| 2008-07-09 14:36:34 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. PER FBC-2004 CHAPTER 1 (W.P.B. AS AMENDED), SECTION |
| | 106.3.5.4 RESIDENTIAL (ONE AND TWO-FAMILY) (9) |
| | PLUMBING: PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC |
| | RISER DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND |
| | SIZES WITH CLEANOUT LOCATIONS THAT REFLECT THE FIRST |
| | AND SECOND FLOOR PLAN OF THE PROPOSED PLUMBING BEING |
| | INDICATED ON SHEETS A.1, A.2, P.1, AND P.2. |
| | NOTE: THE WASHING MACHINE BRANCH DRAIN AND DRAINAGE |
| | STACK SHALL BE 3 INCH AND THE WATER-SEAL TRAP AND |
| | STANDPIPE SHALL BE 2 INCH. PER FBC- PLUMBING SECTION |
| | 406.3. |
| | |
| | 2. SHEET P.1 PLUMBING NOTES #13: PLEASE CLARIFY WHAT |
| | ONE ONE (1) ARMAFLEX IS. DOES THIS MEAN THAT THE |
| | INSULATION WALL THICKNESS IS ONE INCH (1")? PER FBC- |
| | BUILDING, CHAPTER 13, SECTION 612.1 ABC.5. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |