Plan Review Notes
Plan Review Notes For Permit 08060789
Permit Number 08060789
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-16 11:51:56BUILDING PLAN REVIEW
 PERMIT: 08060789
 ADD: 400 N. FLAGLER DR. #2102
 CONT: A.D. SABA ENTERPRISES
 TEL: (561)969-2920
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)THE DESIGN PROFESSIONAL SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO THE DRAWINGS PER
 FLORIDA STATUTES 481.221(1)
  
 4)AN ENGINEER SHALL PROVIDE THE CALCULATION FOR THE
 DESIGN PRESSURE OF THE NEW DOOR DUE TO THE FACT THAT
 THE BUILDING IS OVER 60 FEET. ON THE PRODUCT APPROVAL;
 CIRCLE OR HI-LIGHT ALL INFORMATION PERTAINING TO THE
 DOOR INCLUDING THE WIDTH OF THE PANELS AND THE DOOR
 HEIGHT. DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE
 REQUIRED TO BE DESIGNED USING ASCE7, FBC1609.1.1 AND
 MUST BE DONE BY AN ENGINEER. DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15-23.002.
  
 5)1714.5.1 THE DESIGN PRESSURE FOR WINDOW AND DOOR
 ASSEMBLIES SHALL BE CALCULATED IN ACCORDANCE WITH
 COMPONENTS AND CLADDING WIND LOAD IN FBC 1609
  
 6)INDICATE HOW THE NEW DOOR WILL BE ATTACHED TO THE
 STRUCTURE OF THE BUILDING. DOOR AND WINDOW BUCKS SHALL
 EXTEND BEYOND THE INTERIOR FACE OF THE FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. WHERE THE WOOD
 BUCK THICKNESS IS 1 ? INCHES OR GREATER, THE BUCK SHALL
 BE SECURELY FASTENED TO TRANSFER LOAD TO THE MASONRY,
 CONCRETE OR THE OTHER STRUCTURAL SUBSTRATE AND THE BUCK
 SHALL EXTEND BEYOND THE INTERIOR FACE OF THE DOOR
 FRAME. PROVIDE THE NEW DOOR BUCK DETAIL. FBC
 1714.5.4.2.
  
 7)IS THE PATIO FLOOR AND THE EXISTING BEDROOM FLOOR
 ON THE SAME LEVEL? IF NOT, WILL THE CONTRACTOR BUILD UP
 THE PATIO FLOOR TO MAKE IT EVEN WITH THE EXISTING
 BEDROOM FLOOR? IF THIS IS THE CASE INDICATE AND SHOW
 WHAT MATERIALS WILL BE USED TO ACHIEVE A LEVEL FLOOR.
 PROVIDE DETAIL DRAWINGS TO SHOW COMPLIANCE. ADDITIONAL
 INFORMATION IS REQUIRED 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  