 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, NFPA 110-2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} 700.12 (B)(2) INTERNAL COMBUSTION AS PRIME MOVERS
 WHERE INTERNAL COMBUSTION ENGINES ARE USED AS THE PRIME
 MOVER, AN ON-SITE FUEL SUPPLY SHALL BE PROVIDED WITH AN
 ON-PREMISE FUEL SUPPLY SUFFICIENT FOR NOT LESS THAN 2
 HOURS' FULL-DEMAND OPERATION OF THE SYSTEM. WHERE POWER
 IS NEEDED FOR THE OPERATION OF THE FUEL TRANSFER PUMPS
 TO DELIVER FUEL TO A GENERATOR SET DAY TANK, THIS PUMP
 SHALL BE CONNECTED TO THE EMERGENCY POWER SYSTEM.
 700.12 (B)(3) DUAL SUPPLIES PRIME MOVERS SHALL NOT BE
 SOLELY DEPENDENT ON A PUBLIC UTILITY GAS SYSTEM FOR
 THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY FOR THEIR
 COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR
 AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO
 ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED. THE PROPOSED
 NATURAL GAS GENERATOR DOES NOT COMPLY WITH THESE
 ARTICLES.
  
 2} PANEL E-4 AND PANEL E-1FED FROM MDP1, SHEET E-1,
 WERE ORIGINALLY FED FROM THE REQUIRED EMERGENCY SYSTEM
 AND NOW ARE FED FROM THE OPTIONAL SYSTEMS. PROVIDE
 PANEL SCHEDULES FOR THESE PANELS INDICATING THERE ARE
 NO LIFE SAFETY CIRCUITS BEING FED FROM THE OPTIONAL
 GENERATOR.
  
 3} SHEET E-1 PANEL "EDP". THE #2/0 CONDUCTORS FEEDING
 "PLL" HAVE AN OCP OF 200 AMPS WHICH IS IN VIOLATION OF
 310.16 AND NONCOMPLIANT WITH ARTICLE 240.4(B)(2), WHICH
 INDICATES A 175 AMP OCPFOR THOSE CONDUCTORS.
  
 4} PROVIDE PANEL SCHEDULES FOR NEW PANELS "CL", "EM"
 AND "PLL". PER 408.4 AND 106.3.5.1.2 FBC AS AMENDED.
  
 5} THE ADDRESS ON THE PLAN AND THE APPLICATION DO NOT
 CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]