Plan Review Notes
Plan Review Notes For Permit 08060778
Permit Number 08060778
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-30 11:48:09 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E-2 MUST BE REVISED ON THE BASE BUILDING
 PERMIT AS THAT PERMIT IS IN AN OPEN STATUS. THE
 PERMITTED SET OF PLANS INDICATES A 400 AMP SERVICE AND
 THE RISER SUBMITTED FOR THIS PERMIT HAS A 600 AMP
 SERVICE.THERE ARE SEVERAL INCONSISTENCIES BETWEEN THE
 TWO SETS OF PLANS. PLEASE VERIFY THAT THE SET SUBMITTED
 WAS THE ONE INTENDED TO BE SUBMITTED.
  
 REGARDING SHEET A-6:
  
 2} THE WATER HEATER AND AHU DISCONNECTS DO NOT COMPLY
 WITH 110.26 SPACING REQUIREMENTS AS SHOWN ON THE PLAN.
  
 3} THE 100 AMP DISCONNECT MUST COMPLY WITH 250.32 WHICH
 WOULD BE SHOWN ON THE CORRECTED RISER SHEET E-2.
  
 4} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718