Plan Review Notes
Plan Review Notes For Permit 08070127
Permit Number 08070127
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-18 17:14:45** DENIED REVIEW **
  
 1) NOTE: **** PLEASE READ ****
 IT IS IMPORTANT TO UNDERSTAND THAT THE PLANS SUBMITTED
 ARE NOT COMPLETE. THERE ARE SEVERAL ITEMS MISSING FROM
 MINIMUM CODE COMPLIANCE DESIGN. AS MANY OF THESE ITEMS
 ARE NOT SHOWN A COMPLETE REVIEW FOR MINIMUM CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE BE SURE
 TO SEE ALL COMMENTS BELOW AND UNDERSTAND THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW.
 ** CALLED KAMM CONSULTING AND SPOKE TO ART KAMM WITH
 RESPECT TO PLANS. MR. KAMM MADE COMMENT THAT INCORRECT
 PLANS WERE SIGNED, SEALED AND SUBMITTED.
 ONE COPY OF ELECTRICAL PLANS WERE RETAINED.
  
 2) NOTE: PLEASE SUBMIT COMPLETE PLANS WITH ALL
 CIRCUITING FOR ALL LIGHTING.
 NEC 408, 240.4, 310.16 ETC
 FBC 106.1.1, 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY
 LIGHTS AND EXIT LIGHTS.
  
 4) NOTE: PLEASE SUBMIT PLANS SHOWING COMPLIANCE WITH
 FBC 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. MOST
 REQUIRED LIGHTING CONTROLS ARE MISSING FROM PLANS.
  
 5) NOTE: PLEASE COMPLETE PLANS FOR IDENTIFICATION OF
 ALL LIGHTING FIXTURES. PLEASE SUBMIT COMPLETE LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2,
 13-415.2.ABC.1.1, .1.2.
 PLEASE SEE THE PARTIAL LIGHTING DENSITIES SHOWN ON
 E-2.1 ARE NOT CODE COMPLIANT IN ANY WAY.
  
 6) NOTE: PLEASE SEE THE CONDUCTORS ON THE SECONDARY
 SIDE OF TRANSFORMER TEA TO PANEL K1 SHALL MEET OR
 EXCEED THE OVER CURRENT PROTECTION IN WHICH THE TAPPED
 CONDUCTORS TERMINATES. TYPICALLY IT IS PERMITTED TO GO
 TO THE NEXT SIZE UP HOWEVER NOT ON THE SECONDARY SIDE
 OF A TRANSFORMER.
 240.4,310.16,240.21,240.6 ETC
 ** THIS IS A LIFE SAFETY AND FIRE HAZARD AND SHALL BE
 CORRECTED EVEN IF EXISTING.
  
 7) NOTE: PLEASE SEE RISER SHOWS PANELS E AND F YET THE
 PANEL SCHEDULES WERE NOT SUBMITTED ON SHOWN ON PLANS.
 408.4, 215.5, 240.21, 408.36
 FBC 106.3.5.1.2, 106.1.1
  
 8) NOTE: PLEASE SUBMIT PHOTO-METRICS AND LIGHTING
 LEVELS FOR ALL EGRESS PATHS. PLEASE SEE NFPA-101 2006
 7.8.1.3, 7.9.2.1
 AS FIXTURES ARE NOT COMPLETEAND UNCLEAR IT IS NOT
 KNOWN ALL FIXTURES WHICH MAY PROVIDE THE BACK UP
 ILLUMINATION.
  
 9) NOTE: PLEASE SEE 450.13 AS THE TRANSFORMER ARE NOTED
 AS BEING ABOVE THE CEILING WHICH IS NOT PERMITTED.
  
 10) NOTE: PLEASE SEE A NOTE ON PLANS MENTIONS THE
 REQUIRED GFI PROTECTION HOWEVER PLEASE INDICATE THE
 PROTECTION BY THE DEVICE OR THE CIRCUIT. PLEASE SEE
 THAT ALL RECEPTACLES IN KITCHEN AREAS WHETHER OR NOT
 THE FEED COUNTER SPACES SHALL BE PROTECTED FOR 15/20AMP
 AND 125V.
 PLEASE SEE RECEPTACLES WITHIN 6FT OF WET BAR SINKS
 SHALL ALSO CONTAIN GFI PROTECTION.
 210.8B2
  
 11) NOTE: PLEASE COMPLETE PANEL SCHEDULE TO ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED. THE USE OF *LIGHTING
 OR RECEPTACLES* IS NOT ACCEPTABLE. 408.4
 FBC 106.1.1,106.1.2,106.5
  
 12) NOTE: PLEASE BE SURE THE LATEST ADOPTED CODES FOR
 ELECTRICAL, LIFE SAFETY DESIGN IS STATED ON PLANS. 2005
 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 13) NOTE: PLEASE SUBMIT COMPLETED PLANS FOR BASE FIRE
 ALARM SYSTEM.
 PLEASE BE SURE TO SEE FBC 11-4.28.1,.2 AND .3 FOR
 MINIMUM DEVICES FOR ADA COMPLIANCE.
  
 14) NOTE: PLEASE SEE LIFE SAFETY CODE CHAPTER 7
 NFPA-101.7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT
 IS NEITHER AN EXIT NOR A WAY OF EXIT ACCESS AND THAT IS
 LOCATED OR ARRANGED SO THAT IT IS LIKELY TO BE MISTAKEN
 FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN THAT READS AS
 FOLLOWS: NO EXIT 7
 7.8.10.3.2 THE NO EXIT SIGN SHALL HAVE THE WORD NO IN
 LETTERS 51 MM (2 IN.) HIGH, WITH A STROKE WIDTH OF 9.5
 MM (IN.), AND THE WORD EXIT IN LETTERS 25 MM (1 IN.)
 HIGH, WITH THE WORD EXIT BELOW THE WORD NO, UNLESS SUCH
 SIGN IS AN APPROVED EXISTING SIGN.
  
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]