| Date |
Text |
| 2008-07-16 15:55:22 | |
| | |
| | DENIED |
| | |
| | 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $31.88 FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | 3)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, |
| | AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 4)DEMOLITION NOTE #2 ON SHEET D.2 IS NOT DESIGNATED |
| | ON THE DRAWING |
| | |
| | 5)THE FOLLOWING CORRECTIONS ARE REQUIRED TO THE |
| | ENERGY CALC'S |
| | |
| | A)SHEET A.2 SHOWS EXTERIOR WOOD FRAME WALLS WITH R19, |
| | NO SUCH WALLS ARE ALLOCATED ON ENERGY CALC'S |
| | |
| | B)ACCORDING TO SQUARE FOOTAGE ENTIRE HOUSE IS BEING |
| | USED IN WHOLE BUILDING METHOD A BUT ONLY 5 WINDOW |
| | OPENINGS ARE LISTED IN THE AS-BUILT CALC'S AND NO EAVE |
| | LENGTH OR HEIGHT WAS GIVEN |
| | |
| | 6)PLEASE CLARIFY THE FRAMED WALL SIZE, SHEET A.1 |
| | LEGEND SHOWS 8" BUT BUILDING SECTION ON SHEET A.7 AND |
| | FRAMING DETAIL #1 ON SHEET S.3 SEEMS TO INDICATE A 2X6 |
| | WALL. ALSO IS THE EXISTING WALL THAT SUPPORTS THE |
| | SECOND FLOOR TRUSSES A NEW 2X6 OR EXISTING 2X4 EXTERIOR |
| | WALL |
| | |
| | 7)THE FOLLOWING CORRECTIONS ARE REQUIRED TO THE |
| | PRODUCT APPROVAL SUBMITTALS |
| | |
| | A)THE ROOF TILE PRODUCT APPROVAL WAS SUBMITTED WITH |
| | BOTH TYPES OF ROOF TILE, PLEASE SUBMIT ONLY THE TYPE |
| | THAT WILL BE USED FOR THE JOB |
| | |
| | B)THE PRODUCT APPROVAL FOR THE EXTERIOR DOORS |
| | CONTAINS THE DRAWINGS FOR 4 DIFFERENT DOORS, GLAZED AND |
| | OPAQUE(STEEL NON GLAZED). PROVIDE ONLY THE APPROVAL FOR |
| | THE DOOR THAT WILL BE INSTALLED (NOTE ALL OF THESE |
| | DOORS ARE NON IMPACT RATED AND WOULD REQUIRE SOME TYPE |
| | OF IMPACT RESISTANT COVERING. |
| | |
| | C)THE MIAMI DADE NOA'S FOR THE FIXED AND SINGLE HUNG |
| | WINDOWS ARE NOT THE COMPLIANCE REPORTS THAT WERE USED |
| | BY THE STATE OF FLORIDA. PLEASE USE THE LINKS ON PAGE 2 |
| | OF THE STATE APPROVAL TO DOWNLOAD THE CORRECT DRAWINGS |
| | |
| | D)NO PRODUCT APPROVALS WERE SUBMITTED FOR MULLIONS |
| | WHERE ARCHED WINDOWS ARE SET ABOVE THE SINGLE HUNG |
| | UNITS |
| | |
| | E)PLEASE CLARIFY USE OF ODL DOOR GLAZING COMPONENT, |
| | THIS UNIT IS NOT A RETROFIT FOR NON GLAZED OR NON |
| | IMPACT RATED GLAZED DOORS, IT CAN ONLY BE USED AS |
| | STATED ON THE DRAWING THAT IS PART OF THE PRODUCT NOA |
| | (THESE DRAWINGS WERE NOT SUBMITTED WITH THE MIAMI-DADE |
| | NOA) |
| | |
| | F)NO APPROVALS WERE SUBMITTED FOR STUD TO PLATED |
| | FRAMING TIES (SP6 OR SP8 DEPENDING ON WALL SIZE) |
| | |
| | G)PRODUCT APPROVALS WERE SUBMITTED FOR CONCRETE |
| | POURED IN STRAP HETA20 BUT THIS STRAP IS NOT SPECIFIED |
| | ON THE DRAWINGS, WOULD THIS BE USED AT MASONRY WALL TO |
| | CONNECT FLOOR TRUSSES? |
| | |
| | 8)REMOVE ALL OLD PAGES, INCORRECT PRODUCT APPROVALS, |
| | ETC.AND RESUBMIT 2 COMPLETE SETS WITH REVISIONS AND |
| | INCLUDE 1 COPY OF THE OLD PLAN PAGES ONLY FOR |
| | REFERENCE. |
| | |
| | 9)SUBMIT A COPY OF THE RECORDED NOTICE OF |
| | COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |