| 2008-07-17 16:49:32 | ** DENIED ** |
| | |
| | ** PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY AND |
| | HAVE NOT BEEN SUBMITTED FOR PERMIT APPLICATION. |
| | |
| | |
| | 1) NOTE: PLEASE SEE FBC 13-400.3.A, 13-400.3.B, |
| | 13-400.3.C. THE VERSION REQUIRED AND AS ADOPTED PER |
| | SECTION GIVEN SHALL BE 2.5. PLEASE KNOW IT IS THE |
| | UNDERSTANDING OF THIS OFFICE THERE IS A PATCH AVAILABLE |
| | ON THE ENERGY GAUGE WEBSITE WHICH WILL PROVIDE THE 2.5 |
| | VERSION AS REQUIRED. |
| | |
| | |
| | 2) NOTE: PLEASE SEE THE CERTIFICATION SHEET SUBMITTED |
| | PAGE 3 INDICATES A PERSON PREPARING DOCUMENTS OTHER |
| | THAN THE ENGINEER OF RECORD. THIS IS NOT PERMITTED. |
| | PLEASE BE SURE THE CERTIFICATION SHEET IS SIGNED, DATED |
| | AND SEALED. |
| | FBC 13-103.1, FAC 61G15-23.002, FS 471.025 |
| | |
| | 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 4) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 AND FLORIDA STATUTES 481.219 FOR REQUIRED |
| | INFORMATION ON TITLE BLOCKS WHICH IS MISSING FROM ALL |
| | SHEETS FOR THE ARCHITECTURAL FIRM. |
| | MISSING PRINTED NAME. |
| | MISSING PRINTED LICENSE NUMBER |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADE |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | |
| | 5) NOTE: PLEASE SEE FAC 61G15-23.002 AND FS 471.023 FOR |
| | MISSING INFORMATION FROM THE TITLE BLOCKS FOR |
| | ENGINEERING FIRM. |
| | MISSING PRINTED NAME. |
| | MISSING PRINTED LICENSE NUMBER |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 6) NOTE: PLEASE SEE ELECTRICAL PLANS SEEMED TO BE |
| | SIGNED WITH AN INITIAL OF SOME KIND. IF THIS IS INDEED |
| | THE LEGAL SIGNATURE PLEASE PROVIDE A SIGNATURE |
| | VERIFICATION LETTER SIGNED, DATED, SEALED AND |
| | NOTARIZED. THIS WILL BE PLACED IN SIGNATURE FILE FOR |
| | FUTURE REFERENCE. |
| | FS 471.025 |
| | |
| | 7) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | ARE MISSING THE INPUT DATA REPORT. SEE PAGE 2 WHICH |
| | SPECIFICALLY STATES THE INPUT DATA REPORT MUST |
| | ACCOMPANY SUMMARY OF CALCULATIONS. |
| | PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR MISSING |
| | REQUIRED PERFORMANCE CALCULATIONS AND VERIFICATION TO |
| | BE SUBMITTED ON CALCULATIONS. |
| | PLEASE BE SURE TO SEE SECTIONS ABOVE IN SPECIFIC TO |
| | MINIMUM REQUIRED SHALL BE BASED ON FIXTURE NOT BULB |
| | WATTAGE. |
| | PLEASE BE SURE TO ALSO SEE THE SECTION ABOVE WITH |
| | RESPECT TO TRACK LIGHTING. |
| | ** IT IS IMPORTANT TO KNOW THE SUBMITTED CALCULATIONS |
| | INDICATE IN THE SUMMARY SHEETS THE TOTAL WATTAGE OF ALL |
| | LIGHTS IS 631.0 WATTS. THIS IS NOT POSSIBLE WHEN THE |
| | PLANS CONTAIN A MUCH GREATER AMOUNT. |
| | ** ONE TRACK LIGHT FIXTURE ALONE IS GREATER THAN THE |
| | TOTAL SHOWN. |
| | |
| | 8) NOTE: PLEASE SEE MISSING AUTOMATED LIGHTING CONTROLS |
| | PER 13-415.1.ABC.1.1, .1.2 AND.1.3. THIS SPACE IS |
| | LOCATED IN A BUILDING GREATER THAN 5000 SQ FT AND |
| | AUTOMATED LIGHTING SHUT OFF IS REQUIRED UNDER THE |
| | FLORIDA ENERGY EFFICIENCY CODE. |
| | THE LIGHTING CONTROLS NOTED ON E103 DOES NOT PROVIDE |
| | OVER RIDES, TIMED SCHEDULING, OVER RIDE LOCATIONS, |
| | SEPARATE SPACE CONTROLS, DISPLAY/ACCENT LIGHTING |
| | CONTROLS. ETC |
| | PLEASE ALSO SEE 13-415.1.ABC.1.4 AS ONE OF TWO METHODS |
| | IS REQUIRED FOR CONTROL OF OUTSIDE LIGHTING. |
| | THE TIME CLOCK LISTED ON E104 DOES NOT PROVIDE MINIMUM |
| | FOR CODE. |
| | |
| | 9) NOTE: PLEASE SEE RISER SHOWS EXISTING #4 ON THE |
| | SECONDARY SIDE OF THE TRANSFORMER. PLEASE SEE 240.21, |
| | 310.16, 240.4, AND 240.6 AS THIS SIZE CONDUCTOR DOES |
| | NOT MEET ANY OF THESE SECTIONS. THIS IS A FIRE AND LIFE |
| | SAFETY HAZARD AND EVEN IF EXISTS THE CONDUCTOR SIZE |
| | SHALL MEET THE MINIMUM FOR CODE COMPLIANCE. |
| | PLEASE ADJUST. |
| | |
| | 10) NOTE: PLEASE SEE 700.12F AS ALL EMERGENCY LIGHTING |
| | AND EXIT LIGHTING SHALL BE CIRCUITED TO THE LOCAL |
| | LIGHTING BRANCH CIRCUIT IN ANY ONE AREA. DOES MEET THE |
| | EXCEPTION IN THE NEC. |
| | |
| | 11) NOTE: PLEASE SEE PANEL *B* WHICH ONLY LIST THE AHU. |
| | PLEASE COMPLETE WITH OVER CURRENT PROTECTION FOR ALL |
| | CIRCUITS. |
| | 408.4, 310.16, 240.4, 450.3 ETC. |
| | FBC 106.1.1 FOR CLARITY AND 106.1.2 FOR ADDITIONAL |
| | INFORMATION |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR MINIMUM DESIGN THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |