| 2008-07-08 16:58:10 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SP-1 IS INCORRECTLY INDICATES (4) NEW STUB OUT FOR |
| | POOL CLEANER. THERE SHOULD ONLY BE (1) INDICATED FOR |
| | THIS. PER FBC-RESIDENTIAL CHAPTER 41, SECTION R4101.6 |
| | ENGINEERING DESIGN. |
| | |
| | 2. SP-1 IS INCORRECTLY INDICATING AN ARROW TO THE 9" |
| | MAIN DRAINS AND VENT PIPING WITH THE FOLLOWING "ADD (2) |
| | JANDYDECK JETS W/1-1/2" SUPPLY LINES AND VALVES". THIS |
| | IS CONFUSING, PLEASE CLARIFY THIS AREA ON THE RESUB. |
| | PER FBC-RESIDENTIAL CHAPTER 41, SECTION R4101.6 |
| | ENGINEERING DESIGN. |
| | |
| | 3. SP-2 LEGEND PER THE EQUIPMENT LAYOUT HAS |
| | INCORRECTLY IDENTIFIED #1 AS A "3" POOL MAIN DRAIN |
| | LINE". #1 SHOULD BE THE 1-1/2" RAIN ARCH SUPPLY. ALSO |
| | #2 IS INCORRECTLY IDENTIFIED AS "2" RAIN ARCH SUPPLY |
| | LINES". #2 SHOULD BE THE 3" POOL MAIN DRAIN LINE. |
| | PLEASE CORRELATE AND CORRECT THESE ITEMS. PER |
| | FBC-RESIDENTIAL CHAPTER 41, SECTION R4101.6 ENGINEERING |
| | DESIGN. |
| | |
| | 4. SP-2 POOL/SPA SPECIFICTIONS INDICATES A SALT |
| | GENERATOR AND A JANDY RS-8 SYSTEM THAT ARE NOT |
| | INDICATED ON THE EQUIPMENT LAYOUT. PLEASE CLEARLY |
| | INDICATE THE LOCATION OF THESE ITEMS ON THE RESUBMITTED |
| | EQUIPMENT LAYOUT. PER FBC-RESIDENTIAL CHAPTER 41, |
| | SECTION R4101.6 ENGINEERING DESIGN. |
| | |
| | 5. SP-2 LEGEND #9. CAN'T FIND THIS ITEM ON SHEET SP-1. |
| | PLEASE CLARIFY WHERE THIS ITEM IS ON THE RESUBMITTAL. |
| | PER FBC-RESIDENTIAL CHAPTER 41, SECTION 4101.6 |
| | ENGINEERING DESIGN. |
| | |
| | 6. FBC-2004 SEC. 424.2.14.1, OR |
| | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (PLEASE SUBMIT TWO COPIES OF |
| | MANUFACTURE SHEETS OR IF THE POOL HEATER IS EXISTING |
| | CLEARLY INDICATE THIS ON THE PLANS) |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |