| 2008-07-25 07:28:15 | BUILDING PLAN REVIEW |
| | PERMIT: 08070087 |
| | ADD: 400 N. FLAGLER DR. #1504 |
| | CONT: A MCGILL REMODELING LLC. |
| | TEL: (561)632-9354 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 7-24-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. |
| | 5)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDING AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, ARCHITECTURAL DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION |
| | REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST |
| | ANALYSIS SERVICES PER 108.3 FBC* |
| | 6)PROVIDE DETAIL ELEVATION DRAWINGS AND FRAMING |
| | DETAILS FOR THE NEW WALLS AND SOFFITS INDICATING ALL |
| | MATERIALS, FASTENER AND FLOOR ATTACHMENTS OF THE STUD |
| | SPACING. |
| | 7)THE PLANS NEED TO INDICATE THE TYPE OF BUILDING PER |
| | CHAPTER 6 AND THE USE AND OCCUPANCY PER CHAPTER 3. |
| | 8)FBC 1207.3 FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS IIC RATING OR NOT LESS THAN 50 |
| | (45 IF FIELD TESTED) WHEN IN ACCORDANCE WITH ASTM E |
| | 492. PROVIDE INFORMATION ON THE SOUND PROOFING OF THE |
| | FLOOR. |
| | 9)FBC 106.3.5.1.1(5)* FS553.79 (2) NOW THE FIRE |
| | SPRINKLER SYSTEM WILL BE ALTERED, FIRE SPRINKLER PLANS |
| | ARE REQUIRED TO SHOW THE NEW LAYOUT OF THE SPRINKLER |
| | HEADS. THIS INFORMATION CAN BE SHOWN ON THE CEILING |
| | PLANS. |
| | 10)TABLE 803.5 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION BASED ON INTERIOR |
| | FINISH REQUIREMENTS BASED ON OCCUPANCY |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |