Plan Review Notes
Plan Review Notes For Permit 08060908
Permit Number 08060908
Review Stop B
Sequence Number 2
Notes
Date Text
2008-07-15 16:35:25RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEWSECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- INSTALLATION SCHEDULESUBMITTED DOESN'T REFLECT
 INFORMATIONMARKED ON THE PRODUCT APPROVAL DRAWINGS.
 EG:"U" HEADER IS MARKED WITH #16. THERE IS NOT #16 ON
 INSTALLATION SCHEDULE.ALSO, THERE ARE NOT STUD ANGLES
 SHOWN ON THE MOUNTING CONDITIONS AND IN THE
 INSTALLATION SCHEDULE. AND,DRAWINGS ARE MARKED WITH
 THE INSTALLATION SCHEDULE FOR CONCRETE, WHILE
 INSTALLATION SCHEDULE CALLS FOR CONCRETE BLOCK. REVISE
 AS REQUIRED.
  
  
 2- INFORMATION SUBMITTED ON OCEAN SHUTTERSLETTER HEAD
 CALLS FOR OPENINGS # 5 AND #6 TO HAVE TRACK AND HEADER
 RESPECTIVELY.INSTALLATION SCHEDULE DOESN'T REFLECT
 THIS.REVISE CONNECTION TYPEAND ANCHOR SPACING AS
 REQUIRED.
  
 3-ANCHOR SCHEDULE MARKED ON SHEET 4 OF 5 OF STORM
 SHUTTERS IS FOR CONCRETE SUBSTRATE INSTALLATION ONLY.
 PROVIDE DOCUMENTATION THAT SHOWS THAT EXISTING
 SUBSTRATE IS 3,000/3,140 PSI AT TOP AND BOTTOM OF STORM
 SHUTTERS INSTALLATIONS.OTHERWISE, TABLE FOR HOLLOW
 CONCRETE BLOCK SHALL BE USED OR SITE SPECIFIC
 ENGINEERING WILL BE REQUIRED. (TYPICALLY, WINDOW
 SILLS ARE NOT POURED OR PRECAST SILLS, BUT FILLED
 CONCRETE BLOCK. THAT'S WHYSITE SPECIFIC PROOF IS
 REQUIRED TO USE THE CONCRETE TABLE).SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 THE PROPOSED INSTALLATION AND DESIGN PRESSURES OF SEC.
 R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW.UPDATE VALUATIONAS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004. (REPEAT COMMENT).
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712