Plan Review Notes
Plan Review Notes For Permit 08070127
Permit Number 08070127
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-23 07:18:39BUILDING PLAN REVIEW
 PERMIT: 08070127
 ADD: 550 S ROSEMARY # 250
 CONT: ALLIANCE
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 105.13.1
 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR
 TO PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPECTION PLAN
 PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B)THRESHOLD INSPECTOR
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT JERALD SMITH MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6667 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BUILSING, REQUIRED STATEMENT,
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3) NOTE ISSUED PERMIT NUMBER 08060710 WILL ALSO NEED TO
 MEET THE REQUIREMENTS FOR THRESHOLD BUILDINGS LISTED IN
 COMMENT # 2A-2C. FL S. S. 553.71(7) .
  
 4) LIFE SAFETY PLAN A120.1 IN THE PLAN NOTES AND IN THE
 REQUIRED EGRESS WIDTHS ( 0.3 STAIRS AND 0.2 HORIZONTAL
 AREAS) DOES NOT INDICATE THAT SMOKE CONTROLLED SEATING
 HAS BEEN ACHIEVED AND THE CALCULATIONS ARE BASED ON
 SMOKE CONTROLLED SEATING SEE 1024.6.1. PLEASE PROVIDE
 EITHER COMPLIANCE WITH ALL THE REQUIREMENTS OF 1024.6.2
 OR INDICATE THE FACTORS IN 1024.6.1 FOR RAMPS AND
 STAIRS.
 NOTE A300.1 THE HIGHEST RAISED FLOOR SECTION APPEARS TO
 ONLY BE 14'-0" TO THE CORRUGATED ROOF DECK NOT MEETING
 THE REQUIREMENT OF 1024.6..2.2.
  
 5) LIFE SAFETY PLAN A120.1 & A130.2 THE MAIN ENTRY
 DOOR# 8 INTO THE SHOW ROOM SWING IN THE WRONG
 DIRECTION, PLEASE SEE 1024.2 & 1008.1.2.
 1024.2 EVERY ASSEMBLY OCCUPANCY SHALL BE PROVIDED WITH
 A MAIN ENTRANCE/EXIT. THE MINIMUM AGGREGATE WIDTH OF
 THE MAIN ENTRANCE FOR GROUP A OCCUPANCIES SHALL BE
 SUFFICIENT TO ACCOMMODATE 50 PERCENT OF THE OCCUPANT
 LOAD AND SHALL BE AT THE LEVEL OF EXIT DISCHARGE OR
 SHALL CONNECT TO A STAIRWAY OR RAMP LEADING TO A
 STREET. EACH LEVEL OF A GROUP A OCCUPANCY SHALL HAVE
 ACCESS TO A MAIN EXIT AND SUCH ACCESS SHALL HAVE
 SUFFICIENT CAPACITY TO ACCOMMODATE 50 PERCENT OF THE
 OCCUPANT LOAD OF SUCH LEVELS. WHERE THE MAIN EXIT FROM
 AN ASSEMBLY OCCUPANCY IS THROUGH A LOBBY OR FOYER, THE
 AGGREGATE CAPACITY OF ALL EXITS FROM THE LOBBY OR FOYER
 SHALL BE PERMITTED TO PROVIDE THE REQUIRED CAPACITY OF
 THE MAIN EXIT REGARDLESS OF WHETHER ALL SUCH EXITS
 SERVE AS ENTRANCES TO THE BUILDING.
  
 1008.1.2 EGRESS DOORS SHALL BE SIDE SWINGING. DOORS
 SHALL BE SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE
 SERVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A
 GROUP H OCCUPANCY.
  
 6) WHILE THE FRONT ENTRY DOORS 1,2 & 3 WILL TAKE 50% OF
 THE OCCUPANT LOAD THE OTHER 50% OF THE OCCUPANT LOAD
 WILL NEED TO BE TAKEN THROUGH THE OTHER DESIGNATED
 EXITS, NO OF THE UNKNOWNS IS AT THE EXIT DOOR# 4 THERE
 IS A COVERED PATIO AREA BUT IS NOT CLEAR AS TO WHAT THE
 DOUBLE HASHED LINE INDICATES IS THIS A FENCED IN AREA
 OR IS THIS OPEN FOR THE OCCUPANTS CAN DISPERSE ONCE
 THEY ARE THROUGH DOOR # 4.
 IF THIS IS A FENCED IN AREA THEN BOTH DOORS 4& 5 OR
 12'-0" OF DOOR OPENING ARE EXITING A 5'-0" AREA, PLEASE
 CLARIFY THIS AREA. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED. 1004.5 EGRESS CONVERGENCE.
  
 7) LS A120.1 & A130.2 & A130.3 EXIT HALLWAY
 CONVERGENCE, THE EXIT CORRIDOR THAT BACKS UP TO THE
 SHOW ROOM IS 5'-5 1/2" WIDE AND OPENS UP TO 10'-4 PLUS
 STAIRS FROM THE UPPER SHOWROOM SEATING AREA. THE
 CAPACITY OF THE HALLWAY IS 620 OCCUPANTS BUT DROPS TO
 170 OCCUPANTS AT DOOR # 5. DOOR # 6 AGAIN SWINGS THE
 WRONG WAY TO BE CONSIDERED AN EGRESS DOOR,1008.1.2.
 EVEN WITH BOTH DOORS SWINGING IN THE DIRECTION OF
 TRAVEL YOU WOULD ONLY BE ALLOWED 340 OCCUPANTS THROUGH
 CREATING A CONVERGENCE ( BOTTLE NECKING EFFECT).
 1004.5.
  
 8) LS A120.1 FROM DOORWAY# 5 THROUGH THE CORRIDOR THAT
 LEADS TO THE LOBBY OR VESTIBULE AREA DOES NOT HAVE
 EXIT/ EMERGENCY LIGHT WITH BATTERY BACK UP.
  
 9) LS A120 VESTIBULE IS CURRENTLY SET UP AS A WAITING
 AREA FOR THE NEXT SHOW AND NO EXIT PATH IS PROVIDED FOR
 THE EXITING PATTRENS. CURRENTLY THIS AREA WILL HOLD
 OVER 100 OCCUPANTS REQUIRING TWO EXITS AND OVER 1/3RD
 THE DISTANCE APART. SEE TABLE 1014.1. PLEASE REVISE
 SHOWING THE DOORS FROM THE SHOW ROOM REVERSED AS AN
 EXIT (COMMENT# 5) . INDICATE THE EGRESS PATH FROM THE
 SHOW ROOM AND HOW
 CROWD CONTROL WILL BE ESTABLISHED FOR THOUGHS EXITING
 AND FOR THE PATTRENS WAITNG FOR THE NEXT SHOW.
  
 10) SHEET A500.1 DOOR SCHEDULE EGRESS DOORS THAT ARE
 MISSING PUSH BAR PANIC DEVICE HARDWARE, DOOR 8 WHEN
 REVERSE, DOOR 6 WHEN REVERSED, DOOR 5,17, 23 & 26.
 1008.1.9
 ASSEMBLY OCCUPANCY WHEN LOADS OF 100 OR MORE
 OCCUPANTS.
  
 11) SHEET A 130.2 IN THE UPPER RIGHT SECTION OF THE
 PLAN AND LOWER RIGHT SECTION OF THE PLAN THERE IS A SET
 OF STAIRS WHERE THE HANDRAIL DOES NOT FOLLOW THE DECENT
 PAST THE LAST RISER BUT MAKES A TURN
 IMMEDIATELY, PLANS CALL FOR A DETAIL 5 / A400.3 THE
 DETAIL IS BLANK. 11-4.9.4(2) AT THE BOTTOM, THE
 HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE
 WIDTH OF ONE TREAD FROM THE BOTTOM RISER; THE REMAINDER
 OF THE EXTENSION SHALL BE HORIZONTAL. THE PLANS
 INDICATE THE LAST RISER IN LINE WITH THE WALL NOT
 ALLOWING THE NOT ALLOWING THE SLOPE TO CONTINUE IN A
 STRAIGHT LINE.
  
 12) LS A120.1 THE RAMP AT THE TOP OF THE SHEET FAILS TO
 HAVE 6'-0" CLEARENCE AT THE BOTTOM LANDING.
 11-4.8.4(2).
  
 13) SHEET A130.2 DETAIL INDICATES 3STAIR DETAILS 4, 5&6
 A400.3 PLEASE CORRECT, 106.1.2 ADDITIONAL INFORMATION
 REQUIRED, WRONG DETAILS.
  
 14) SHEET A 130.3 OFFICE BOTTOM OF RAMP DOES NOT HAVE A
 6'-0" CLEAR BOTTOM RAMP. SEE 11-4.8.4(2).
  
 15) SHEET A 130.3 TICKET OFFICE AT DOOR # 4 THE FIRE
 EXTINGUISHER IS HIDDEN BEHIND THE DOOR WHEN OPENED. NO
 CODE SECTION JUST A BAD LOCATION IF NOT VISIBLE.
  
 16) LS A120 PLAN FAILS TO INDICATE COMPLIANCE WITH
 PLACEMENT OF WHEELCHAIR LOCATIONS. 11-4.33.3.
  
 17) LS A120 INDICATE COMPLIANCE WITH 11-4.33.6
 PLACEMENT OF LISTENING SYSTEMS.
  
 18) LS A120 SHOW COMPLIANCE WITH 11-4.32.1-2.
  
 19) A140.5 PLEASE PROVIDE SQ FT OF ROOM AND OF THE
 RAISED PLATFORM AREA, 410.4.
  
 20) A140.1 FLOOR FINISHES PLEASE PROVIDE CARPET
 DOCUMENTATION WITH COMPLIANCE OF SECTION 804.5.1 ,
 CLASS II FOR THE ASSEMBLY OCCUPANCY.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved