| Plan Review Notes For Permit 08060778 |
| Permit Number |
08060778 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-27 16:39:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-103.3. | | | | | | 2) THE COOLING LOAD CALCULATIONS NEED TO BE THE LONG | | | FORM, PER 2004 FBC 13-607.1.ABC.1. | | | | | | 3) THE MECHANICAL PLAN NEEDS THE JOB ADDRESS ON THEM, | | | PER 2004 WPB AMEND. 106.1.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|