Plan Review Notes
Plan Review Notes For Permit 08060908
Permit Number 08060908
Review Stop B
Sequence Number 3
Notes
Date Text
2008-07-21 14:51:08RESIDENTIAL (R3)SHUTTERS, BUILDING REVIEWTHIRD
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-INFORMATION SUBMITTED ON OCEAN SHUTTERS LETTER HEAD
 CALLS FOR OPENING #6 TO HAVE HEADER.INSTALLATION
 SCHEDULE DOESN'T REFLECT THIS. REVISE CONNECTION TYPE
 AND ANCHOR SPACING AS REQUIRED.(REPEAT COMMENT).
  
 2- DESIGN PRESSURES SHOWN ON INSTALLATION SCHEDULE ARE
 DIFFERENT FROM THOSE DESIGN PRESSURES SHOWNON THE
 WIND LOADS CALCULATIONS AND DESIGN PRESSURES
 HIGHLIGHTED ONSHUTTERSPAGE 5 OF 5. COORDINATE
 INFORMATION AS REQUIRED WITH EACH OPENING AND REVISE AS
 REQUIRED TO MATCH.REVISE ANCHOR SPACING AS REQUIRED.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 * NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK
 UP.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712