Plan Review Notes
Plan Review Notes For Permit 08060791
Permit Number 08060791
Review Stop B
Sequence Number 2
Notes
Date Text
2008-07-14 14:15:08RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- ACCORDION SHUTTERS FLORIDA PRODUCT APPROVAL FL5354
 SUBMITTED LISTS DRAWING #05-285.DRAWING SUBMITTED IS
 06-174. NEED TO PROVIDE DRAWING NUMBER THAT MATCHES ONE
 APPROVED IN THE FLORIDA PRODUCT APPROVAL.
  
 2- ACCORDION SHUTTERSDRAWING #05-285 IS ONLY APPROVED
 FOR CONCRETE AND CONCRETE BLOCK INSTALLATIONS.NOT FOR
 WOOD INSTALLATION.NEED TO PROVIDE PRODUCT APPROVAL
 THAT INCLUDES WOOD INSTALLATION.
  
 3- DRAWINGS SUBMITTED WITH STORM SHUTTERS NOA
 05-0713.03 ARE MISMATCHED.THERE ARE DRAWINGS #05-353
 AND #05-350. DRAWING THAT WAS APPROVED WITH THIS NOA
 IS DRAWING #05-353. PROVIDE COMPLETE AND CORRECT
 INFORMATION.
  
 4- REVISE INSTALLATION SCHEDULE:
 A) SHUTTER SPAN COLUMN IS FOR THE ACTUAL SPAN USED
 FOR SPECIFIC OPENING. REVISE AS REQUIRED. PROVIDE
 ACTUAL SPAN LENGTH FOR EACH OPENING.
  
 B)CLARIFY SPECIFIC MOUNTING CONDITION AND
 CONNECTION TYPE FOR EACH OPENING. "F" TRACK
 MOUNTING HAS NOT CONNECTION TYPE "C3". REVISEAS
 REQUIRED.
  
 C) REVISE SHUTTER GLASS SEPARATION. SEE PRODUCT
 APPROVAL FOR MINIMUM REQUIREMENTS.
  
 D) REVISE ANCHOR SPACING AS REQUIRED TO MATCH
 INFORMATION ON PRODUCT APPROVALS.
  
 E) REVISE ANCHOR TYPE FOR EACH INSTALLATION. EG:
 WOOD FRAME OR CONCRETE BLOCK. SEE PRODUCT APPROVAL.
  
 F) REVISE ANCHOR LENGTH TO MEET MINIMUMEMBEDMENT
 REQUIREMENTS SHOWN ON THE PRODUCT APPROVAL.
  
 G) REVISE MINIMUM EDGE DISTANCE. TAKE INTO
 CONSIDERATION IF SUBSTRATE IS WOOD OR CONCRETE BLOCK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  