| Plan Review Notes For Permit 08060891 |
| Permit Number |
08060891 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-30 14:26:58 | ***DENIED*** | | | | | | 1) ADDRESS ON PLANS DO NOT CORRELATE WITH PERMIT | | | APPLICATION. | | | | | | 2) CLEARLY INDICATE SOUCE OF FUEL AS PLANS, MORE | | | SPECIFICALLY SHEET E-1 SEEMS TO SUGGEST (2) SEPARATE | | | GENERATORS AND PERMIT APPLICATION MENTIONS (1). | | | | | | 3) IN ADDITION TO ALL OTHER APPLICABLE CODES, LIFE | | | SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 4) CLEARLY INDICATE THE LOCATION OF EXHAUST TERMINUS | | | RELATIVE TO BUILDING OPENINGS AND MEANS OF EGRESS. | | | | | | 5) INDICATE WHAT SPECIFIC BUILDING AND LIFE SAFETY | | | EQUIPMENT WOULD BE POWERED BY GENERATOR(S) SHOULD IT | | | BECOME NECESSARY AS A RESULT OF POWER LOSS. | | | | | | 6) IN ADDITION TO NFPA 704 PLACARDING, NO SMOKING SIGNS | | | ARE REQUIRED IN AREA OF FUEL SOURCE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|