Plan Review Notes
Plan Review Notes For Permit 08060706
Permit Number 08060706
Review Stop B
Sequence Number 2
Notes
Date Text
2008-09-11 11:30:11BUILDING PLAN REVIEW
 PERMIT: 08060706 PLAN REVIEW/MAJOR WORKING DRAWINGS
 ADD: 600 S. ROSEMARY AVE. PH 03
 CONT: BERGMEYER ASSOCIATES
 TEL: (617)695-7759
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 SEPT. 11,2008
  
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B) NOT APPLICABLE.
  
 1C) PLEASE SEE COMMENT # 3 SITED CODE. 106.1.1* W.P.B.
 ADMINISTRATIVE CODE/2004 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E-G) COMPLIED.
  
 2) COMPLIED.
  
 3) 2ND REQUEST, AS STATED ABOVE 106.1.1 SUCH
 INFORMATION SHALL BE SPECIFIC TO THE TECNICAL CODE,
 CODE CAN NOT BE REPEATED AS SATISFYING THE CODE ISSUE.
 THIS IS MISSING WIND INFORMATION NEEDED TO BE ABLE TO
 COMPLETE THE REVIEW. TO DATE THE DESIGNER OF RECORD HAS
 NOT PROVIDED WIND INFORMATION NOR PRESSURES FOR
 COMPONENTS AND CLADDING. SHEET AD-101 INDICATES THE
 REMOVAL OF THE STOREFRONT SYSTEM AND A401 & A402
 INDICATE VARIOUS DETAILS OF THE NEW STOREFRONT SYSTEM
 BUT NO WIND DESIGN INFORMATION IS INDICATED WWITHIN THE
 PLANS: 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 4) 2ND REQUEST, SUBMITTED WERE TWO DIFERENT SETS
 OFPRODUCTS, (2) PGT PRODUCTS & (2) KAWNEER:
 PGT NOA 07-0817.04 SERIES "IR-500" ALUMINIUM GLAZING (W
 SOLUTIA/ DUPONT'S PVB) WINDOW WALL
 PGT NOA 06-0309.01 SERIES "IR-500" ALUMINIUM GLAZED (W/
 STORM GUARD) WINDOW WALL SYSTEM
  
 KAWNEER NOA 04-0123.01 SERIES "IR 500" GLAZED WALL
 -IMPACT NOTE THE MAXIMUM SPACING FOR GLAZED UNITS IS
 48" SEE SHEET 1OF 8.
 KAWNEER NOA 040123.02 SERIES 350 OUTSWING STOREFRONT
 DOOR W/IR 500 FRAMING SYSTEM
  
 PLEASE NOTE THAT ALSO SUBMITTED WAS A COVERSHEET FOR
 KAWNEER IR500/501 FRAMING AND SUPPOSED SHOP DRAWINGS
 THAT ARE ONLY ENLARGED TECHNICAL SHEETS FROM THE
 KAWNEER 07-0817.04 NOA.
 PLEASE REMOVE SETS OF PRODUCT APPROVALS NOT TO BE
 REVIEWED FOR CODE COMPLIANCE.
  
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 4A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 4A)(1) STOREFRONT NOA SUBMITTED IS NOT ONE LISTED ON
 STATE WEB-SITE THER ARE 3 IR500 REPORTS LISTED.
 4A)(2) GLAZED EXTERIOR SWING DOORS
 4A)(3) MULLIONS-VERTICAL
  
 4B) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5) SHEET A402 DETAIL# 4 INDICATES AN EXTERIOR MALL
 WALKWAY, THIS IS THE EXTERIOR OFTHE BUILDING AND NOT
 LOCATED WITHIN A MALL, PLEASE INDICATE HOW THIS
 INSTALLATION WILL MAKE A WATERTIGHT SEAL.
 1403.2. WEATHER PROTECTION. EXTERIOR WALLS SHALL
 PROVIDE THE BUILDING WITH A WEATHER-RESISTANT EXTERIOR
 WALL ENVELOPE. THE EXTERIOR WALL ENVELOPE SHALL INCLUDE
 FLASHING, AS DESCRIBED IN SECTION 1405.3 .
 1405.3 FLASHING.
 FLASHING SHALL BE INSTALLED IN SUCH A MANNER SO AS TO
 PREVENT MOISTURE FROM ENTERING THE WALL OR TO REDIRECT
 IT TO THE EXTERIOR. FLASHING SHALL BE INSTALLED AT THE
 PERIMETERS OF EXTERIOR DOOR AND WINDOW ASSEMBLIES,
 PENETRATIONS AND TERMINATIONS OF EXTERIOR WALL
 ASSEMBLIES, EXTERIOR WALL INTERSECTIONS WITH ROOFS,
 CHIMNEYS, PORCHES, DECKS, BALCONIES AND SIMILAR
 PROJECTIONS AND AT BUILT-IN GUTTERS AND SIMILAR
 LOCATIONS WHERE MOISTURE COULD ENTER THE WALL. FLASHING
 WITH PROJECTING FLANGES SHALL BE INSTALLED ON BOTH
 SIDES AND THE ENDS OF COPINGS, UNDER SILLS AND
 CONTINUOUSLY ABOVE PROJECTING TRIM.
  
 6) 2ND REQUEST, SHEET A401DETAIL# 2 INDICATES A
 STOREFRONT FRAME, PLEASE PROVIDE A CUT SECTION THROUGH
 THE STOREFRONT FRAME AND DOOR FRAME, THIS IS WHERE IT
 WOULD APPEAR A VERTICAL MULLION WOULD BE REQUIRED,
 PLEASE PROVIDE ADDITIONAL INFORMATION HOW THE WIND
 LOADS WILL BE MET IN 1609.6.2.2. COMPONENTS AND
 CLADDING.
  
 7) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.