Plan Review Notes
Plan Review Notes For Permit 08060778
Permit Number 08060778
Review Stop E
Sequence Number 3
Notes
Date Text
2008-11-06 08:55:46 
  
  
  
  
  
  
 PROVISO
  
 SHEET E-2 MUST BE REVISED ON THE BASE BUILDING PERMIT
 AS THAT PERMIT IS IN AN OPEN STATUS PRIOR TO
 INSTALLATION OF THE 600 AMP SERVICE SHOWN ON THIS PLAN.
 THE PERMITTED SET OF PLANS INDICATES A 400 AMP SERVICE
 AND THE RISER SUBMITTED FOR THIS PERMIT HAS A 600 AMP
 SERVICE
  