2008-07-03 10:43:37PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. THE ENGINEERS SIGNATURE APPEARS TO BE A PHOTOCOPY.
 PER FLORIDA STATUTES 471.025 SIGNATURE SHALL BE
 ORIGINAL.
  
 2. SHEET 1 PLUMBING RISER: CLEARLY INDICATE THE
 CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND
 BUILDING SEWER AS BEING A TWO-WAY CLEANOUT. PER FBC-
 PLUMBING SECTION 708.3.5.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  