| Plan Review Notes For Permit 08060706 |
| Permit Number |
08060706 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-23 15:08:20 | ***DENIED*** | | | | | | FOR PLAN REVIEW ONLY NOT FOR PERMIT | | | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | | SAFETY TO COMPLY WITH NFPA 101, 2003. PLEASE ADD TO | | | CODE SECTION ON SHEET G-001. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. PLEASE ADD TO CODE SECTION ON SHEET | | | G-001. | | | | | | 3) 2A-10B,C RATED FIRE EXTINGUISHER(S) REQUIRED WITH | | | LOCATION(S) BEING ILLUSTRATED ON PLANS. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE | | | SPRINKLER REMODEL. | | | | | | 5) ADDRESS SUITE NUMBER SHALL MEET THE STANDARDS OF | | | CITY OF WEST PALM BEACH FOR COMMERCIAL BUILDINGS. SUITE | | | NUMBER SHALL BE PROVIDED AT THE REAR ENTRANCE FOR | | | EMERGENCY UNIT IDENTIFICATION. SUITE NUMBERS TO BE A | | | MINIMUM OF 3" IN HEIGHT AND CONTRASTING WITH | | | BACKGROUND. | | | | | | 6) NEW FIRE DAMPER INSTALLATIONS TO BE TESTED FOR | | | CLOSURE IN ACCORDANCE WITH UL 555 AND APPROVED PRIOR TO | | | FINAL INSPECTION. | | | | | | 7) DUCT SMOKE DETECTORS SHALL BE LOCATED IN SUPPLY DUCT | | | UNLESS BOTH SUPPLY AND RETURN DUCTS ARE REQUIRED. WHERE | | | FIRE ALARM SYSTEM IS PROVIDED, DUCT SMOKE DETECTORS | | | SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 8) LOCKING ARRANGEMENTS SHALL MEET THE REQUIREMENTS OF | | | NFPA 101, SEC. 7.2.1.5. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | | | | |
|