| Plan Review Notes For Permit 08060706 |
| Permit Number |
08060706 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-10-28 16:48:01 | | | | | | | ** DENIED REVIEW** | | | | | | | | | | | | 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND | | | NOT FOR PERMIT APPLICATION. | | | | | | 2) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1, | | | .1.2 . | | | ** PLEASE BE SURE TO LOOK AT SECTIONS NOTED ESPECIALLY | | | FOR TRACK LIGHTING. | | | PLEASE SEE THE LIGHTING SHALL BE BASED ON THE WATTAGE | | | OF THE FIXTURES OR THE MINIMUM 30VA PER FT OF TRACK | | | WHICH EVER IS GREATER. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|