| 2008-07-10 10:36:43 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ALL COMMENTS RELATE TO SHEET-3 UNLESS OTHERWISE NOTED. |
| | ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), CIRCUIT #14 DOES NOT COMPLY. |
| | |
| | 2} CIRCUIT #15 APPEARS AT THE KITCHEN COUNTER AS WELL |
| | AS THE WASHER IN VIOLATION OF 210.52(B)(1) "RECEPTACLE |
| | OUTLETS SERVED IN THE KITCHEN, PANTRY, BREAKFAST ROOM, |
| | DINING ROOM, OR SIMILAR AREA OF A DWELLING UNIT, THE |
| | TWO OR MORE 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS |
| | REQUIRED BY 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR |
| | RECEPTACLE OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP |
| | OUTLETS COVERED BY 210.52(C), AND RECEPTACLE OUTLETS |
| | FOR REFRIGERATION EQUIPMENT.". |
| | |
| | 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.THERE IS NO |
| | RECEPTACLES SHOWN INDICATING COUTERTOP REQUIREMENTS. |
| | |
| | 4} THE DESIGN PROFESSIONAL OR OWNER MUST ELECT THE |
| | LEVEL OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND |
| | 305 OF THE EXISTING BUILDING CODE. PLEASE DECLARE SAME |
| | ON THE PLAN. |
| | |
| | 5} NOTE #20 INDICATES CUTTING THE STRUCTURE. PROVIDE |
| | ENGINEERING INDICATING THE STRUCTURAL INTEGRITY OF THE |
| | CEILING OR FLOOR ABOVE WILL NOT BE COMPROMISED, SIGNED |
| | AND SEALED. |
| | |
| | 6} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 |
| | NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID |
| | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE |
| | LOCATIONS OF THE SOUNDING DEVICES. |
| | |
| | 7} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE |
| | ARTICLE, PUT A ON THE PLAN FOR CLARITY IN THE FIELD. |
| | |
| | 8} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |