Plan Review Notes
Plan Review Notes For Permit 08060706
Permit Number 08060706
Review Stop E
Sequence Number 2
Notes
Date Text
2008-09-12 16:39:47 
 ** DENIED 2ND REVIEW **
  
 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND
 NOT FOR PERMIT APPLICATION.
  
 2) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,
 .1.2 . THE SUBMITTED METHOD*C* CALCULATIONS ARE NOT
 COMPLETE AND DO NOT COMPLY WITH THE CODE SECTIONS AS
 NOTED. THE TOTAL EFFECTIVE WATTAGE SHOWN AS 631 IS NOT
 POSSIBLE AS THE DISPLAY OR ACCENT LIGHTING IN THIS
 OCCUPANCY UNDER THE CONTROLS WHICH ARE SHOWN ARE NOT
 EXEMPT.
 PLEASE MEET PRESCRIPTIVE REQUIREMENTS. IT WAS NOTED IN
 NOTE #7 ON PREVIOUS REVIEW.
 ** PLEASE BE SURE TO LOOK AT SECTIONS NOTED ESPECIALLY
 FOR TRACK LIGHTING.
 ** BASED ON THE WATTAGE NUMBERS AT THIS TIME THE
 LIGHTING IS SHOWN AS THREE TIMES OVER THE ALLOWANCE AS
 METHOD *C*.
  
 3) NOTE: DOCUMENTS SUBMITTED WITH NOT SIGNED, DATED,
 SEALED OR CERTIFIED IN ANY MANOR. THIS WAS NOTE #2 ON
 PREVIOUS REVIEW.
  
 ** PREVIOUS REVIEW NOTE #2.
 PLEASE SEE THE CERTIFICATION SHEET SUBMITTED PAGE 3
 INDICATES A PERSON PREPARING DOCUMENTS OTHER THAN THE
 ENGINEER OF RECORD. THIS IS NOT PERMITTED. PLEASE BE
 SURE THE CERTIFICATION SHEET IS SIGNED, DATED AND
 SEALED.
 FBC 13-103.1, FAC 61G15-23.002, FS 471.025
  
 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** SAME AS PREVIOUS REVIEW. PLEASE SEE ELECTRICAL PLANS
 ONLY STATE TO COMPLY WITH CODES AND DO NOT LIST THE
 ABOVE AS NOTED.
 ** PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT APPLICATION.
  
  
 5) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUTES 481.219 FOR REQUIRED
 INFORMATION ON TITLE BLOCKS WHICH IS MISSING FROM ALL
 SHEETS FOR THE ARCHITECTURAL FIRM.
 MISSING PRINTED NAME.
 MISSING PRINTED LICENSE NUMBER
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADE
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
  
 6) NOTE: ** SAME AS PREVIOUS REVIEW**
 PLEASE SEE ELECTRICAL PLANS SEEMED TO BE SIGNED WITH AN
 INITIAL OF SOME KIND. IF THIS IS INDEED THE LEGAL
 SIGNATURE PLEASE PROVIDE A SIGNATURE VERIFICATION
 LETTER SIGNED, DATED, SEALED AND NOTARIZED. THIS WILL
 BE PLACED IN SIGNATURE FILE FOR FUTURE REFERENCE.
 FS 471.025
  
 7) NOTE: PLEASE SEE MISSING AUTOMATED LIGHTING CONTROLS
 PER 13-415.1.ABC.1.1, .1.2 AND.1.3 PLEASE PROVIDE MORE
 DETAIL ON THE SYSTEM, THE DEVICES, MAXIMUM TIMES, TIMED
 SCHEDULING, OVER RIDES ETC.
  
 9) NOTE: ** THIS IS THE SAME NOTE FROM PREVIOUS REVIEW
 IN FACT THE RISER WAS CHANGED TO NOW SHOW THE BREAKER
 IN PANEL *A* AS 60AMP MCB YET THE PANEL SCHEDULE STILL
 SHOWS 100AMPS. THIS DOES NOT MEET MINIMUM REQUIRED IN
 THE NEC.
 SECTIONS AS NOTED PREVIOUSLY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER SHOWS EXISTING #4 ON THE SECONDARY
 SIDE OF THE TRANSFORMER. PLEASE SEE 240.21, 310.16,
 240.4, AND 240.6 AS THIS SIZE CONDUCTOR DOES NOT MEET
 ANY OF THESE SECTIONS. THIS IS A FIRE AND LIFE SAFETY
 HAZARD AND EVEN IF EXISTS THE CONDUCTOR SIZE SHALL MEET
 THE MINIMUM FOR CODE COMPLIANCE.
 PLEASE ADJUST.
  
 10) NOTE: AS NOTED PREVIOUSLY PLEASE COMPLETE PANEL
 SCHEDULES WITH ALL CONDUCTORS AND OVER CURRENT
 PROTECTION.
 408.4, 310.16, 240.4, 450.3 ETC.
 FBC 106.1.1 FOR CLARITY AND 106.1.2 FOR ADDITIONAL
 INFORMATION
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH
 INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK
 WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE
 REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  