Plan Review Notes
Plan Review Notes For Permit 08060706
Permit Number 08060706
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-07-23 15:08:20***DENIED***
  
 FOR PLAN REVIEW ONLY NOT FOR PERMIT
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003. PLEASE ADD TO
 CODE SECTION ON SHEET G-001.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241. PLEASE ADD TO CODE SECTION ON SHEET
 G-001.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHER(S) REQUIRED WITH
 LOCATION(S) BEING ILLUSTRATED ON PLANS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL.
  
 5) ADDRESS SUITE NUMBER SHALL MEET THE STANDARDS OF
 CITY OF WEST PALM BEACH FOR COMMERCIAL BUILDINGS. SUITE
 NUMBER SHALL BE PROVIDED AT THE REAR ENTRANCE FOR
 EMERGENCY UNIT IDENTIFICATION. SUITE NUMBERS TO BE A
 MINIMUM OF 3" IN HEIGHT AND CONTRASTING WITH
 BACKGROUND.
  
 6) NEW FIRE DAMPER INSTALLATIONS TO BE TESTED FOR
 CLOSURE IN ACCORDANCE WITH UL 555 AND APPROVED PRIOR TO
 FINAL INSPECTION.
  
 7) DUCT SMOKE DETECTORS SHALL BE LOCATED IN SUPPLY DUCT
 UNLESS BOTH SUPPLY AND RETURN DUCTS ARE REQUIRED. WHERE
 FIRE ALARM SYSTEM IS PROVIDED, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 8) LOCKING ARRANGEMENTS SHALL MEET THE REQUIREMENTS OF
 NFPA 101, SEC. 7.2.1.5.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  