Plan Review Notes For Permit 08060706
Permit Number 08060706
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-17 16:49:32** DENIED **
  
 ** PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT APPLICATION.
  
  
 1) NOTE: PLEASE SEE FBC 13-400.3.A, 13-400.3.B,
 13-400.3.C. THE VERSION REQUIRED AND AS ADOPTED PER
 SECTION GIVEN SHALL BE 2.5. PLEASE KNOW IT IS THE
 UNDERSTANDING OF THIS OFFICE THERE IS A PATCH AVAILABLE
 ON THE ENERGY GAUGE WEBSITE WHICH WILL PROVIDE THE 2.5
 VERSION AS REQUIRED.
  
  
 2) NOTE: PLEASE SEE THE CERTIFICATION SHEET SUBMITTED
 PAGE 3 INDICATES A PERSON PREPARING DOCUMENTS OTHER
 THAN THE ENGINEER OF RECORD. THIS IS NOT PERMITTED.
 PLEASE BE SURE THE CERTIFICATION SHEET IS SIGNED, DATED
 AND SEALED.
 FBC 13-103.1, FAC 61G15-23.002, FS 471.025
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 4) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUTES 481.219 FOR REQUIRED
 INFORMATION ON TITLE BLOCKS WHICH IS MISSING FROM ALL
 SHEETS FOR THE ARCHITECTURAL FIRM.
 MISSING PRINTED NAME.
 MISSING PRINTED LICENSE NUMBER
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADE
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
  
 5) NOTE: PLEASE SEE FAC 61G15-23.002 AND FS 471.023 FOR
 MISSING INFORMATION FROM THE TITLE BLOCKS FOR
 ENGINEERING FIRM.
 MISSING PRINTED NAME.
 MISSING PRINTED LICENSE NUMBER
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 6) NOTE: PLEASE SEE ELECTRICAL PLANS SEEMED TO BE
 SIGNED WITH AN INITIAL OF SOME KIND. IF THIS IS INDEED
 THE LEGAL SIGNATURE PLEASE PROVIDE A SIGNATURE
 VERIFICATION LETTER SIGNED, DATED, SEALED AND
 NOTARIZED. THIS WILL BE PLACED IN SIGNATURE FILE FOR
 FUTURE REFERENCE.
 FS 471.025
  
 7) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE MISSING THE INPUT DATA REPORT. SEE PAGE 2 WHICH
 SPECIFICALLY STATES THE INPUT DATA REPORT MUST
 ACCOMPANY SUMMARY OF CALCULATIONS.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR MISSING
 REQUIRED PERFORMANCE CALCULATIONS AND VERIFICATION TO
 BE SUBMITTED ON CALCULATIONS.
 PLEASE BE SURE TO SEE SECTIONS ABOVE IN SPECIFIC TO
 MINIMUM REQUIRED SHALL BE BASED ON FIXTURE NOT BULB
 WATTAGE.
 PLEASE BE SURE TO ALSO SEE THE SECTION ABOVE WITH
 RESPECT TO TRACK LIGHTING.
 ** IT IS IMPORTANT TO KNOW THE SUBMITTED CALCULATIONS
 INDICATE IN THE SUMMARY SHEETS THE TOTAL WATTAGE OF ALL
 LIGHTS IS 631.0 WATTS. THIS IS NOT POSSIBLE WHEN THE
 PLANS CONTAIN A MUCH GREATER AMOUNT.
 ** ONE TRACK LIGHT FIXTURE ALONE IS GREATER THAN THE
 TOTAL SHOWN.
  
 8) NOTE: PLEASE SEE MISSING AUTOMATED LIGHTING CONTROLS
 PER 13-415.1.ABC.1.1, .1.2 AND.1.3. THIS SPACE IS
 LOCATED IN A BUILDING GREATER THAN 5000 SQ FT AND
 AUTOMATED LIGHTING SHUT OFF IS REQUIRED UNDER THE
 FLORIDA ENERGY EFFICIENCY CODE.
 THE LIGHTING CONTROLS NOTED ON E103 DOES NOT PROVIDE
 OVER RIDES, TIMED SCHEDULING, OVER RIDE LOCATIONS,
 SEPARATE SPACE CONTROLS, DISPLAY/ACCENT LIGHTING
 CONTROLS. ETC
 PLEASE ALSO SEE 13-415.1.ABC.1.4 AS ONE OF TWO METHODS
 IS REQUIRED FOR CONTROL OF OUTSIDE LIGHTING.
 THE TIME CLOCK LISTED ON E104 DOES NOT PROVIDE MINIMUM
 FOR CODE.
  
 9) NOTE: PLEASE SEE RISER SHOWS EXISTING #4 ON THE
 SECONDARY SIDE OF THE TRANSFORMER. PLEASE SEE 240.21,
 310.16, 240.4, AND 240.6 AS THIS SIZE CONDUCTOR DOES
 NOT MEET ANY OF THESE SECTIONS. THIS IS A FIRE AND LIFE
 SAFETY HAZARD AND EVEN IF EXISTS THE CONDUCTOR SIZE
 SHALL MEET THE MINIMUM FOR CODE COMPLIANCE.
 PLEASE ADJUST.
  
 10) NOTE: PLEASE SEE 700.12F AS ALL EMERGENCY LIGHTING
 AND EXIT LIGHTING SHALL BE CIRCUITED TO THE LOCAL
 LIGHTING BRANCH CIRCUIT IN ANY ONE AREA. DOES MEET THE
 EXCEPTION IN THE NEC.
  
 11) NOTE: PLEASE SEE PANEL *B* WHICH ONLY LIST THE AHU.
 PLEASE COMPLETE WITH OVER CURRENT PROTECTION FOR ALL
 CIRCUITS.
 408.4, 310.16, 240.4, 450.3 ETC.
 FBC 106.1.1 FOR CLARITY AND 106.1.2 FOR ADDITIONAL
 INFORMATION
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR MINIMUM DESIGN THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  