| 2008-07-24 12:51:18 | *****DENIED***** |
| | |
| | |
| | 1. THE SUBMITTED PLANS SHALL BE SIGNED AND SEALED. |
| | |
| | 2. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED IN ADDITION TO THE 2004 FLORIDA FIRE |
| | PREVENTION CODE |
| | |
| | 3. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 4. THE REMOVAL AND (OR) THE REPLACEMENT OF BUILDING |
| | MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH |
| | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR |
| | VICINITY THEREOF (INCLUDING FIRE LANES) . |
| | |
| | 5. ON SHEET A0-0, THE PROJECT TEAM INFORMATION IS |
| | INCORRECT. PLEASE BE ADVISED THAT AHJ FOR THE JOB SITE |
| | IS THE CITY OF WEST PALM BEACH. AMEND BUILDING |
| | DEPARTMENT AND FIRE DEPARTMENT INFORMATION. |
| | |
| | 6. SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR |
| | ELEVATION WHICH FRONTS OKEECHOBEE BOULEVARD. AS PER |
| | WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN |
| | 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE. |
| | |
| | 7. SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS IN THE TERMS OF CLASS A, CLASS B, OR CLASS |
| | C. |
| | |
| | 8. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCES |
| | TO THE EXITS, EXIT LIGHTS, EMERGENCY LIGHTS, FIRE |
| | EXTINGUISHERS, AND ANY OTHER PERTINENT LIFE SAFETY |
| | FEATURES. |
| | |
| | 9. PROVIDE A LAYOUT FOR THE SPRINKLER HEADS AND A |
| | LAYOUT FOR THE FIRE ALARM DEVICES FOR THIS FLOOR PLAN. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| | EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WIOLLIAMS |
| | FIRE PLAN REVIEW |