| 2008-07-03 13:30:15 | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PROVIDE A PANEL SCHEDULE SO THAT BRANCH/FEEDER |
| | CIRCUIT CONDUCTOR AND OVER CURRENT PROTECTION |
| | COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, 106.3.5.4 FBC |
| | AS AMENDED. |
| | |
| | 2} 9B-3.0472 CARBON MONOXIDE PROTECTION. |
| | (1) DEFINITIONS: FOR PURPOSES OF THIS RULE, THE |
| | FOLLOWING DEFINITIONS SHALL APPLY: |
| | (A) CARBON MONOXIDE ALARM. A DEVICE FOR THE PURPOSE OF |
| | DETECTING CARBON MONOXIDE, THAT PRODUCES A DISTINCT |
| | AUDIBLE ALARM, AND IS LISTED OR LABELED WITH THE |
| | APPROPRIATE STANDARD, EITHER ANSI/UL 2034 - 96, |
| | STANDARD FOR SINGLE AND MULTIPLE STATION CO ALARMS, |
| | INCORPORATED HEREIN BY REFERENCE, OR UL 2075 - 04, GAS |
| | AND VAPOR DETECTOR SENSOR, INCORPORATED HEREIN BY |
| | REFERENCE, IN ACCORDANCE WITH ITS APPLICATION. BOTH |
| | DOCUMENTS MAY BE OBTAINED BY WRITING TO: CODES AND |
| | STANDARDS SECTION, DEPARTMENT OF COMMUNITY AFFAIRS, |
| | 2555 SHUMARD OAK BOULEVARD, TALLAHASSEE, FLORIDA |
| | 32399-2100. |
| | (B) FOSSIL FUEL. COAL, KEROSENE, OIL, FUEL GASES, OR |
| | OTHER PETROLEUM OR HYDROCARBON PRODUCT THAT EMITS |
| | CARBON MONOXIDE AS A BY-PRODUCT OF COMBUSTION. |
| | (2) EVERY BUILDING FOR WHICH A PERMIT FOR NEW |
| | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A |
| | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, |
| | OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON |
| | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM |
| | USED FOR SLEEPING PURPOSES. |
| | (3) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR |
| | PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING |
| | IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS |
| | SHALL HAVE BATTERY BACK UP. |
| | (4) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED |
| | 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. |
| | HISTORY?NEW 11-18-07.** THE CONTRACTOR WILL DECIDE IF |
| | ANY OF THE SECTIONS OF THIS HOUSE BILL APPLIES. |
| | |
| | 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED, LABEL THE ROOMS AND INCLUDE THE ADDRESS OF |
| | THE PROJECT ON THE PLANS |
| | |
| | 4} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3) |
| | IF APPLICABLE. |
| | |
| | 5} 210.70(A)(2).(C) WHERE ONE OR MORE LIGHTING |
| | OUTLET(S) ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE |
| | SHALL BE A WALL SWITCH AT EACH FLOOR LEVEL, AND LANDING |
| | LEVEL THAT INCLUDES AN ENTRYWAY, TO CONTROL THE |
| | LIGHTING OUTLET(S) WHERE THE STAIRWAY BETWEEN FLOOR |
| | LEVELS HAS SIX RISERS OR MORE.*** SECOND LEVEL APPEARS |
| | TO BE MISSING. |
| | |
| | 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER |
| | 106.1.3.FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |