 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET-3 UNLESS OTHERWISE NOTED.
 ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), CIRCUIT #14 DOES NOT COMPLY.
  
 2} CIRCUIT #15 APPEARS AT THE KITCHEN COUNTER AS WELL
 AS THE WASHER IN VIOLATION OF 210.52(B)(1) "RECEPTACLE
 OUTLETS SERVED IN THE KITCHEN, PANTRY, BREAKFAST ROOM,
 DINING ROOM, OR SIMILAR AREA OF A DWELLING UNIT, THE
 TWO OR MORE 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS
 REQUIRED BY 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR
 RECEPTACLE OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP
 OUTLETS COVERED BY 210.52(C), AND RECEPTACLE OUTLETS
 FOR REFRIGERATION EQUIPMENT.".
  
 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.THERE IS NO
 RECEPTACLES SHOWN INDICATING COUTERTOP REQUIREMENTS.
  
 4} THE DESIGN PROFESSIONAL OR OWNER MUST ELECT THE
 LEVEL OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND
 305 OF THE EXISTING BUILDING CODE. PLEASE DECLARE SAME
 ON THE PLAN.
  
 5} NOTE #20 INDICATES CUTTING THE STRUCTURE. PROVIDE
 ENGINEERING INDICATING THE STRUCTURAL INTEGRITY OF THE
 CEILING OR FLOOR ABOVE WILL NOT BE COMPROMISED, SIGNED
 AND SEALED.
  
 6} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 7} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE, PUT A ON THE PLAN FOR CLARITY IN THE FIELD.
  
 8} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  