Plan Review Notes
Plan Review Notes For Permit 08070087
Permit Number 08070087
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-25 07:28:15BUILDING PLAN REVIEW
 PERMIT: 08070087
 ADD: 400 N. FLAGLER DR. #1504
 CONT: A MCGILL REMODELING LLC.
 TEL: (561)632-9354
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 7-24-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
 5)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDING AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, ARCHITECTURAL DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES PER 108.3 FBC*
 6)PROVIDE DETAIL ELEVATION DRAWINGS AND FRAMING
 DETAILS FOR THE NEW WALLS AND SOFFITS INDICATING ALL
 MATERIALS, FASTENER AND FLOOR ATTACHMENTS OF THE STUD
 SPACING.
 7)THE PLANS NEED TO INDICATE THE TYPE OF BUILDING PER
 CHAPTER 6 AND THE USE AND OCCUPANCY PER CHAPTER 3.
 8)FBC 1207.3 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS IIC RATING OR NOT LESS THAN 50
 (45 IF FIELD TESTED) WHEN IN ACCORDANCE WITH ASTM E
 492. PROVIDE INFORMATION ON THE SOUND PROOFING OF THE
 FLOOR.
 9)FBC 106.3.5.1.1(5)* FS553.79 (2) NOW THE FIRE
 SPRINKLER SYSTEM WILL BE ALTERED, FIRE SPRINKLER PLANS
 ARE REQUIRED TO SHOW THE NEW LAYOUT OF THE SPRINKLER
 HEADS. THIS INFORMATION CAN BE SHOWN ON THE CEILING
 PLANS.
 10)TABLE 803.5 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION BASED ON INTERIOR
 FINISH REQUIREMENTS BASED ON OCCUPANCY
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER