| Plan Review Notes For Permit 08060706 |
| Permit Number |
08060706 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2009-09-24 11:33:16 | ** REDLINED PLANS ** | | | | | | | | | | | | 1) NOTE: PREVIOUS PLANS CONTAINED A 50AMP BREAKER FOR | | | THE 30KVA TRANSFORMER WHICH WAS OK. THE REVIEW COMMENT | | | HAD TO DO WITH THE INCORRECT CONDUCTOR SIZES. | | | THE OVER CURRENT PROTECTION FOR THE SAME 30 KVA | | | TRANSFORMER HAS NOW BEEN REVISED FROM THE PREVIOUS | | | PLANS AND DOES NOT MEET 450.3B. THE MAXIMUM OCP FOR | | | THIS SIZE TRANSFORMER IS 125%. | | | THE 125% COMES OUT TO JUST OVER 45AMPS. HOWEVER IT IS | | | PERMISSIBLE TO GO UP TO 50AMPS. | | | A 45AMP OR 50AMP BREAKER IS PERMITTED HOWEVER 60AMP IS | | | TOO HIGH. | | | IF TRANSFORMER MEETS NOTE #3 ON TABLE THEN IT WOULD BE | | | OK, HOWEVER THE TRANSFORMER ONSITE WOULD HAVE TO MEET | | | *ALL* OF NOTE #3 OF 450.3B TABLE NOTES. | | | | | | ** PLANS MAY BE REVISED BY SUBMITTED A SMALLER VERSION | | | OF THE PANEL SCHEDULE WITH THE CORRECT OCP AND | | | CONDUCTORS ON 8 ?? BY 11 SHEETS. STILL REQUIRED TO | | | CONTAIN TITLE BLOCKS, SIGNATURE, DATE AND SEAL PER FAC | | | 61G15-23.002, FS 471.025 | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|