Plan Review Notes
Plan Review Notes For Permit 08060835
Permit Number 08060835
Review Stop P
Sequence Number 1
Notes
Date Text
2008-07-07 09:46:11PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE SUBMITTED PRODUCT APPROVALS FOR THE SUNSTAR
 SOLAR COLLECTOR, HELIOCOL ARE EXPIRED AS OF 9/12/97. AN
 ONLINE SEARCH OF SAID PRODUCT APPROVALS BY THIS PLANS
 EXAMINER CAME UP WITH "THERE ARE NO RECORDS THAT MATCH
 THE SEARCH CRITERIA". PLEASE SUBMIT TWO COPIES OF
 UPDATED PRODUCT APPROVALS.
  
 2. SHEET S-1, THE ENGINEERED ANCHORING OF THE "SUN
 STAR" COLLECTORS IS EXPIRED. SHEET S-1 INDICATES PER
 2001 FLORIDA BUILDING CODE. THE CORRECT CODE CYCLE IS
 2004 FLORIDA BUILDING CODES WITH 2007 REVISIONS. PLEASE
 PROVIDE TWO COPIES OF UPDATED ENGINEERED ANCHORING
 DETAILS WITH THE CORRECT CODE CYCLES AND COMPLIANT TO
 MEET THE 140 MPH WIND LOAD PER FBC-2004 BUILDING
 CHAPTER 16, SECTION 1603.1.4 WIND DESIGN DATA AND
 SECTION 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT
 AND SLIDING..
  
 3. SHEET S-1 ALSO INDICATES A PHOTO COPY OF THE
 ENGINEER'S SEAL, DATE AND SIGNATURE. PER
 FAC-61G15-23.002 SEAL SIGNATURE AND DATE SHALL BE
 AFFIXED: EACH SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER PROVISIONS OF CHAPTER 471 SHALL BE SEALED,
 SIGNED AND DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET.
 IF
 PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGNEERING
 BUSINESS ON EACH SHEET.
  
 4. THE SUBMITTED "GOOGLE 2008 TELE ATLAS" OF 3800
 WASHINGTON ROAD, PORTOFINO SOUTH WITH THE SOLAR
 COLLECTORS INDICATED ON THE ROOF NEEDS MORE
 INFORMATION. PLEASE PROVIDE A SCHEDULE WITH THE PIPE
 SIZES, THE EXACT NUMBER OF SOLAR COLLECTORS, OR CLEARLY
 IDENTIFY THE COLLECTORS AND PIPE SIZES ON THE DRAWING.
 PER FBC-2004 MECHANICAL SECTION 1401.1 SCOPE.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  