Plan Review Notes
Plan Review Notes For Permit 08060706
Permit Number 08060706
Review Stop E
Sequence Number 5
Notes
Date Text
2009-09-11 10:09:19** DENIED **
  
  
 1) NOTE: TRANSFORMER ON ORIGINAL PLANS STATED 15K AND
 REVISED IS NOW 30K.
 PLEASE COORDINATE RISER AND 277/480 PANEL. RISER
 INDICATES #6 CONDUCTORS TO TRANSFORMER HOWEVER PANEL
 SCHEDULE INDICATES #12. PER 240.21,240.4,310.16 #12 AWG
 IS NOT LARGE ENOUGH.
  
 2) NOTE: REVISION NOW HAS TRANSFORMER BEING RELOCATED.
 THE NEW LOCATION APPEARS TO SHOW THE TAPPED CONDUCTORS
 EXCEEDING THE LIMITS OF 240.21.
 THE TAPPED CONDUCTOR RULE IS 10FT OF CONDUCTORS. PLEASE
 REVISE BY ADDING A DISCONNECTING MEANS WITH OVER
 CURRENT PROTECTION, OR RELOCATE. IF ACTUAL TAPPED
 CONDUCTOR LENGTH IS 10FT OR LESS PROVIDE THIS ON PLANS.
 BASED ON SCALE OF PLANS THIS IS NOT POSSIBLE WITH THE
 LOCATION SHOWN.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  