |
| | ILLUMINATION. |
| | |
| | 9) NOTE: PLEASE SEE 450.13 AS THE TRANSFORMER ARE NOTED |
| | AS BEING ABOVE THE CEILING WHICH IS NOT PERMITTED. |
| | |
| | 10) NOTE: PLEASE SEE A NOTE ON PLANS MENTIONS THE |
| | REQUIRED GFI PROTECTION HOWEVER PLEASE INDICATE THE |
| | PROTECTION BY THE DEVICE OR THE CIRCUIT. PLEASE SEE |
| | THAT ALL RECEPTACLES IN KITCHEN AREAS WHETHER OR NOT |
| | THE FEED COUNTER SPACES SHALL BE PROTECTED FOR 15/20AMP |
| | AND 125V. |
| | PLEASE SEE RECEPTACLES WITHIN 6FT OF WET BAR SINKS |
| | SHALL ALSO CONTAIN GFI PROTECTION. |
| | 210.8B2 |
| | |
| | 11) NOTE: PLEASE COMPLETE PANEL SCHEDULE TO ALL ROOMS |
| | AND AREAS IN WHICH CIRCUITS FEED. THE USE OF *LIGHTING |
| | OR RECEPTACLES* IS NOT ACCEPTABLE. 408.4 |
| | FBC 106.1.1,106.1.2,106.5 |
| | |
| | 12) NOTE: PLEASE BE SURE THE LATEST ADOPTED CODES FOR |
| | ELECTRICAL, LIFE SAFETY DESIGN IS STATED ON PLANS. 2005 |
| | NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 13) NOTE: PLEASE SUBMIT COMPLETED PLANS FOR BASE FIRE |
| | ALARM SYSTEM. |
| | PLEASE BE SURE TO SEE FBC 11-4.28.1,.2 AND .3 FOR |
| | MINIMUM DEVICES FOR ADA COMPLIANCE. |
| | |
| | 14) NOTE: PLEASE SEE LIFE SAFETY CODE CHAPTER 7 |
| | NFPA-101.7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT |
| | IS NEITHER AN EXIT NOR A WAY OF EXIT ACCESS AND THAT IS |
| | LOCATED OR ARRANGED SO THAT IT IS LIKELY TO BE MISTAKEN |
| | FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN THAT READS AS |
| | FOLLOWS: NO EXIT 7 |
| | 7.8.10.3.2 THE NO EXIT SIGN SHALL HAVE THE WORD NO IN |
| | LETTERS 51 MM (2 IN.) HIGH, WITH A STROKE WIDTH OF 9.5 |
| | MM (IN.), AND THE WORD EXIT IN LETTERS 25 MM (1 IN.) |
| | HIGH, WITH THE WORD EXIT BELOW THE WORD NO, UNLESS SUCH |
| | SIGN IS AN APPROVED EXISTING SIGN. |
| | |
| | |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |