Plan Review Notes
Plan Review Notes For Permit 08060706
Permit Number 08060706
Review Stop E
Sequence Number 6
Notes
Date Text
2009-09-24 11:33:16** REDLINED PLANS **
  
  
  
 1) NOTE: PREVIOUS PLANS CONTAINED A 50AMP BREAKER FOR
 THE 30KVA TRANSFORMER WHICH WAS OK. THE REVIEW COMMENT
 HAD TO DO WITH THE INCORRECT CONDUCTOR SIZES.
 THE OVER CURRENT PROTECTION FOR THE SAME 30 KVA
 TRANSFORMER HAS NOW BEEN REVISED FROM THE PREVIOUS
 PLANS AND DOES NOT MEET 450.3B. THE MAXIMUM OCP FOR
 THIS SIZE TRANSFORMER IS 125%.
 THE 125% COMES OUT TO JUST OVER 45AMPS. HOWEVER IT IS
 PERMISSIBLE TO GO UP TO 50AMPS.
 A 45AMP OR 50AMP BREAKER IS PERMITTED HOWEVER 60AMP IS
 TOO HIGH.
 IF TRANSFORMER MEETS NOTE #3 ON TABLE THEN IT WOULD BE
 OK, HOWEVER THE TRANSFORMER ONSITE WOULD HAVE TO MEET
 *ALL* OF NOTE #3 OF 450.3B TABLE NOTES.
  
 ** PLANS MAY BE REVISED BY SUBMITTED A SMALLER VERSION
 OF THE PANEL SCHEDULE WITH THE CORRECT OCP AND
 CONDUCTORS ON 8 ?? BY 11 SHEETS. STILL REQUIRED TO
 CONTAIN TITLE BLOCKS, SIGNATURE, DATE AND SEAL PER FAC
 61G15-23.002, FS 471.025
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  