| 2008-07-14 14:15:08 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- ACCORDION SHUTTERS FLORIDA PRODUCT APPROVAL FL5354 |
| | SUBMITTED LISTS DRAWING #05-285.DRAWING SUBMITTED IS |
| | 06-174. NEED TO PROVIDE DRAWING NUMBER THAT MATCHES ONE |
| | APPROVED IN THE FLORIDA PRODUCT APPROVAL. |
| | |
| | 2- ACCORDION SHUTTERSDRAWING #05-285 IS ONLY APPROVED |
| | FOR CONCRETE AND CONCRETE BLOCK INSTALLATIONS.NOT FOR |
| | WOOD INSTALLATION.NEED TO PROVIDE PRODUCT APPROVAL |
| | THAT INCLUDES WOOD INSTALLATION. |
| | |
| | 3- DRAWINGS SUBMITTED WITH STORM SHUTTERS NOA |
| | 05-0713.03 ARE MISMATCHED.THERE ARE DRAWINGS #05-353 |
| | AND #05-350. DRAWING THAT WAS APPROVED WITH THIS NOA |
| | IS DRAWING #05-353. PROVIDE COMPLETE AND CORRECT |
| | INFORMATION. |
| | |
| | 4- REVISE INSTALLATION SCHEDULE: |
| | A) SHUTTER SPAN COLUMN IS FOR THE ACTUAL SPAN USED |
| | FOR SPECIFIC OPENING. REVISE AS REQUIRED. PROVIDE |
| | ACTUAL SPAN LENGTH FOR EACH OPENING. |
| | |
| | B)CLARIFY SPECIFIC MOUNTING CONDITION AND |
| | CONNECTION TYPE FOR EACH OPENING. "F" TRACK |
| | MOUNTING HAS NOT CONNECTION TYPE "C3". REVISEAS |
| | REQUIRED. |
| | |
| | C) REVISE SHUTTER GLASS SEPARATION. SEE PRODUCT |
| | APPROVAL FOR MINIMUM REQUIREMENTS. |
| | |
| | D) REVISE ANCHOR SPACING AS REQUIRED TO MATCH |
| | INFORMATION ON PRODUCT APPROVALS. |
| | |
| | E) REVISE ANCHOR TYPE FOR EACH INSTALLATION. EG: |
| | WOOD FRAME OR CONCRETE BLOCK. SEE PRODUCT APPROVAL. |
| | |
| | F) REVISE ANCHOR LENGTH TO MEET MINIMUMEMBEDMENT |
| | REQUIREMENTS SHOWN ON THE PRODUCT APPROVAL. |
| | |
| | G) REVISE MINIMUM EDGE DISTANCE. TAKE INTO |
| | CONSIDERATION IF SUBSTRATE IS WOOD OR CONCRETE BLOCK. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |