2008-07-30 14:26:58***DENIED***
  
 1) ADDRESS ON PLANS DO NOT CORRELATE WITH PERMIT
 APPLICATION.
  
 2) CLEARLY INDICATE SOUCE OF FUEL AS PLANS, MORE
 SPECIFICALLY SHEET E-1 SEEMS TO SUGGEST (2) SEPARATE
 GENERATORS AND PERMIT APPLICATION MENTIONS (1).
  
 3) IN ADDITION TO ALL OTHER APPLICABLE CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 4) CLEARLY INDICATE THE LOCATION OF EXHAUST TERMINUS
 RELATIVE TO BUILDING OPENINGS AND MEANS OF EGRESS.
  
 5) INDICATE WHAT SPECIFIC BUILDING AND LIFE SAFETY
 EQUIPMENT WOULD BE POWERED BY GENERATOR(S) SHOULD IT
 BECOME NECESSARY AS A RESULT OF POWER LOSS.
  
 6) IN ADDITION TO NFPA 704 PLACARDING, NO SMOKING SIGNS
 ARE REQUIRED IN AREA OF FUEL SOURCE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756