Plan Review Notes
Plan Review Notes For Permit 08060706
Permit Number 08060706
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-08 16:46:08BUILDING PLAN REVIEW
 PERMIT: 08060706 PLAN REVIEW/MAJOR WORKING DRAWINGS
 ADD: 600 S. ROSEMARY AVE. PH 03
 CONT: BERGMEYER ASSOCIATES
 TEL: (617)695-7759
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS, NOTE
 GOO1 CODE SUMMARYDOES NOT INDICATE THE 2007 SUPPLEMENTS
 NOR THE 2004 EXISTING BUILDING CODE.
  
 1F) PLANS FAIL TO INDICATE TO WHAT LEVEL ALTERATION THE
 DESIGNER AND OR OWNER HAVE ELECTED TO REMODEL OR
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO SECTION
 303, 304 AND 305 OF THIS CODE. SEE SECTION 301.5 /2004
 FBC EXISTING BUILDING CODE.
  
 SHEET G001 HEADING FIRE RESISTANCE SEPERATION, TENANT
 SEPERATION- INDICATES TABLE602, PLEASE CORRECT TO
 708.1( 5) WALLS SEPERATING INDIVIDUAL TENANT SPACES,
 708.3 FIRE-RESISTANCE RATING OF THE WALLS SHALL BE AT
 LEAST 1 HR.
  
 2) NOTE: SHEET A401 AND A402 INDICATE SIGNAGE AND
 AWNINGS. BOTH REQUIRE SEPERATE PERMITS, AND NOT COVERED
 UNDER THIS PERMIT. NOTE AWNINGS ARE TO MEET THE SHEET
 A402 DETAIL# 2 INDICATES A 7'-6" AWNING WITH A 8" DROP
 FRONT OR FINISHED HEIGHT OF 6'-10". SECTION 3105.1.1.1
 NO PART OF THE CLOTH DROP SHALL BE LESS THAN 7
 FEET.WIND DESIGNS MUST MEET ONE OF THE WIND SCENARIOS
 OF 3105.2.
  
 3) SHEET AD-101 INDICATES THE REMOVAL OF THE STOREFRONT
 SYSTEM AND A401 & A402 INDICATE VARIOUS DETAILS OF THE
 NEW STOREFRONT SYSTEM BUT NO WIND DESIGN INFORMATION IS
 INDICATED WWITHIN THE PLANS: 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 4) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 4A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 4A)(1) STOREFRONT NOA SUBMITTED IS NOT ONE LISTED ON
 STATE WEB-SITE THER ARE 3 IR500 REPORTS LISTED.
 4A)(2) GLAZED EXTERIOR SWING DOORS
 4A)(3) MULLIONS-VERTICAL
  
 4B) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) SHEET A402 DETAIL# 4 INDICATES AN EXTERIOR MALL
 WALKWAY, THIS IS THE EXTERIOR OFTHE BUILDING AND NOT
 LOCATED WITHIN A MALL, PLEASE INDICATE HOW THIS
 INSTALLATION WILL MAKE A WATERTIGHT SEAL.
 1403.2. WEATHER PROTECTION. EXTERIOR WALLS SHALL
 PROVIDE THE BUILDING WITH A WEATHER-RESISTANT EXTERIOR
 WALL ENVELOPE. THE EXTERIOR WALL ENVELOPE SHALL INCLUDE
 FLASHING, AS DESCRIBED IN SECTION 1405.3 .
 1405.3 FLASHING.
 FLASHING SHALL BE INSTALLED IN SUCH A MANNER SO AS TO
 PREVENT MOISTURE FROM ENTERING THE WALL OR TO REDIRECT
 IT TO THE EXTERIOR. FLASHING SHALL BE INSTALLED AT THE
 PERIMETERS OF EXTERIOR DOOR AND WINDOW ASSEMBLIES,
 PENETRATIONS AND TERMINATIONS OF EXTERIOR WALL
 ASSEMBLIES, EXTERIOR WALL INTERSECTIONS WITH ROOFS,
 CHIMNEYS, PORCHES, DECKS, BALCONIES AND SIMILAR
 PROJECTIONS AND AT BUILT-IN GUTTERS AND SIMILAR
 LOCATIONS WHERE MOISTURE COULD ENTER THE WALL. FLASHING
 WITH PROJECTING FLANGES SHALL BE INSTALLED ON BOTH
 SIDES AND THE ENDS OF COPINGS, UNDER SILLS AND
 CONTINUOUSLY ABOVE PROJECTING TRIM.
  
 6) SHEET A401DETAIL# 2 INDICATES A STOREFRONT FRAME,
 PLEASE PROVIDE A CUT SECTION THROUGH THE STOREFRONT
 FRAME AND DOOR FRAME, THIS IS WHERE IT WOULD APPEAR A
 VERTICAL MULLION WOULD BE REQUIRED, PLEASE PROVIDE
 ADDITIONAL INFORMATION HOW THE WIND LOADS WILL BE MET
 IN 1609.6.2.2. COMPONENTS AND CLADDING.
  
 7) SHEET A402 DETAIL# 4 INDICATES THE USE OF STEEL
 STUDS, THIS WALL IS AN EXTERIOR WALL REQUIRED TO RESIST
 WIND PRESSURE PLEASE PROVIDE THE DESIGN CRITERIA FOR
 THE BEARING STUDS, (WIND) SIZE OF STUD, GAUGE OF STUD,
 AND THE SPACING REQUIREMENTS. 2508 , GA-216 OR ASTM C
 1007.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.