| Plan Review Notes For Permit 08060706 |
| Permit Number |
08060706 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2009-09-11 10:09:19 | ** DENIED ** | | | | | | | | | 1) NOTE: TRANSFORMER ON ORIGINAL PLANS STATED 15K AND | | | REVISED IS NOW 30K. | | | PLEASE COORDINATE RISER AND 277/480 PANEL. RISER | | | INDICATES #6 CONDUCTORS TO TRANSFORMER HOWEVER PANEL | | | SCHEDULE INDICATES #12. PER 240.21,240.4,310.16 #12 AWG | | | IS NOT LARGE ENOUGH. | | | | | | 2) NOTE: REVISION NOW HAS TRANSFORMER BEING RELOCATED. | | | THE NEW LOCATION APPEARS TO SHOW THE TAPPED CONDUCTORS | | | EXCEEDING THE LIMITS OF 240.21. | | | THE TAPPED CONDUCTOR RULE IS 10FT OF CONDUCTORS. PLEASE | | | REVISE BY ADDING A DISCONNECTING MEANS WITH OVER | | | CURRENT PROTECTION, OR RELOCATE. IF ACTUAL TAPPED | | | CONDUCTOR LENGTH IS 10FT OR LESS PROVIDE THIS ON PLANS. | | | BASED ON SCALE OF PLANS THIS IS NOT POSSIBLE WITH THE | | | LOCATION SHOWN. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|