| 2008-08-25 15:44:56 | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| | COMMENTS. |
| | |
| | 1. PER FBC-2004 CHAPTER 1 (W.P.B. AS AMENDED), SECTION |
| | 106.3.5.4 RESIDENTIAL (ONE AND TWO-FAMILY) (9) |
| | PLUMBING: PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC |
| | RISER DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND |
| | SIZES WITH CLEANOUT LOCATIONS THAT REFLECT THE FIRST |
| | AND SECOND FLOOR PLAN OF THE PROPOSED PLUMBING BEING |
| | INDICATED ON SHEETS A.1, A.2, P.1, AND P.2. |
| | NOTE: THE WASHING MACHINE BRANCH DRAIN AND DRAINAGE |
| | STACK SHALL BE 3 INCH AND THE WATER-SEAL TRAP AND |
| | STANDPIPE SHALL BE 2 INCH. PER FBC- PLUMBING SECTION |
| | 406.3. |
| | |
| | **RESPONSE NOTED, HOWEVER PLEASE CORRECT THE FOLLOWING |
| | ON THE SANITARY ISOMETRIC RISER DIAGRAMS PER THE |
| | FBC-2004 PLUMBING SECTIONS. |
| | |
| | A} SHEET P-1 A CLEANOUT IS REQUIRED AT THE BASE OF THE |
| | 3" SANITARY STACK TO THE SECOND FLOOR. PER SECTION |
| | 708.3.5. BASE OF STACK. |
| | |
| | B} SHEET P-1 IS INDICATING A "S" TRAP FOR ONE OF THE |
| | SINK BOWLS. "S" TRAPS ARE PROHIBITED. PER SECTION |
| | 1002.3(5) PROHIBITED TRAPS. |
| | |
| | C} SHEET P-1 PLEASE CLEARLY INDICATE THE DRAIN FOR THE |
| | DISHWASHER TO DISCHARGE INTO THE WYE-BRANCH FITTING ON |
| | THE TAILPIECE OF THE KITCHEN SINK. PER 802.1.6 DOMESTIC |
| | DISHWASHING MACHINES. |
| | |
| | D} SHEET P-2 CLEARLY INDICATE THE REQUIRED WATER-SEAL |
| | TRAPS FOR THE SHOWER AND TUB. PER SECTION 1002.1 |
| | FIXTURE TRAPS. |
| | |
| | E} SHEET P-2 ONE OF THE LAVATORIES IS BEING DRAINED BY |
| | A "S" TRAP. "S" TRAPS ARE PROHIBITED. PER SECTION |
| | 1002.3(5) PROHIBITED TRAPS. |
| | |
| | F} SHEET P-2 THE HORIZONTAL BRANCH DRAIN AND STACK FOR |
| | THE WASHING MACHINE SHALL BE 3 INCH AND THE WATER-SEAL |
| | TRAP SHALL BE 2 INCH. PER SECTION 406.3 WASTE |
| | CONNECTIONS. |
| | |
| | G} SHEET P-2 THE LAVATORIES ARE BEING IDENTIFIED AS A |
| | VAN. WHAT IS A VAN? SHOULDN'T THIS BE LAV. PLEASE |
| | CLARIFY AND CORRECT THIS. PER SECTIONS 401.1 AND 701.1 |
| | SCOPE. |
| | |
| | 2. "OK" COMMENT ADDRESSED. |
| | |
| | **THE FOLLOWING IS A NEW COMMENT** |
| | |
| | 3. SHEET P.2 SECOND FLOOR PLUMBING PLAN: CLEARLY |
| | IDENTIFY ALL PLUMBING FIXTURES AS SOME FIXTURES ARE |
| | BEING MIS-IDENTIFIED AND OTHERS ARE NOT IDENTIFIED AT |
| | ALL (SHOWER IS BEING IDENTIFIED AS A LAVATORY AND THE |
| | LAVATORIES ARE NOT BEING IDENTIFIED AT ALL). PER |
| | FBC-2004 PLUMBING SECTIONS 401.1 AND 701.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |