Plan Review Notes
Plan Review Notes For Permit 08060706
Permit Number 08060706
Review Stop P
Sequence Number 1
Notes
Date Text
2008-07-18 12:00:11PLUMBING PLAN REVIEW:
 DENIED:
  
 **FOR PLAN REVIEW ONLY NOT FOR PERMT**
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1.INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2. INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G1-16.004 PLANS PREPARED BY A REGISTERED
 ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL
 -
 INCLUDE THE PRINTED NAME OF THE ARCHITECT
 SEALING THE
 PLANS
 NOTE: MISSING PRINTED NAME, PRINTED LICENSE NUMBER,
 AND CERTIFICATE OF AUTHORIZATION NUMBER.
  
 3. SHEET GOO1 PLUMBING FACILITIES: INDICATES BOTTLED
 WATER PROVIDED INSTEAD OF THE REQUIRED DRINKING
 FOUNTAIN. PER FBC- PLUMBING SECTION 410.1 BOTTLED WATER
 DISPENSERS SHALL BE PERMITTED TO BE SUBSTITUTED FOR NOT
 MORE THAN 50 PERCENT OF THE REQUIRED DRINKING
 FOUNTAINS. PER FBC- PLUMBING TABLE 401.3 WITH AN
 OCCUPANCY OF MERCANTILE (M) DRINKING FOUNTAIN
 REQUIREMENTS ARE 1 PER 1000. PLEASE INDICATE THE
 REQUIRED DRINKING FOUNTAIN ON THE RESUBMITTED SHEET
 A101 CONSTRUCTION FLOOR PLAN, SHEET M102 PLUMBING PLAN,
 SANITARY AND WATER RISER DIAGRAMS.
 NOTE: THE DRINKING FOUNTAIN IS REQUIRED TO BE
 ACCESSIBLE AND COMPLIANT WITH FBC- CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE THE FOLLOWING SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
  
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
  
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
  
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
  
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE. (CLEARLY INDICATE THE REQUIRED CLEAR FLOOR SPACE
 ON SHEET A101 CONSTRUCTION FLOOR PLAN.
  
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 4. SHEET A201 DETAIL 8 & 9 INTERIOR TOILET ROOM
 ELEVATIONS: PLEASE PROVIDE THE FOLLOWING REQUIRED
 INFORMATION PER FBC- CHAPTER 11, FLORIDA ACCESSIBILITY
 CODE.
  
 A} WATER CLOSET= CLEARLY INDICATE THE HEIGHT OF THE
 WATER CLOSET 17"-19". PER SECTION 11-4.16.3.
 B} LAVATORY= CLEARLY PROVIDE A CLEARANCE OF AT LEAST
 29 INCHES ABOVE THE FINNISH FLOOR TO THE BOTTOM OF THE
 APRON. KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE
 31. PER SECTION 11-4.19.2.
  
 5. SHEET M102 WATER RISER DIAGRAM: PER FBC- PLUMBING
 SECTION 604.9 WATER HAMMER. WATER-HAMMER ARRESTORS
 SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS. MANUFACTURER'S
 SPECIFICATIONS FRO BOTH MODELS PPP AND SIOUX CHIEF
 STATE THAT WATER-HAMMER ARRESTORS SHALL BE PLACED AS
 NEAR TO THE SOURCE OF SHOCK AS POSSIBLE. PLEASE LOCATE
 WATER-HAMMER ARRESTORS CLOSE TO FIXTURE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved