| Plan Review Notes For Permit 08060778 |
| Permit Number |
08060778 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-30 11:48:09 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} SHEET E-2 MUST BE REVISED ON THE BASE BUILDING | | | PERMIT AS THAT PERMIT IS IN AN OPEN STATUS. THE | | | PERMITTED SET OF PLANS INDICATES A 400 AMP SERVICE AND | | | THE RISER SUBMITTED FOR THIS PERMIT HAS A 600 AMP | | | SERVICE.THERE ARE SEVERAL INCONSISTENCIES BETWEEN THE | | | TWO SETS OF PLANS. PLEASE VERIFY THAT THE SET SUBMITTED | | | WAS THE ONE INTENDED TO BE SUBMITTED. | | | | | | REGARDING SHEET A-6: | | | | | | 2} THE WATER HEATER AND AHU DISCONNECTS DO NOT COMPLY | | | WITH 110.26 SPACING REQUIREMENTS AS SHOWN ON THE PLAN. | | | | | | 3} THE 100 AMP DISCONNECT MUST COMPLY WITH 250.32 WHICH | | | WOULD BE SHOWN ON THE CORRECTED RISER SHEET E-2. | | | | | | 4} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 | | | NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID | | | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE | | | LOCATIONS OF THE SOUNDING DEVICES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|