| 2008-07-18 11:41:06 | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE PLANS BEING SUBMITTED FOR EXPIRED |
| | PERMIT ARE ALL PHOTO-COPIES OF SIGNED AND SEALED PLANS |
| | WHICH IS NOT PERMITTED UNDER FS 481.221, 471.025, FAC |
| | 61G15-23.002 ETC |
| | |
| | 2) NOTE: PLEASE BE SURE ALL ELECTRICAL IS THAT OF THE |
| | PERMITTED SET OF PLANS WITH ANY CHANGES. PLANS |
| | SUBMITTED ARE NOT THE SAME. |
| | THE PLANS SUBMITTED ARE NOT THE PLANS STAMPED WHEN |
| | ISSUED FOR PERMIT. IN FACT THERE WERE SEVERAL CODE |
| | REVIEWS BEFORE THIS PERMIT WAS ISSUED. THE PLANS |
| | SUBMITTED HAD AT A MINIMUM OF THREE ELECTRICAL |
| | REVISIONS BEFORE ISSUANCE. |
| | PLEASE SEE 2005 NFPA-70, 2003 NFPA-101, 2004 FBC W/2006 |
| | REVISION ETC |
| | FBC 106.1 FOR MINIMUM INFORMATION REQUIRED. |
| | |
| | 3) NOTE: PLANS NEED TO COMPLY WITH THE FLORIDA ENERGY |
| | CODE. |
| | FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND .1.3, |
| | 13-415.2, 13-415.2.ABC.1.1,.1.2 |
| | PLEASE SUBMIT THE COMPLETED FLA COM CALCULATIONS. THE |
| | INPUT DATA REPORT REQUIRED IS MISSING FROM PLANS AND |
| | PACKAGE. THIS INFORMATION NEEDS TO BE SHOWN. |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS AND TITLE BLOCKS ARE |
| | MISSING REQUIRED INFORMATION PER FAC 61G15-23.002 AND |
| | FS 471.023 FOR ENGINEERING FIRM. |
| | PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS PER FAC |
| | 61G1-16.004, FS 481.219 FOR ARCHITECTURAL FIRM. |
| | |
| | |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |