Plan Review Notes
Plan Review Notes For Permit 08070112
Permit Number 08070112
Review Stop P
Sequence Number 2
Notes
Date Text
2008-08-25 15:44:56PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
  
 1. PER FBC-2004 CHAPTER 1 (W.P.B. AS AMENDED), SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO-FAMILY) (9)
 PLUMBING: PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC
 RISER DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND
 SIZES WITH CLEANOUT LOCATIONS THAT REFLECT THE FIRST
 AND SECOND FLOOR PLAN OF THE PROPOSED PLUMBING BEING
 INDICATED ON SHEETS A.1, A.2, P.1, AND P.2.
 NOTE: THE WASHING MACHINE BRANCH DRAIN AND DRAINAGE
 STACK SHALL BE 3 INCH AND THE WATER-SEAL TRAP AND
 STANDPIPE SHALL BE 2 INCH. PER FBC- PLUMBING SECTION
 406.3.
  
 **RESPONSE NOTED, HOWEVER PLEASE CORRECT THE FOLLOWING
 ON THE SANITARY ISOMETRIC RISER DIAGRAMS PER THE
 FBC-2004 PLUMBING SECTIONS.
  
 A} SHEET P-1 A CLEANOUT IS REQUIRED AT THE BASE OF THE
 3" SANITARY STACK TO THE SECOND FLOOR. PER SECTION
 708.3.5. BASE OF STACK.
  
 B} SHEET P-1 IS INDICATING A "S" TRAP FOR ONE OF THE
 SINK BOWLS. "S" TRAPS ARE PROHIBITED. PER SECTION
 1002.3(5) PROHIBITED TRAPS.
  
 C} SHEET P-1 PLEASE CLEARLY INDICATE THE DRAIN FOR THE
 DISHWASHER TO DISCHARGE INTO THE WYE-BRANCH FITTING ON
 THE TAILPIECE OF THE KITCHEN SINK. PER 802.1.6 DOMESTIC
 DISHWASHING MACHINES.
  
 D} SHEET P-2 CLEARLY INDICATE THE REQUIRED WATER-SEAL
 TRAPS FOR THE SHOWER AND TUB. PER SECTION 1002.1
 FIXTURE TRAPS.
  
 E} SHEET P-2 ONE OF THE LAVATORIES IS BEING DRAINED BY
 A "S" TRAP. "S" TRAPS ARE PROHIBITED. PER SECTION
 1002.3(5) PROHIBITED TRAPS.
  
 F} SHEET P-2 THE HORIZONTAL BRANCH DRAIN AND STACK FOR
 THE WASHING MACHINE SHALL BE 3 INCH AND THE WATER-SEAL
 TRAP SHALL BE 2 INCH. PER SECTION 406.3 WASTE
 CONNECTIONS.
  
 G} SHEET P-2 THE LAVATORIES ARE BEING IDENTIFIED AS A
 VAN. WHAT IS A VAN? SHOULDN'T THIS BE LAV. PLEASE
 CLARIFY AND CORRECT THIS. PER SECTIONS 401.1 AND 701.1
 SCOPE.
  
 2. "OK" COMMENT ADDRESSED.
  
 **THE FOLLOWING IS A NEW COMMENT**
  
 3. SHEET P.2 SECOND FLOOR PLUMBING PLAN: CLEARLY
 IDENTIFY ALL PLUMBING FIXTURES AS SOME FIXTURES ARE
 BEING MIS-IDENTIFIED AND OTHERS ARE NOT IDENTIFIED AT
 ALL (SHOWER IS BEING IDENTIFIED AS A LAVATORY AND THE
 LAVATORIES ARE NOT BEING IDENTIFIED AT ALL). PER
 FBC-2004 PLUMBING SECTIONS 401.1 AND 701.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  