Plan Review Notes
Plan Review Notes For Permit 08060891
Permit Number 08060891
Review Stop Z
Sequence Number 1
Notes
Date Text
2008-07-14 08:19:06***FAILED***
  
 1. THE PROPOSED 8 FOOT SCREEN WALL IS OF INSUFFICIENT
 HEIGHT TO SCREEN THE GENERATOR. INCREASE THE HEIGHT OF
 THE PROPOSED SCREEN WALL TO 13 FEET.
  
 2. SHRUBS AND HEDGES PLANTED AT TWO FOOT INTERVALS MUST
 BE PLANTED AROUND THE EXTERIOR OF THE PROPOSED
 ENCLOSURE. ENSURE THAT THE PLACEMENT OF LANDSCAPING IS
 COORDINANTED WITH THE PLACEMENT OF THE PROPOSED
 GUARDRAILS.
  
 3. PLEASE SHOW THE PROPOSED GENERATOR IN THE CONTEXT OF
 ITS SURROUNDINGS. PLEASE SHOW THE EXISTING PARKING
 SPACES WHICH ARE TO REMAIN INCLUDING THOSE ON THE WEST
 SIDE OF THE DRIVE AISLE. MAKE SURE DIMENSIONS ARE
 PROVIDED SHOWING THE WIDTH OF THE DRIVE AISLE AS WELL
 AS THE PARKING SPACES.
  