| 2008-07-03 09:58:18 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THE ENERGY CALCULATIONS NEED TO BE SIGNED BY |
| | OWNER/AGENT, PER FBC- 2004 SECTION 13-103.3. |
| | |
| | 2. THE ENERGY CALCULATIONS FAIL TO HAVE THE WATER |
| | HEATER. THE NEW WATER HEATER FOR THE CABANA SHALL |
| | COMPLY WITH FBC- 2004 TABLE 13-612.1.ABC.3.2 MINIMUM |
| | PERFORMANCE STANDARDS WATER HEATING EQUIPMENT. |
| | |
| | 3. SHEET A-06 POOL CABANA PLUMBING RISER. PLEASE |
| | CORRECT THE SANITARY RISER DIAGRAM PER FBC- PLUMBING |
| | THE FOLLOWING SECTIONS. |
| | |
| | A} 917.7 VENT REQUIRED. WITHIN EACH PLUMBING SYSTEM, A |
| | MINIMUM OF ONE VENT OR VENT STACK SHALL EXTEND OUTDOORS |
| | TO THE OPEN AIR. THE SUBMITTED RISER DIAGRAM INDICATES |
| | TWO STUDOR VENTS BEING INSTALLED WITH NO VENT OUTDOORS |
| | TO OPEN AIR. |
| | |
| | B} PLEASE CLEARLY INDICATE THE CLEANOUT AT THE |
| | JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER AS |
| | BEING A TWO-WAY CLEANOUT. PER SECTION 708.3.5. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |