| 2008-09-12 16:39:47 | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND |
| | NOT FOR PERMIT APPLICATION. |
| | |
| | 2) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1, |
| | .1.2 . THE SUBMITTED METHOD*C* CALCULATIONS ARE NOT |
| | COMPLETE AND DO NOT COMPLY WITH THE CODE SECTIONS AS |
| | NOTED. THE TOTAL EFFECTIVE WATTAGE SHOWN AS 631 IS NOT |
| | POSSIBLE AS THE DISPLAY OR ACCENT LIGHTING IN THIS |
| | OCCUPANCY UNDER THE CONTROLS WHICH ARE SHOWN ARE NOT |
| | EXEMPT. |
| | PLEASE MEET PRESCRIPTIVE REQUIREMENTS. IT WAS NOTED IN |
| | NOTE #7 ON PREVIOUS REVIEW. |
| | ** PLEASE BE SURE TO LOOK AT SECTIONS NOTED ESPECIALLY |
| | FOR TRACK LIGHTING. |
| | ** BASED ON THE WATTAGE NUMBERS AT THIS TIME THE |
| | LIGHTING IS SHOWN AS THREE TIMES OVER THE ALLOWANCE AS |
| | METHOD *C*. |
| | |
| | 3) NOTE: DOCUMENTS SUBMITTED WITH NOT SIGNED, DATED, |
| | SEALED OR CERTIFIED IN ANY MANOR. THIS WAS NOTE #2 ON |
| | PREVIOUS REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE #2. |
| | PLEASE SEE THE CERTIFICATION SHEET SUBMITTED PAGE 3 |
| | INDICATES A PERSON PREPARING DOCUMENTS OTHER THAN THE |
| | ENGINEER OF RECORD. THIS IS NOT PERMITTED. PLEASE BE |
| | SURE THE CERTIFICATION SHEET IS SIGNED, DATED AND |
| | SEALED. |
| | FBC 13-103.1, FAC 61G15-23.002, FS 471.025 |
| | |
| | 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** SAME AS PREVIOUS REVIEW. PLEASE SEE ELECTRICAL PLANS |
| | ONLY STATE TO COMPLY WITH CODES AND DO NOT LIST THE |
| | ABOVE AS NOTED. |
| | ** PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY AND |
| | HAVE NOT BEEN SUBMITTED FOR PERMIT APPLICATION. |
| | |
| | |
| | 5) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 AND FLORIDA STATUTES 481.219 FOR REQUIRED |
| | INFORMATION ON TITLE BLOCKS WHICH IS MISSING FROM ALL |
| | SHEETS FOR THE ARCHITECTURAL FIRM. |
| | MISSING PRINTED NAME. |
| | MISSING PRINTED LICENSE NUMBER |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADE |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | |
| | 6) NOTE: ** SAME AS PREVIOUS REVIEW** |
| | PLEASE SEE ELECTRICAL PLANS SEEMED TO BE SIGNED WITH AN |
| | INITIAL OF SOME KIND. IF THIS IS INDEED THE LEGAL |
| | SIGNATURE PLEASE PROVIDE A SIGNATURE VERIFICATION |
| | LETTER SIGNED, DATED, SEALED AND NOTARIZED. THIS WILL |
| | BE PLACED IN SIGNATURE FILE FOR FUTURE REFERENCE. |
| | FS 471.025 |
| | |
| | 7) NOTE: PLEASE SEE MISSING AUTOMATED LIGHTING CONTROLS |
| | PER 13-415.1.ABC.1.1, .1.2 AND.1.3 PLEASE PROVIDE MORE |
| | DETAIL ON THE SYSTEM, THE DEVICES, MAXIMUM TIMES, TIMED |
| | SCHEDULING, OVER RIDES ETC. |
| | |
| | 9) NOTE: ** THIS IS THE SAME NOTE FROM PREVIOUS REVIEW |
| | IN FACT THE RISER WAS CHANGED TO NOW SHOW THE BREAKER |
| | IN PANEL *A* AS 60AMP MCB YET THE PANEL SCHEDULE STILL |
| | SHOWS 100AMPS. THIS DOES NOT MEET MINIMUM REQUIRED IN |
| | THE NEC. |
| | SECTIONS AS NOTED PREVIOUSLY. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE RISER SHOWS EXISTING #4 ON THE SECONDARY |
| | SIDE OF THE TRANSFORMER. PLEASE SEE 240.21, 310.16, |
| | 240.4, AND 240.6 AS THIS SIZE CONDUCTOR DOES NOT MEET |
| | ANY OF THESE SECTIONS. THIS IS A FIRE AND LIFE SAFETY |
| | HAZARD AND EVEN IF EXISTS THE CONDUCTOR SIZE SHALL MEET |
| | THE MINIMUM FOR CODE COMPLIANCE. |
| | PLEASE ADJUST. |
| | |
| | 10) NOTE: AS NOTED PREVIOUSLY PLEASE COMPLETE PANEL |
| | SCHEDULES WITH ALL CONDUCTORS AND OVER CURRENT |
| | PROTECTION. |
| | 408.4, 310.16, 240.4, 450.3 ETC. |
| | FBC 106.1.1 FOR CLARITY AND 106.1.2 FOR ADDITIONAL |
| | INFORMATION |
| | |
| | |
| | ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH |
| | INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK |
| | WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE |
| | REVIEW. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |